DOI QR코드

DOI QR Code

Experimental Study of an AIIR Ventilation System for Effective Removal of Airborne Contamination in Hospitals

병원 내 공기감염의 효과적 방지를 위한 음압격리병실 최적 환기시스템의 실험적 연구

  • 조진균 (한국건설생활환경시험연구원 건설에너지사업본부) ;
  • 우경헌 (삼성물산(주)건설부문 기술팀) ;
  • 강호석 (삼성물산(주)건설부문 기술팀)
  • Received : 2016.11.30
  • Accepted : 2017.01.25
  • Published : 2017.03.30

Abstract

The purpose of this study is to analyze the removal performance of airborne contamination in a negative airborne infectious isolation room by conducting the field measurement and numerical analysis. This research investigates the pollutant distribution patterns by network ventilation simulation (macro analysis), CFD modeling (micro analysis) and field measurement based on three ventilation systems. An effective ventilation system is crucial to protect doctors, nurses and other healthcare workers from patients with infectious diseases. The results show that ventilation systems utilizing the low-level extraction technique are very effective at removing pollutants in the human breathing zone. A new clean isolation room ventilation strategy has been developed that employs two exhaust air grilles on the wall behind the bed, and is found to have the highest pollutant removal efficiency. The numerical simulation was verified by comparing its prediction result and the field measurement. Isolation room design strategies are formulated based on the results made in this study.

Keywords

References

  1. American Institute of Architects (1987). Guidelines for construction and equipment of hospital and medical facilities, Washington DC: The American Institute of Architect Press.
  2. ASHRAE (2015). ASHRAE Handbook: HVAC Applications. Atlanta, GA: ASHRAE Inc.
  3. Cheong, K.W.D., & Phua, S.Y. (2006). Development of ventilation design strategy for effective removal of pollutant in the isolation room of a hospital. Building and Environment, 41(9), 1161-1170. https://doi.org/10.1016/j.buildenv.2005.05.007
  4. Ha, K.M. (2016). A lesson learned from the MERS outbreak in South Korea in 2015, Journal of Hospital Infection, 92, 232-234. https://doi.org/10.1016/j.jhin.2015.10.004
  5. Li, Y., Huang, X., Yu, I.T., Wong T.W., & Qian, H. (2005). Role of air distribution in SARS transmission during the largest nosocomial outbreak in Hong Kong, Indoor Air, 15(2), 83-95. https://doi.org/10.1111/j.1600-0668.2004.00317.x
  6. Sung M.K. (2016). From a MERS point of view, hospital ventilation system and infection control, Magazine of SAREK, 44(8), 58-64.
  7. US. CDC (1994). Guidelines for preventing the transmission of mycobacterium tuberculosis in health-care facilities, US Department of Health and Human Services, Public Health Services, Federal Register.
  8. WHO (2007). International travel and health. Geneva, Switzerland: World Health Organization.
  9. Yoon, J.H., Lee, B.H., Yeo, M.S., & Kim, K.W. (2016). Comparison of Domestic and Foreign Guidelines for Preventing Airborne Infection in Negative-Pressure Isolation Rooms, Proceeding of Annual Conference of the Architectural Institute of Korea, 36(2), 688-689.

Cited by

  1. Simulation of splash diffusion analysis for prevention of infection in hospital vol.18, pp.6, 2018, https://doi.org/10.12813/kieae.2018.18.6.121