Study of Comparison on Energy Consumption Based on HVAC area along Floor in High Rise Building

고층빌딩의 층별 에너지 사용량 비교에 관한 연구

  • Park, Woo-Pyeng (Graduate School, Department of Architectrual Engineering, Kyonggi University) ;
  • Choi, Byong-Jeong (Department of Architectrual Engineering, Kyonggi University) ;
  • Kim, Jin-Ho (Building Technology Department, Suwon Science College)
  • 박우평 (경기대학교 대학원 건축공학과) ;
  • 최병정 (경기대학교 건축공학과) ;
  • 김진호 (수원과학대학교 건축기계설비과)
  • Received : 2018.08.07
  • Accepted : 2018.11.29
  • Published : 2018.12.01

Abstract

In this study, the energy consumption of the typical floor was compared by the total energy comsumption of the building in highrise building. In gerneral, many researchers are studying on the typical floor in highrise buildings for avoiding complexity in energy simulation. But few papers are studied on energy consumption along the floors. In the model bulding, the energy consumption data were acquired by BEMS system in 2011. According the data, the total net energy consumption was $193.99kWh/m^2$ for all area and the total net energy consumption was $247.61kWh/m^2$ for HVACR area. The total electricity and gas energy are used 47.7% for heating and cooling, 33.5% for lighting and plug, 12.9% for conveyance power and 5.9% for restaurant. In comparison of only ground floor, amount of energy consumption in the lobby is 10%, and 90% of total energy consumption is used in the typical floor. For this result, energy simulation on the typical floor is acceptable for calculating the total energy consumption in the highrise building.

Keywords

JOOJBH_2018_v14n4_1_f0001.png 이미지

Fig. 1. Typycal Floor Plan.

JOOJBH_2018_v14n4_1_f0002.png 이미지

Fig. 2. Schematic of BEMS.

JOOJBH_2018_v14n4_1_f0003.png 이미지

Fig. 3. Screen View of Web version.

JOOJBH_2018_v14n4_1_f0004.png 이미지

Fig. 4. Net Energy Consumption along Floor.

JOOJBH_2018_v14n4_1_f0005.png 이미지

Fig. 5. Net Energy Consumption Ratio along Floor.

JOOJBH_2018_v14n4_1_f0006.png 이미지

Fig. 6. Net Energy Consumption Restaurant along Floor without Restaurant and Fitness.

Table 1. Building Outlines

JOOJBH_2018_v14n4_1_t0001.png 이미지

Table 2. Floor Usage

JOOJBH_2018_v14n4_1_t0002.png 이미지

Table 3. HVAC&R System

JOOJBH_2018_v14n4_1_t0003.png 이미지

Table 4. Enegy Intensity

JOOJBH_2018_v14n4_1_t0004.png 이미지

Table 5. Energy Consumption Rate for Usages

JOOJBH_2018_v14n4_1_t0005.png 이미지

References

  1. Korea Energy Management Corporation, 2015 Korea Energy Handbook, pp. 16, 2015.
  2. H. T. Seok, S. Y. Song, I. H. Yang, J. M. Choi, and K. W. Kim, Sensitivity Analysis of Building Energy Factors, '1998 Summer Conference of SAREK, pp. 1317-1322, 1998.
  3. J. H. Kim, W. P. Park, S. H. Shin, J. K. Min, and D. H. Kim, An Analysis on Building Energy Load along Core Position, Area Ratio and Orientation, J. of KSGEE, Vol. 9, No. 1, pp. 15-19, 2013.
  4. J. K. Cho, J. H. Kim, S. J. Lee, and H. S. Kang, Interaction Analysis between Cooling-to-Heating Load Ratio and Primary Energy Consumption of HVAC&R System for Building Energy Conservation, J. of SAREK, Vol. 27, No. 3, pp. 113-122, 2015.
  5. J. K. Cho, J. H. Kim, S. J. Lee, and J. M. Koo, A Bi-Directional Systematic Design Approach to Energy Optimization for Energy-Efficient Buildings, Energy and Buildings, Vol. 120, pp. 135-144, 2016. https://doi.org/10.1016/j.enbuild.2016.03.066
  6. J.-K. Cho, S.-J. Lee, J.-H. Kim, and S.-H. Shin, Energy Consumption Characteristic of Office Building HVAC&R Systems, J. of AIK, Vol. 28, No. 9, pp. 251-260, 2012.
  7. S.-G. Yong, J.-H. Kim, Y. Gim, J. Kim, J. Cho, H. Hong, Y.-J Baik, and J. Koo, Impacts of Building Envelope Design Factors upon Energy Loads and Their Optimization in US Standard Climate Zones using Experimental Design, Energy and Buildings, Vol. 141, pp. 1-15, 2017. https://doi.org/10.1016/j.enbuild.2017.02.032
  8. KEEI, Energy Consumption Survey the 12th Ed. (2014), pp. 654, 658, 2015.