DOI QR코드

DOI QR Code

Analysis of the Causes of Multiple Casualties in an Electronics Factory Fire

전자공장 화재의 다수 사상자 발생원인 분석

  • Lee, Eui-Pyeong (Department of Fire Safety Engineering, Jeonju University)
  • 이의평 (전주대학교 소방안전공학과)
  • Received : 2019.07.10
  • Accepted : 2019.08.08
  • Published : 2019.08.31

Abstract

The electronics factory fire, that occurred at 15:40 on August 21, 2018, killed nine people and injured six. This study analyzes the causes of many of the casualties from the fire, and is based on fire investigation results and so on. The findings suggest that major causes included failure of the automatic alarm system to function, failure of the emergency broadcasting system to function, the fire suddenly spreading due to polyurethane foam in a ceiling on the 4thfloor, a power outage immediately after the fire started, a sprinkler system that was not working, a delay in reporting the fire, and improper management of fire facilities by a fire safety management company.

2018년 8월 21일 15시 40분경 발생한 전자공장화재로 9명이 사망하고 6명이 부상을 입는 인명피해가 발생하였다. 이 논문에서는 이 전자공장화재에서 다수 사상자가 발생한 원인을 화재조사결과 등을 토대로 구체적으로 분석하고 있다. 다수 사상자가 발생한 주요 원인은 자동화재탐지설비 기능 정지, 비상방송시설 기능 정지, 4층 천장의 우레탄폼 착화로 인한 급격한 화재 확산, 화재발견 직후 정전 발생, 스프링클러설비 미작동, 화재신고 지연, 소방시설관리 업체의 소방시설관리 부실 등으로 분석하였다.

Keywords

References

  1. S. C. Jeong, "Case Study on the Daegu Subway Fire Disaster Accident in 2003", Master's Thesis, Kyungbook National University (2004).
  2. T. H. Kim, "Analysis for Daegu Subway Fire", Proceeding of 2003 Autumn Conference, The Society of Air-Conditioning and Refrigerating Engineers of Korea, pp. 240-248 (2003).
  3. M. S. Hur, "A Study on Fire Prevention and Safety Facilities based on Investigation Report on Cold Storage Fire Case", Proceedings of 2009 Autumn Annual Conference, Korean Institute of Fire Science & Engineering, pp. 204-209 (2009).
  4. E. P. Lee, "Problems and Measures to Prevent Recurrence of Cold Storage Fire", Journal of the Architectural Institute of Korea Planning & Design, Vol. 24, No. 12, pp. 39-46 (2008).
  5. Y. B. Lee, C. H. Jeong, T. J. Jeong and H. Kim, "An Experimental Study on the Fire Characteristic of National Museum", Journal of the Fire Investigation Society & Equipment Technology, Vol. 3, No. 2, pp. 81-88 (2012).
  6. E. P. Lee, "Analysis of the Causes of Catastrophic Damage of Goyang Bus Terminal Fire and the Preventive Measures for Similar Catastrophic Fires", Journal of Scientific Criminal Investigation, Vol. 12, No. 1, pp. 39-48 (2018). https://doi.org/10.20297/jsci.2018.12.1.39
  7. S. B. Choi and D. M. Choi, "A Study on Fire Risk of Apartment House with Pilotis Structure - Focused on the Fire case of Uijeongbu-si Urban Living Homes -", Fire Science and Engineering, Vol. 30, No. 3, pp. 48-54 (2016). https://doi.org/10.7731/KIFSE.2016.30.3.048
  8. E. P. Lee, "Analysis of Causes of Casualties in Jecheon Sports Center Fire - Focus on Structural Factors of Building and Equipment -", Fire Science and Engineering, Vol. 32, No. 4, pp. 86-94 (2018). https://doi.org/10.7731/KIFSE.2018.32.4.086
  9. B. Y. Oh. "A Study on the Fire Risk of Special Combustible Materials", Master's Thesis, Gacheon University, p. 56 (2004).
  10. E. P. Lee, "Analysis of the Actual Conditions of Fire Outbreak and its Preventive Measures during New Construction of Buildings", Journal of the Architectural Institute of Korea Planning & Design, Vol. 24, No. 10, pp. 97-104 (2008).
  11. H. K. Kim, S. H. Park and T. H. Jung, "A Study on the Alternatives for Fire Safety Management by Warehouse Fire Analysis", Proceedings of 2009 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 598-605 (2009).