Influence of multi-component ground motions on seismic responses of long-span transmission tower-line system: An experimental study

  • Tian, Li (School of Civil Engineering, Shandong University) ;
  • Ma, Ruisheng (School of Civil Engineering, Shandong University) ;
  • Qiu, Canxing (School of Civil Engineering, Shandong University) ;
  • Xin, Aiqiang (School of Civil Engineering, Shandong University) ;
  • Pan, Haiyang (School of Civil Engineering, Shandong University) ;
  • Guo, Wei (School of Civil Engineering, Central South University)
  • Received : 2018.08.25
  • Accepted : 2018.10.08
  • Published : 2018.12.25

Abstract

Seismic performance is particularly important for life-line structures, especially for long-span transmission tower line system subjected to multi-component ground motions. However, the influence of multi-component seismic loads and the coupling effect between supporting towers and transmission lines are not taken into consideration in the current seismic design specifications. In this research, shake table tests are conducted to investigate the performance of long-span transmission tower-line system under multi-component seismic excitations. For reproducing the genuine structural responses, the reduced-scale experimental model of the prototype is designed and constructed based on the Buckingham's theorem. And three commonly used seismic records are selected as the input ground motions according to the site soil condition of supporting towers. In order to compare the experimental results, the dynamic responses of transmission tower-line system subjected to single-component and two-component ground motions are also studied using shake table tests. Furthermore, an empirical model is proposed to evaluate the acceleration and member stress responses of transmission tower-line system subjected to multi-component ground motions. The results demonstrate that the ground motions with multi-components can amplify the dynamic response of transmission tower-line system, and transmission lines have a significant influence on the structural response and should not be neglected in seismic analysis. The experimental results can provide a reference for the seismic design and analysis of long-span transmission tower-line system subjected to multi-component ground motions.

Keywords

Acknowledgement

Supported by : National Natural Science Foundation of China

References

  1. Bai, F.L., Hao, H., Bi, K.M. and Li, H.N. (2011), "Seismic response analysis of transmission tower-line system on a heterogeneous site to multi-component spatial ground motions", Adv. Struct. Eng., 286(3), 565-585.
  2. GB 18306-2015 (2015), Seismic Ground Motion Parameters Zonation Map of China, Standardization Administration of China Press, Beijing, China.
  3. GB 50260-2013 (2013), Code for Seismic Design of Electrical Installations, China Architecture & Building Press, Beijing, China.
  4. Ghobarah, A. and Aziz, T.S. (1996), "El-Attar M. response of transmission lines to multiple support excitation", Eng. Struct., 18(12), 936-946. https://doi.org/10.1016/S0141-0296(96)00020-X
  5. Hall, J.F., Holmes, W.T. and Somers, P. (1996), "Northridge earthquake of January 17, 1994", Earthquake Engineering Research Institute, California, USA.
  6. Lei, Y.H. and Chien, Y.L. (2009), "Seismic analysis of transmission towers under various line configurations", Struct. Eng. Mech., 31(3), 241-264 https://doi.org/10.12989/sem.2009.31.3.241
  7. Li, H.N., Shi, W.L. and Jia, L.G. (2004), "Limitations of effects of lines on in-plane vibration of transmission towers and simplified seismic calculation method", J. Vib. Control., 23(2), 1-7.
  8. Li, H.N., Shi, W.L., Wang, G.X. and Jia, L.G. (2005), "Simplified models and experimental verification for coupled transmission tower-line system to seismic excitations", J. Sound. Vib., 286(3), 565-585.
  9. Lu, X.L., Chen, Y. and Mao, Y.J. (2012), "Shaking table model test and numerical analysis of a super tall building with high-level transfer storey", Struct. Des. Tall Spec. Build., 21(10), 699-723. https://doi.org/10.1002/tal.632
  10. NCREE (1999), Investigation Report of Chi-Chi Earthquake, National Center for Research on Earthquake Engineering, Taiwan.
  11. Park, H.S., Choi, B.H., Kim, J.J. and Lee, T.H. (2016), "Seismic performance evaluation of high voltage transmission towers in South Korea", KSCE J. Civil Eng., 20(6), 2499-2505. https://doi.org/10.1007/s12205-015-0723-3
  12. Sedov, L. (1959), Similarity and Dimensional Methods in Mechanics, CRC Press.
  13. Shinozuka, M. (1995), "The Hanshin-Awaji earthquake of January 17, 1995 Performance of life lines", Report NCEER-95-0015, NCEER.
  14. Tian, L., Gai, X. and Qu, B. (2017b), "Shake table tests of steel towers supporting extremely long-span electricity transmission lines under spatially correlated ground motions", Eng. Struct., 132, 791-807. https://doi.org/10.1016/j.engstruct.2016.11.068
  15. Tian, L., Gai, X., Qu, B., Li, H.N. and Zhang, P. (2016), "Influence of spatial variation of ground motions on dynamic responses of supporting towers of overhead electricity transmission systems: an experimental study", Eng. Struct., 128, 67-81. https://doi.org/10.1016/j.engstruct.2016.09.010
  16. Tian, L., Li, H.N. and Liu, G.H. (2012), "Seismic response of power transmission tower-line system under multi-component multi-support excitations", J. Earthq. Tsunami, 6(4), 1250025-1-21. https://doi.org/10.1142/S179343111250025X
  17. Tian, L., Ma, R.S., Li, H.N. and Zhang, P. (2014), "Seismic Response of straight line type and broken line type transmission lines subjected to non-uniform seismic excitations", Adv. Steel. Constr., 10(1), 85-98.
  18. Tian, L., Niu, Y.H., Ma, R.S., Li, X.J., Yi, S.Y., Xin, A.Q. and Guo, W. (2017c), "Design study on shaking table test model of a long span transmission tower-line system coupling system", World Earthq. Eng., 33(3), 42-50.
  19. Tian, L., Pan, H.Y., Ma, R.S. and Qiu C.X. (2017a), "Collapse simulations of a long span transmission tower-line system subjected to near-fault ground motions", Earthq. Struct., 13(2), 211-220. https://doi.org/10.12989/EAS.2017.13.2.211
  20. Wang, W.M., Li, H.N. and Tian, L. (2013), "Progressive collapse analysis of transmission tower-line system under earthquake", Adv. Steel. Constr., 9(2), 161-174.
  21. Zhang, M.Z. (1997), "Study on similitude laws for shaking table tests", Earthq. Eng. Eng. Vib., 17(2), 52-58.
  22. Zhou, Y. and Lu, X.L. (2012), Method and Technology for Shaking Table Model Test of Building Structures, Science Press, Beijing, China.

Cited by

  1. Seismic and collapse analysis of a UHV transmission tower-line system under cross-fault ground motions vol.19, pp.6, 2020, https://doi.org/10.12989/eas.2020.19.6.457