Abstract
In 2018, overload, overcurrent, insulation aging, and a contact failure caused 659 electric fires. There is almost no failure of electrical socket outlets during their manufacturing or installation period. After several months or several years, overload or overcurrent of electrical socket outlets leads to a contact failure or short circuit which causes an electric fire. Therefore, this paper analyzed for thermal characteristics based on a current value and the change in insulation resistance along with a temperature rise caused by electrical socket outlets and the state of laboratory use in workplaces. As a results, regarding the thermal characteristics based on the current value of each installation year, a temperature increase was related to a current value, an installation year, and whether the contact unit is corroded. Insulation resistance began to decrease when a temperature increased to a certain level. With a lapse of installation year, the temperature at which insulation resistance began to decrease was lowered. This paper can be applicable for the survey data about electrical socket outlet induced fire accidents and management guidelines.