DOI QR코드

DOI QR Code

A Study for the Fire Analysis and Igniting Cause of Freezing Protection Heating Cables

동파방지열선 화재 흔적분석과 발화원인 연구

  • Received : 2018.03.13
  • Accepted : 2018.05.21
  • Published : 2018.06.30

Abstract

There have been a number of major fatal fire accidents in Korea recently. The number of fires in 2017 were 44,178, which is not only increasing number of fires but also increasing in casualties. Particularly, the fire at Jecheon Sports Center, which suffered many casualties, is expected to have a huge impact. The cause of the fire has not been determined yet, but heat waves on the ceiling have also been pointed out. As such, the copper heating waves, which are used as a preventive measure against damage of pipes due to freezing of pipes, etc., always have a fire hazard. To determine the possibility of a flame-resistant heated fire, a positive electric cable product was used to artificially ignite and analyze the results. In case of a short circuit, the external covering of the positive electric cable is damaged, but not short circuit unless the heating material surrounding the wire is damaged. Due to the characteristics of heating cable for preventing copper waves, the chances of insulation becoming more severe due to moisture and temperature changes are higher than normal wires. If the internal heating system is carbonized by insulating deterioration without damage to the outer coating, it is likely to cause trekking, to form a winding loop in the heating materials, and to cause short circuit in the heated materials. For the positive temperature line, if the middle is shorted, the current continues to flow to the short circuit unless the breaker disconnects. Consequently, a heated fire that does not cut off the power immediately may leave multiple marks or cuts.

Keywords

References

  1. National Fire Emergency Management Agency, "National Fire Data", National Fire Information System, 2017.
  2. J. H. Lee and J. R. Park, "A Study on the Potential of the Fire Resistance of the Hot Heat Storage System", Buan Fire Station in Jeonbuk Province, 2018.
  3. H. I. Lee, "An Experimental Study on the Evaluation of the Risk and cause of Fire in the Heat Electric Cable", Daejeon Fire Station, 2017.
  4. Korea Electrical Safety Corporation's Institute, "Electrical Safety Education", Korea Electrical Safety Corporation's Institute, 2017.
  5. Kirk, "Kirk's Fire Investigation(6th edition) Chapter 10 Electric fire", 2017.