DOI QR코드

DOI QR Code

Study of High-capacity Foam Discharging Systems for Full Surface Fire of Big Oil Tanks

대형 유류저장탱크 전면화재 대응을 위한 대용량포방사시스템 연구

  • Im, Joo-Yeol (Graduate School of Industry & Science, Kangwon National Univ.) ;
  • Chung, Yeong-Jin (Dept. of fire Protection Engineering, Kangwon National Univ.)
  • 임주열 (강원대학교 산업과학대학원) ;
  • 정영진 (강원대학교 소방방재공학과)
  • Received : 2019.10.25
  • Accepted : 2019.11.23
  • Published : 2019.12.31

Abstract

Oil tank fires need to be suppressed differently from other oil-related fires, due to the high-temperature flames and hot updraft above the tank, in the former case, that cause the destruction of large amounts of foam. We studied high-capacity foam discharge systems based on the standards of the American Petroleum Institute (API), National Fire Protection Association (NFPA), British Standard European Norm (BS EN), and the laws of Japan. The performance of a high-capacity foam discharge system was measured by conducting real fire experiments with model oil tanks. We concluded that lightweight and easily movable high-capacity foam discharge systems should be urgently introduced in domestic operations. Additionally, the obstacles faced by major tanks, such as long-distance installation of large-diameter fire hoses and narrowing of firefighting spaces, should be resolved depending on the conditions of the site.

유류탱크 화재는 화재진압이 쉽지 않다. 미국, 일본, 싱가포르 등의 국가에서는 오랜 시행착오 끝에 대형 유류저장탱크의 전면화재에 대응하기 위한 대용량의 포방사 시스템을 도입하였다. 본 연구에서는 American Petroleum Institute (API), National Fire Protection Association (NFPA), British Standard European Norm (BS EN)의 관련 기준과 일본의 법령 등을 바탕으로 대용량 포방사에 대한 기준과 방법 등을 연구하였고, 모형탱크 전면화재 진압 비교실험을 통해 대용량 포방사의 성능을 확인하였다. 그 결과 소용량의 노즐 여러 개를 사용하는 것보다 대용량의 노즐 하나를 사용하는 대용량 포방사가 화재진압 성능이 더 우수 하였고, 노즐의 배치를 달리하여 서로 다른 방향에서 방사하는 것보다 동일한 방향에서 집중 방사하는 것이 더욱 효과적이었다. 결국 대용량포방사시스템의 국내도입 필요성을 확인하였다. 그러나 대용량포방사시스템의 운용은 현장 여건에 따라서는 매우 제한적일 수밖에 없다. 따라서 시스템을 최대한 경량화 되고 이동이 쉬운 것으로 도입하여야 한다. 또한 주요 탱크별로 운영계획을 수립하면서 대구경 소방호스의 장거리 설치문제, 소방활동 공간의 협소문제 등 파악되는 장애요인을 현장 여건에 따라 해결해 나가는 것이 현실적 방안으로 보인다.

Keywords

References

  1. National Fire Agency, "White Paper on the Goyang Oil Tank Fire Response", pp. 12-33 (2019).
  2. H. Persson and A. Lonnermark, "Tank Fires, Review of fire incidents 1951-2003, BRANDFORSK Project 513-021", Sweden : SP Swedish National Testing and Research Institute, pp. 5-7 (2004).
  3. United Stated Patent, "Method For Extinguishing Tank Fires", Patent Number 5566766A, Retrieved from https://patents.google.com/patent (1996).
  4. Fire and Disaster Management Office, "Training manual of Disaster Prevention Headquarters of Petrochemical Complex", Ministry of Internal Affairs, Japan (2016).
  5. Fire and Disaster Management Office, "Disaster Prevention Measures at Petrochemical Complexes in Japan", Ministry of Internal Affairs, Japan, pp. 33-37 (2017).
  6. Singapore Civil Defence Academy, "Oil Refinery Fires", Singapore, pp. 40-75 (2016).
  7. Protec Group, "Fire Protection for Fuel Storage Facilities", Retrieved by https://slideplayer.com, p. 6 (2009).
  8. American Petroleum Institute, "API RP 2021 Management of Atmospheric Storage Tank Fires", 4th ed., Washington DC. p. 4 (2001).
  9. American Petroleum Institute, "API RP 2021 Management of Atmospheric Storage Tank Fires", 4th ed., Washington DC. pp. 16-17 (2001).
  10. British Standard Institution, "BS EN 13565-2 Fixed Firefighting Systems-Foam Systems Part 2: Design, Construction and Maintenance", London, UK (2009).
  11. National Fire Protection Association, "NFPA 11 Standard for Low-Expansion Foam", 2016 Ed., Qincy, MA, USA, p. II-63 (2016).
  12. ChemGuard, "Storage Tank Protection High Flow Monitors, DATA SHEET #D10D03191", REVISION: 09 (2005).
  13. Ministry of Internal Affairs, "Petroleum Complex Disaster Prevention Act Ordinance(No.129)", Japan (1976).
  14. Y. H. Lee, "Guide on the Fire facilities for Refinery and Petro-Chemical Plant", Korea Occupational Safety & Health Agency, pp. 13-14 (2012).