Abstract
This study made a testing device to evaluate the distribution board management system. Power was supplied to the testing device using a loading-back method and the voltage applied to it was 440 V at the same turn ratio. When the human body electric shock current is 30 mA, the breaking time is set to be less than 240 ms while 30~45 mA current is flowing. The test result shows that in the case of the R-phase it was measured to be 5.19 Hz (193 ms). And the S-phase and T-phase were perfectly cut off at 5.39 Hz (186 ms) and 5.71 Hz (175 ms), respectively. When the human body electric shock current is 60mA, the breaking time is set to be less than 120 ms while 45~75 mA current is flowing. The test result shows that the R-phase, S-phase, and T-phase were accurately cut off at 8.39 Hz (11 ms), 8.87Hz (113 ms) and 9.69 Hz (103 ms), respectively. When the human body electric shock current is 90 mA, the breaking time is set to be less than 48 ms while 75 mA current is flowing. The test result shows that the R-phase, S-phase, and T-phase were accurately cut off at 19.8 Hz (50.4 ms), 16.9 Hz (59.2 ms), and 17.9 Hz (56.0 ms), respectively. That is, the developed testing device satisfied all the requirements of the distribution board evaluation criteria, and it becomes available for the performance evaluation of the distribution board management system.