Abstract
In this paper, the flux-lock type superconducting fault current limiter (SFCL) using double quench was suggested and its transient current limiting characteristics were analyzed. The suggested flux-lock type SFCL using double quench consists of two magnetically coupled windings and two $high-T_{c}$ superconducting (HTSC) elements connected in series with each winding. To analyze the transient current limiting characteristics of the flux-lock type SFCL using double quench, the short-circuit tests according to the fault angles, which affect the transient component of the fault current right after the fault occurs, were executed. From the comparative analysis for the short-circuit tests at both $0^{\circ}$ and $90^{\circ}$ fault angles, the useful transient current limiting operations of the suggested flux-lock type SFCL through the double or the single quench occurrence were confirmed.