Browse > Article
http://dx.doi.org/10.5916/jkosme.2009.33.8.1123

Analysis of Performance Characteristics of a Cascade Refrigeration System with Internal Heat Exchanger using Natural Refrigerants  

Son, Chang-Hyo (부경대학교 기계공학부)
Oh, Hoo-Kyu (부경대학교 냉동공조공학과)
Abstract
In this paper, the cycle performance characteristics of a cascade refrigeration system with internal heat exchanger using natural refrigerants is presented to offer the basic design data for the operating parameters of the system. This system considered in this study is consisted of a high temperature cycle using a carbon dioxide(R744) and low temperature cycle using refrigerants such as R290, R1270, R600a and Ethane. The main results were summarized as follows : The COP of the cascade refrigeration system of R600a with internal heat exchanger is the highest grade in low temperature cycle using refrigerants such as R290, R1270, R600a and Ethane. The COP of the cascade refrigeration system with internal heat exchanger only in high temperature cycle is the highest value among three type cycle, such as only low temperature cycle, only high temperature cycle and all the cycle.
Keywords
Cascade refrigeration system; Internal heat exchanger; Performance Characteristics; Natural Refrigerant;
Citations & Related Records
연도 인용수 순위
  • Reference
1 S. Sawalha, 'Using $CO_{2}$ in supermarket refrigeration', ASHRAE J. vol. 47, no. 8, pp. 26–30, 2005
2 I. Wilson and D. Maier, "Carbon dioxide for use as a refrigerant", Refrigeration Science and Technology, Proceedings, IIR-IRHACE Conference, Innovative Equipment and Systems for Comfort and Food Preservation. The University of Auckland, pp. 305–311, 2006
3 S. N. Park and M. S. Kim, "Performance of autocascade refrigeration system using carbon dioxide and R134a", Korea J. of Air-Conditioning and Refrigeration Eng., Vol. 11, No. 6, pp. 880-890, 1999
4 S. Bhattacharyya, S. Mukhopadhyay, A. Kumar, R. K. Khurana and J. Sarkar, "Optimization of a $CO_2C_3H_8$ cascade system for refrigeration and heating", Int. J. Refrigeration 28, pp.1284–1292, 2005   DOI   ScienceOn
5 EES: Engineering Equation Solver, 2006. fChart Software Inc
6 C. Chaichana, L. Aye and W.W.S. Charters, 2003. "Natural working fluids for solar-boosted heat pumps", Int. J. Refrigeration 26, pp. 637–643, 2003   DOI   ScienceOn
7 T. S. Lee, C. H. Liu and T. W. Chen, "Thermodynamic analysis of optimal condensing temperature of cascade condenser in $CO_2/NH_3$ cascade refrigeration systems", Int. J. Refrigeration 29, pp. 1100–1108, 2006   DOI   ScienceOn
8 P. K. Bansal and S. Jain, Cascade systems: past, present, and future. ASHRAE Trans. 113 (1), pp. 245–252 (DA-07-027), 2007