Browse > Article
http://dx.doi.org/10.5806/AST.2012.25.4.230

The study of quantitative analysis for noxious gases of plastic materials by remote sensing open path FT-IR spectrometer  

Cho, Nam-Wook (Korea Institute of Construction Technology)
Cho, Won-Bo (College of Pharmacy, Dongduck Women's University)
Kim, Hyo-Jin (College of Pharmacy, Dongduck Women's University)
Publication Information
Analytical Science and Technology / v.25, no.4, 2012 , pp. 230-235 More about this Journal
Abstract
It is to use many plastic materials as living essential goods. But when the fire is happened, owing to noxious gases, many men should be injured. Therefore as the noxious gases are measured by open path FT-IR spectrometer as remote monitoring, the demage of men could be minimized. Such this system consists of a Fourier transform spectrometer and infrared lamp fitted to long length. The study was to do the quantitative analysis on CO, $NO_2$, HCl, HF gas by remote monitoring open path FT-IR spectrometer. And the method of it should use MLR (multiple linearity regression) method. As result, It was confirmed to be more than 0.95 as $R^2$ of MLR. And then Urethane and PVC of plastic materials selected was burned, the concentration of polluted gases were measured by remote monitoring method.
Keywords
open path FT-IR spectrometer; remote monitoring; MLR method;
Citations & Related Records
연도 인용수 순위
  • Reference
1 W. Lindberg, J. A. Persson and S. Wold, Anal. Chem., 55, 643-647 (1983).   DOI
2 W. F. Herget and J. D. Brasher, Opt. Eng., 19, 508-514 (1980).
3 S. N. Williams, S. J. Schaefer, V. M. L. Calvache and D. Lopez, Geochim. Cosmochim. Acta., 56, 1765-1770 (1992).   DOI   ScienceOn
4 E. L. Dreniak and G. D. Boreman, 'Infrared Detectors and Systems', John Wiley & Sons (1996).
5 A. Hadni, 'Essentials of Modern Physics Applied to the Study of the Infrared', Pergamon (1967).
6 P. M. McCormick, L. W. Thomason and C. R. Trepte, Nature, 373, 399-404 (1995).   DOI   ScienceOn
7 P. W. Francis, C. Chaffin, A. J. H. Maciejewski and C. M. M. Oppenheimer, Geophys. Res. Lett., 23, 249-252 (1996).   DOI
8 H. Martens and T. Naes, 'Multivariate Calibration (2nd edn), Vol. 1. Wiley', Chichester (1989).