Abstract
Internal factors having effects on compressive strength test results of concrete include size, shape, height-diameter ratio(h/d), section processing method, dryness and wetness, etc. of the specimen. As it is difficult to ensure dimensions of core specimen due to rebar cutting from rebar spacing, wall thickness, effects on the structure, etc. when taking core of the concrete structure, correction of dimensions and h/d of the specimen become important for quality control of the concrete. Thus, in order to review effects of specimen size and height-diameter ratio for the concretes with compressive strength within 40~60MPa, this study has experimentally reviewed compressive strength test values by applying correction factors pursuant to KS F 2422 (Method of obtaining and testing drilled cores and sawed beams of concrete), when changing specimen diameter to ${\emptyset}5{\sim}15cm$, and h/d to 2.0~1.25.
콘크리트의 압축강도에 영향을 미치는 요인에는 공시체의 치수, 형상, 길이비(h/d), 단면 처리방법 및 공시체의 건습 등을 들 수 있다. 콘크리트 구조물의 코어 채취 시, 배근 간격에 의한 철근 절단, 벽두께, 구조물에 미치는 악영향 등을 고려할 때, 공시체 치수나 길이비를 2/1로 맞추기가 어려우므로 품질 관리 시 공시체 치수 및 길이비에 대한 강도의 보정이 필요하다. KS의 경우, 콘크리트에서 절취한 코어 나 보의 강도 시험 방법에서 길이비에 대한 보정 계수를 정하고 있으나, 최근 콘크리트의 고강도화가 진행됨에 따라 이를 일괄적으로 적용하기에는 다소 무리가 있다는 연구가 보고되고 있다. 본 연구에서는 압축강도 40~60MPa 범위의 콘크리트를 대상으로 공시체 크기와 길이비의 영향(이하 길이효과)과 길이비를 2/1로 유지하면서 치수의 변화에 따른 강도추이를 검토하기 위해 공시체 직경을 ${\emptyset}5{\sim}15cm$, 길이비를 2.0~1.25로 변화시킨 경우의 압축강도 시험 값을 KS F 2422에 의한 보정 계수와 비교하고, 고강도 콘크리트에의 적용 가능성을 확인하는데 그 목적이 있다.