Performance Analysis on a Heat Pump System using Waste Heat

폐열이용 열펌프시스템의 성능에 관한 연구

  • Park, Youn Cheol (Department of Mechanical Engineering, Jeju National University) ;
  • Song, Lei (Department of Mechanical Engineering, Graduate School, Jeju National University) ;
  • Ko, Gwang Soo (Department of Mechanical Engineering, Graduate School, Jeju National University)
  • 박윤철 (제주대학교 기계공학과) ;
  • 송뢰 (제주대학교 일반대학원 기계공학과) ;
  • 고광수 (제주대학교 일반대학원 기계공학과)
  • Received : 2018.11.01
  • Accepted : 2018.11.28
  • Published : 2018.12.01

Abstract

This study was conducted for analysis of a heat pump system using waste heat in an enclosed space such as a green house. The model was developed with mathematical equations in literature and Engineering Equation Solver (EES) was used to get the solution of the developed equations. The simulation results have 5% of reliability comparing the results with actual test data of heat pump system's dynamic operation. The operating performance of the system was calculated with variation of working fluid temperature in the thermal storage tank such as $25^{\circ}C$, $35^{\circ}C$, $45^{\circ}C$ and $55^{\circ}C$. As a result, the system's the highest total heating capacity shows 280 kWh and the storage tank's operating time decreased as the starting storage tank's temperature was high.

Keywords

JOOJBH_2018_v14n4_53_f0001.png 이미지

Fig. 1. Flow chart of heat pump system simulation.

JOOJBH_2018_v14n4_53_f0002.png 이미지

Fig. 2. Schematic of heat storage tank source heating mode and outdoor air source heating mode.

JOOJBH_2018_v14n4_53_f0003.png 이미지

Fig. 3. Comparison of the experimental and simulated data for compressor power.

JOOJBH_2018_v14n4_53_f0004.png 이미지

Fig. 4. Comparison of the experimental and simulated data for heating capacity.

JOOJBH_2018_v14n4_53_f0005.png 이미지

Fig. 5. Comparison of the experimental and simulated data for COP at thermal storage mode.

JOOJBH_2018_v14n4_53_f0006.png 이미지

Fig. 6. Indoor and outdoor temperature variation with time when storage tank water temperature start at 25℃.

JOOJBH_2018_v14n4_53_f0007.png 이미지

Fig. 7. Indoor and outdoor temperature variation with time when storage tank water temperature start at 35℃.

JOOJBH_2018_v14n4_53_f0008.png 이미지

Fig. 8. Indoor and outdoor temperature variation with time when storage tank water temperature start at 45℃.

JOOJBH_2018_v14n4_53_f0009.png 이미지

Fig. 9. Indoor and outdoor temperature variation with time when storage tank water temperature start at 55℃.

JOOJBH_2018_v14n4_53_f0010.png 이미지

Fig. 10. Comparison of heating and thermal storage capacity with different initial water temperature of thermal storage tank.

JOOJBH_2018_v14n4_53_f0011.png 이미지

Fig. 11. Comparison of operating time of heating and thermal storage mode with different initial water temperature of thermal storage tank.

Table 1. Numerical value of A and B in equations

JOOJBH_2018_v14n4_53_t0001.png 이미지

References

  1. J. J. Allen and J. F. Hamilton, 1983, Steady-state reciprocating water chiller models, ASHRAE Transactions, Vol. 84, No. 2, pp. 398-407.
  2. M. W. Browne and P. K. Bansal, 1998, Steady-state model of centrifugal liquid chillers, Int. J. Refrigeration, Vol. 2, No. 1, pp. 343-358.
  3. Z. C. Qin, 2007, Simulation and experimental research of air-source heat pump with the refrigerant R410A, Nanjing Normal University.
  4. L. Yang, 2012, Model-based robust design method of refrigeration system, Institute of Refrigeration & Cryogenics School of Mechanical Engineering, Shanghai Jiao Tong University.
  5. Z. C. Qin, 2007, Simulation and experimental research of air-source heat pump with the refrigerant R410A, Nanjing Normal University, pp. 18-21.
  6. M. M. Shah, 1979, A general correlation for heat transfer during film condensation inside pipes, Int J of Heat Mass Transfer, Vol. 22, No. 4, pp. 547-556. https://doi.org/10.1016/0017-9310(79)90058-9
  7. L. M. Schlager and M. B. Pate, 1990, Performance predictions of refrigerant-oil mixtures in smooth and internally finned tubes-part1: literature review, ASHRAE Transactions, Vol. 96, No. 1, pp. 160-169.
  8. W. Li and W. Q. Tao, 1997, Experimental study on heat transfer and pressure drop characteristics for fin-and-tube heat exchangers, Journal of Mechanical Engineering, Vol. 97, No. 1, pp. 81-86.
  9. F. Qiu and B. Gu, 2010, Simulation on heat transfer and pressure drop of R410A two-phase flow in plate heat exchanger, Journal of Refrigeration, Vol. 31, No. 1, pp. 39-44. https://doi.org/10.3969/j.issn.0253-4339.2010.01.039
  10. Y. Y. Yan and T. F. Lin, 1999, Evaporation heat transfer and pressure drop of refrigerant R134a in a plate heat exchanger, Journal of Heat Transfer, Vol. 121, pp. 118-127. https://doi.org/10.1115/1.2825924
  11. Y. Y. Yan and T. F. Lin, 1999, Condensation heat transfer and pressure drop of refrigerant R134a in a plate heat exchanger, Int. J. of Heat Mass Transfer, Vol. 42, pp. 993-1006. https://doi.org/10.1016/S0017-9310(98)00217-8
  12. G. A. Carlson, http://www.ece.rochester.edu/courses/ECE111/error_uncertainty.pdf.
  13. K. Jo, 2017, Empirical Study on a Thermal Storage Type Hybrid Heat Pump System for Greenhouse, Master thesis of Jeju National University.