Lim, Jung-Ho;Lee, Tae-Gu;Moon, Seung-Jae;Lee, Jae-Heon
66
In this inquiry, I would suggest jet ventilation system for effective elimination of welding flaw at machinery material welding shop on plant and evaluate the airstream on inner space and property of welding flaw's density through the examination. We can know outer atmosphere inflows at the speed of about 0.05m/s from western entrance in case of stopping the jet ventilation system, but airstream is accumulated on entire space. At height of worker's breathing surface(Ground Level = 1.5 m, below of GL) and welding work center, density of welding flaw on upper part(GL = 12m) is appeared 4 times higher than outer atmosphere at surplus range besides nearby of western entrance. At operation of jet ventilation system, since the smooth air current transfer at inner space and exhaust effect the wind speed is maintained at 0.932 m/s at the point of height of worker's breathing surface on inner space and it's concluded about the working conditions have been better than before operation of jet ventilation system because of that results show that inner space density of welding flaw at height of worker's breathing surface is 40.5%, and in the work shop, it is 20.3% at upper part.