Leakage experiments and applications of leakage detection algorithm in the pilot plant of water distribution system

상수관망 파일럿플랜트에서의 누수실험 및 누수탐지 알고리즘의 적용

  • Received : 2017.05.16
  • Accepted : 2017.07.18
  • Published : 2017.09.30

Abstract

In this study, algorithm for the selecting the optimum monitoring location and leakage detection algorithm based on back tracing calculation method were developed and verified by the experiments in pilot plant of water distribution system. First of all, optimum monitoring locations were selected and pressure changes were measured due to artificial leakage by pressure gauges in pilot plant. Simulations of leakage detection was performed for the verification of back tracing calculation method as a leakage detection method. From the results, it was found that leakage locations and leakage amount were exactly estimated. Various leakage amount from $0.0005m^3/s$ to $0.0018m^3/s$ were reproduced and leakage location was detected by back tracing calculation method. It was verified that back tracing calculation method as a leakage detection method is effective.

본 연구에서는 상수관망의 최적 수압모니터링 지점선정 알고리즘과 역추적 계산법을 이용한 누수탐지 알고리즘을 개발하였고 파일럿 플랜트에서 실험을 통해 검증하였다. 먼저 누수탐지를 위한 최적의 모니터링 지점선정을 선정하고 압력계를 설치하여 누수로 인한 압력변위를 측정하였다. 누수탐지를 위한 역추적계산법의 검증을 위하여 누수탐지를 수행하였고 파일럿플랜트에서 실제 재현된 누수의 지점과 누수량을 정확하게 산정하였다. 누수량을 $0.0005m^3/s$로부터 $0.0018m^3/s$까지 변화시키며 누수를 재현하였고 누수지점에 근접한 장소를 찾는데 성공하였다. 본 연구에서는 실험을 통해서 누수탐지기법으로 사용된 역추적계산법이 유효함을 검증할 수 있었다.

Keywords

References

  1. Chung, G. H., Chang, D. I., Yoo, D. G., Jun, H. D., and Kim, J. H. (2009). "Determination of optimal pressure monitoring locations for water distribution." Journal of Korea Water Resources Association, Vol. 42, No. 7, pp. 537-546. https://doi.org/10.3741/JKWRA.2009.42.7.537
  2. Ha, S. R., Ryu, Y. H., and Park, S. Y. (2006). "Probabilistic neural network for prediction of leakage in water distribution network." Journal of the Korean Society of Water and Wastewater, Vol. 20, No. 6, pp. 799-811.
  3. Jun, H. D., Cho, M. S., Back, C. W., Yoo, D. G., and Kim, J. H. (2008). "A methodology to determine realtime monitoring locations for water distribution systems based on the effect index matrix." KWAR Annual Conference, Korea Water Resources Association, pp. 1428-1432.
  4. Kim, H. K., Kim, H. S., Lee, M. H., Son, M. N., and Kim, S. H. (2005). "A study of leakage detection methods using frequency analysis and transient flow." Conference of Korean Society of Civil Engineers, KSCE, pp. 2688-2691.
  5. Kim, S. W., Choi, D. Y., Bae, C. H., and Kim, J. H. (2013). "Leakage detection of water distribution system using adaptive Kalman filter." Journal of Korea Water Resources Association, Vol. 46, No. 10, pp. 969-976. https://doi.org/10.3741/JKWRA.2013.46.10.969
  6. Koo, J. Y., Kim, Y. H., and Kim, S. G. (2003). "A study on leakage control by regulating water pressure in a water distribution system." 2003 Annual Conference, Korean Society of Water and Wastewater.
  7. Kwon, H. J. (2013a). "Methods of determination of optimum pressure monitoring location for the leakage detection in water distribution system." Conference of Korean Water Resources Association, KWRA, pp. 297.
  8. Kwon, H. J. (2013b). "Back tracing calculation method for the leakage detection in water distribution system." Conference of Korean Society of Water and Wastewater, KSWW.
  9. Lee, M. H., Song, Y. S., and Kim, S. H. (2006). "Transient analysis and experiment considering unsteady friction and leakage in a pipeline system." Journal of the Korean Society of Water and Wastewater, Vol. 20, No. 2, pp. 207-214.
  10. Misiunas, D., Vitkovsky, J., Olsson G., Simpson, A., and Lambert, M. (2005). "Pipeline break detection using pressure transient monitoring." Journal of Water Resources Planning and Management, Vol. 131, No. 4, pp. 316-325. https://doi.org/10.1061/(ASCE)0733-9496(2005)131:4(316)
  11. National Waterworks Information System (2015). http://www.waternow.go.kr/.
  12. Park, P. I., Hong, S. H., Park, N. S., and Jeon, S. Y. (2004). "Comparison of optimization methods for the leakage detection." Journal of Korean Society of Civil Engineers, KSCE, Vol. 24, No. 6, pp. 529-536.
  13. Park, S. W., Im, G. C., Choi, C. L., and Kim, K. L. (2009). "Hierarchical clustering analysis of water main leak location data." Journal of Korea Water Resources Association, Vol. 42, No. 3, pp. 177-190. https://doi.org/10.3741/JKWRA.2009.42.3.177
  14. Vitkovsky, J. P., Liggett, J. A., Simpson, A. R., and Lambert, M. F. (2003). "Optimal measurement site locations for inverse transient analysis in pipe networks." Journal of Water Resources Planning and Management, Vol. 129, No. 6, pp. 480-492. https://doi.org/10.1061/(ASCE)0733-9496(2003)129:6(480)
  15. Yoo, D. G., Chang, D. E., Jun, H., and Kim, J. H. (2012). "Optimization of pressure gauge locations for water distribution systems using entropy theory." Environmental Monitoring and Assessment, Vol. 184, No. 12, pp. 7309-7322. https://doi.org/10.1007/s10661-011-2500-1