Browse > Article
http://dx.doi.org/10.5916/jkosme.2015.39.3.206

A Development of Methodology for NOVEC Gas Fire Extinguishing System  

Yun, Jeong-In (Energy and Marine Research Division, Korea Marine Equipment Research Institute)
Choi, Jae-Hyuk (Division of Marine System Engineering, Korea Maritime and Ocean University)
Abstract
The most important thing for NOVEC gas fire extinguishing equipment is to release NOVEC gas, which contained in the extinguishing container, to the safety section by the time appointed. For this matter, it is significant to decide arrangement and size of the proper piping equipment. This study has developed the design methodology of NOVEC gas fire extinguishing equipment in use of pipe network analysis techniques. Based on the design methodology, each design coefficient is chosen. It is found that the calculated result, which is 6.498 seconds, has been counted within the 10 seconds limit, which is fairly satisfied with extinguishing releasing time based on the developed methodology. At that time, the pressure loss is 21.09bar.
Keywords
NOVEC gas; Fire extinguishing system; Pipe network analysis; Fire extinguishing agent;
Citations & Related Records
연도 인용수 순위
  • Reference
1 M. E. Kim, "Trends of onboard fire extinguishing system," Proceedings of the KOSME Fall Conference, pp. 127-128, 2005 (in Korean).
2 NFPA, "NFPA 12-Standard on Carbon Dioxide Extinguishing Systems," National Fire Protection Association, 2011.
3 MINIMAX, "MX 1230 Fire Extinguishing System," pp. 6-13, 2014.
4 J. H. Choi and J. I. Yun, "A numerical study on pressure drop for Novec gas fire fighting system," Proceedings of the KOSME Fall Conference, pp. 233, 2014 (in Korean).
5 IMO, "MO RESOLUTION A.829(19), Guidelines for the Evaluation of the Adequacy of Type C Tank Vent Systems," 1995.