A Study on the Regional Energy Conservation Effects of a Multi-stage Outdoor Air Enabled Cooling System in a Data Center

데이터센터용 멀티 외기이용 냉방시스템의 지역별 에너지 절감효과에 대한 연구

  • Received : 2016.12.31
  • Accepted : 2017.01.16
  • Published : 2017.02.28

Abstract

A Data center houses a large number of server computers, storage and etc in racks. With the rapid increase of heat generation rates per rack in a data center, energy consumption rates for cooling have been increased year by year. In this study, energy conservation effects of a MOA (multi-stage outdoor air enabled) cooling system in a data center has been investigated when it is applied to 5 different locations, Korea. As results, Energy conservation effects of the MOA cooling system was achieved at about 20% to 30%. Humidifier operation time was 40 to 55 days when supply air temperature was maintained at 13, and humidity condition was kept within the allowed range even though humidifier was off. Furthermore, humidification was not needed when supply air temperature was maintained at $25^{\circ}C$. In selected 5 locations in Korea, the difference of regional climatic conditions affected no more than 5% in cooling energy consumption rates.

Keywords

References

  1. ASHRAE, ASHRAE datacom series: Thermal guidelines for data processing environments, 2011.
  2. Cho, J. K., Jeong, C. S., and Kim, B. S., Viability of HVAC system for energy conservation in high density internal-load dominated buildings, Korean journal of air-conditioning and refrigeration engineering, Vol. 22, No. 8, pp. 530-537, 2010.
  3. Ham, S. W., Kim, M. H., Jeoing, J. W., Energy saving potentials of various air-side economizers in a modular center for supply air conditions and geological locations, Journal of the architectural institute of korea ; planning and design, Vol. 30, No. 6, pp. 263-270, 2014. https://doi.org/10.5659/JAIK_PD.2014.30.6.263
  4. Kim. J. Y, Chang. H. J, Jung. Y. H, Cho. K. M, Augenbroe G. Energy Conservation Effects of a Multi-Stage Outdoor Air Enabled Cooling system in a Data Center, Energy and buildings, Vol. 138, pp. 257-270, 2017. https://doi.org/10.1016/j.enbuild.2016.12.057
  5. ASHRAE, ASHRAE datacom series: Best practices for Datacom facility energy efficiency, Second edition, pp.53-66, 2009.
  6. Lee. K. P, Chen. H. L, Analysis of energy saving potential of air-side free cooling for datacenters in worldwide climate zones, Energy and Buildings, 64, pp. 103-112, 2013. https://doi.org/10.1016/j.enbuild.2013.04.013
  7. LBNL, Data center economizer contamination and humidity study. Lawrence Berkeley National Lab, 2007.
  8. Kishor Khankari, Rack enclosures, ASHRAE Journal, August, pp. 48-51, 2009.
  9. ASHRAE, ASHRAE datacom series: Best practices for Datacom facility energy efficiency, Second edition, pp. 39-41, 2009.

Cited by

  1. 데이터센터의 급기온도 변화가 서버 냉각 성능에 미치는 영향에 대한 연구 vol.30, pp.2, 2017, https://doi.org/10.6110/kjacr.2018.30.2.083
  2. 외기냉방시스템이 적용된 데이터센터 CRAH의 급기온도와 설계 풍량에 따른 에너지성능 분석 vol.35, pp.11, 2017, https://doi.org/10.5659/jaik_sc.2019.35.11.181