In this study, the combined-type diffuser developed by the Authors, in a previous study, was applied to a residential space. The performance of a ventilation and thermal environment, created by the use of a combined-type diffuser was compared to the pan-type diffuser widely used in apartment houses. In cooling conditions, because of the relatively high air flow rate of ceiling cassette-type air conditioners, the characteristics of airflow distribution in a room were governed by the air conditioner's airflow. In heating conditions, because of the low air flow rate of the diffuser, the characteristics of airflow distribution were governed by the buoyancy effect created by cold external walls and a hot floor. In terms of the Air Diffusion Performance Index (ADPI), which is a thermal environmental index, the result of a combined-type diffuser was greater than a pan-type diffuser in both of cooling and heating conditions. Consequently, the combined-type diffuser showed equal or superior ventilation and thermal environment performance compared to a pan-type diffuser.

키워드

참고문헌

  1. Lim, S.-Y. and Chang, H.-J., 2016, A study on the performance of ventilation and maintaining thermal environment for a combined type diffuser, Journal SAREK, Vol. 28, No. 6, pp. 232-241.
  2. SPS-KARSE B 0008-170 : 2004, Diffuser Performance Testing method.
  3. Park, J. S. and Kim, H. J., 2012, A field study of occupant behavior and energy consumption in apartments with mechanical ventilation, Energy and Building, Vol. 50, pp. 19-25. https://doi.org/10.1016/j.enbuild.2012.03.015
  4. Chang, H.-J. and Lee, H.-Y., 2012, A Study on the Improvement of Indoor Thermal and Air Environment Made by Ceiling Cassette Type Cooling and Heating Unit in Classrooms, Journal KSES, Vol. 32, No. 6, pp. 141-148.
  5. Chang, H.-J. and Kim, H.-J., 2011, A study on ventilation characteristics made by thin line type ventilator in an apartment house, Journal SAREK, Vol. 23, No. 3, pp. 201-207.
  6. Ministry of Land, 2013, Infrastructure and Transport, Law of building for facility.
  7. ASHRAE, 2015, ASHRAE Handbook-HVAC Applications, Room air diffusion, pp. 57.5-57.10.
  8. Chang, H.-J., 2002, Effects of air-conditioning and interior of office on indoor environment air conditioned by hybrid system utilizing natural ventilation, Journal AIK, Vol. 18, No. 9, pp. 223-230.
  9. Ministry of trade-industry and energy, 2015, Korea energy agency, Energy Saving Design Standards of Buildings.
  10. Ministry of trade-industry and energy, 2006, Korea energy agency, Regulations concerning the promotion of high energy-efficiency equipment supply.
  11. Seok, H.-T., Choi, D.-H., Kim, H.-J., and Yang, J.-H., 2010, A Study on the Modeling and Analysis Method according to the Diffuser Shape, Journal AIK, Vol. 26, No. 1, pp. 341-348.
  12. Huang, Y. and Zhang, H., 1997, commercial heating and cooling loads component analysis, Energy analysis program.
  13. ASHRAE, 2009, ASHRAE standard 113 : Method of Testing for Room Air Diffusion.