DOI QR코드

DOI QR Code

Consideration of Pressure-Rise and Water Hammer for Pipe System in Relation to Start-Up and Sudden Stop of the Pump

펌프 기동 및 정지에 따른 배관 압력상승과 수격작용 영향 고찰

  • 허민웅 (한국수력원자력(주) 중앙연구원) ;
  • 민지호 (한국수력원자력(주) 중앙연구원)
  • Received : 2017.05.29
  • Accepted : 2017.06.28
  • Published : 2017.06.30

Abstract

In the fire protection system or fire fighting water supply system, the jockey pump is generally installed for the prevention of the pressure decrease of pipes, the frequent driving of the fire pump and protection the pipes from the water hammer. In this paper, the pressure-rise in fire fighting water distribution pipes in condition of pipe pressurization by the surge tank at the start-up and the sudden-stop of the fire pump without additional installation of jockey pump is considered by using simple formula calculations and the evaluation of water hammer occurrence in condition of pipe pressurization by the surge tank is included. As a result, the pressure-rise of pipes is less than the pipe design pressure at the condition of pump's start-up and sudden stop, and the possibility of water hammer occurrence is remarkably low due to pressurization of the pipes by the surge tank.

Keywords

References

  1. Sharp, B. B, Sharp, D. B., 1996, Water Hammer : Practical Solutions, Americas Halsted Press, pp. 9 - 14
  2. Joukowsky, N., 1904, "The Hydraulic Hammer in Water Supply Pipes," Proceeding American Water Works Association, Vol. 24, pp. 341 - 424
  3. Electric Power Research Institute, 1996, Water Hammer Handbook for Nuclear Plant Engineers and Operators, EPRI TR-106438s
  4. Hanif Chaudhry, M., 2014, Applied Hydraulic Transients, Springer New York, pp. 1 - 58
  5. The American Society of Mechanical Engineers, 2002, ASME Code for Pressure Piping, B31