Study on Characteristics of Leakage Current and Insulation Resistance for a Circuit According to Load Types

부하종류에 따른 회로의 누설전류 및 절연저항 특성 연구

  • Received : 2019.04.01
  • Accepted : 2019.06.13
  • Published : 2019.06.30

Abstract

The ratios of compliant branch circuit of leakage current and insulation resistance were 68.4% and 90.8%, respectively at the lamp load, 64.6% and 96.5% at the heat load, 86.7% and 88.9% at the power load. Limit of residual current of the zero phase secondary current value at the zero phase primary current was 100 A when rated primary current 400 A more than. The reason why the ratio of branch circuit of the leakage current was less than the ratio of compliant branch circuit of the insulation resistance might be that the leakage current includes the capacitive leakage current and the zero phase current.

본 논문에서는 전기재해를 일으킬 수 있는 요소를 미리 제거하기 위해 전등부하, 전열부하, 동력부하를 대상으로 누설전류와 절연저항을 측정하여 분포비율과 누적비율을 비교하고 분석하여 보다 효과적이고 신뢰성 있는 누설전류 검출방법을 찾고자 하였다. 누설전류와 절연저항의 적합 비율 차이는 전열부하 32.5%, 전등부하 22.8%, 동력부하 2.2%의 순으로 나타났으며, 누설전류계가 낮은 적합 비율을 나타내었으며, 누설전류계는 측정방법에 따른 오차와 용량성 누설전류 및 영상전류가 포함되어 있기 때문으로 생각되었다.

Keywords

JGGJB@_2019_v23n2_364_f0001.png 이미지

Fig. 1. ZCT in steady-state. 그림 1. 정상 상태의 ZCT

JGGJB@_2019_v23n2_364_f0002.png 이미지

Fig. 2. ZCT in leakage state. 그림 2. 누설 상태의 ZCT

JGGJB@_2019_v23n2_364_f0003.png 이미지

Fig. 3. Distribution of leakage current and insulation resistance at lamp load. 그림 3. 전등부하의 누설전류와 절연저항의 분포

JGGJB@_2019_v23n2_364_f0004.png 이미지

Fig. 4. Distribution of leakage current and insulation resistance at heat load. 그림 4. 열부하의 누설전류와 절연저항의 분포

JGGJB@_2019_v23n2_364_f0005.png 이미지

Fig. 5. Distribution of leakage current and insulation resistance at power load. 그림 5. 동력부하의 누설전류와 절연저항의 분포

JGGJB@_2019_v23n2_364_f0006.png 이미지

Fig. 6. leakage current and insulation resistance by load type. 그림 6. 부하별 누설전류와 절연저항

Table 1. Tolerance of zero phase current transformer. 표 1. 영상 변류기의 허용오차

JGGJB@_2019_v23n2_364_t0001.png 이미지

Table 2. Residual current limit of zero phase current transformer. 표 2. 영상 변류기의 전류 한계

JGGJB@_2019_v23n2_364_t0002.png 이미지

Table 3. Standard and error range of insulation meter. 표 3. 절연저항계의 표준과 허용오차

JGGJB@_2019_v23n2_364_t0003.png 이미지

Table 4. Leakage current and insulation resistance by load type. 표 4. 부하별 누설전류와 절연저항

JGGJB@_2019_v23n2_364_t0004.png 이미지

References

  1. Y. H. Kim, "Consideration of Electrical Fire Prevention Measures Combing Electrical Fire Statistics and Cases," Hanyang University Graduate School, p.10, 2017.
  2. D. W. Joo, "A Study on Prevention and Improved Statistical Classification of Electrical Fire Based on Statistics and Case Analysis," Seoul City University Graduate School, p.1, 2017.
  3. H. M. Park, "Improvement of Electric Safety Management through Analysis for Check List of Electric Safety Management Agency," Seoul National University of Science & Technology Graduate School, p.9, 2017.
  4. Korea Electrical Safety, Corporation Statistical analysis of electricity disaster in 2016, No.26, 2016.
  5. M. I. Choi and others, J. KIIEIE, No.23, p.83, 2009.
  6. N. K. Joo and others, KIEE symposium, p.172, 2009.
  7. C. S Choi, S. Y. Han, KIEE symposium, p.301, 2008.
  8. K. C. Han, Master Thesis, Dongshin Univ. 2018.

Cited by