Measurement and Analysis of Insulation Detects of Cast-resin Transformers using Antenna

안테나를 이용한 몰드변압기 절연결함 측정기법 연구

  • Choi, Myeong-Il (Electrical Safety Research Institute, Korea Electrical Safety Co.) ;
  • Kim, Jae-Jin (Electrical Safety Research Institute, Korea Electrical Safety Co.) ;
  • Han, Ga-Ram (Electrical Safety Research Institute, Korea Electrical Safety Co.) ;
  • Jeon, Jeong-Chay (Electrical Safety Research Institute, Korea Electrical Safety Co.) ;
  • Lee, Hyun-Ok (Korea Polytechnics Mokpo Campus)
  • Received : 2016.08.18
  • Accepted : 2016.09.20
  • Published : 2016.11.01

Abstract

Unlike oil immersed transformers, cast-resin transformers have the solid insulator 'epoxy resin' in sealed structure. Therefore, they reveal a lot of limitations in checking aging conditions and predicting an accident. This study analyzed the characteristics of Cast-resin transformers by the measurement distance and measurement sensitivity with a corona defect sample, using antenna sensor. Therefore, the experiment has proven that the antenna sensor-based measurement method proposed in this study is able to detect the insulation defect location of the cast-resin transformer, unlike conventional measurement methods. It is expected that the result of this study will be used to develop a new type of measuring method in order to measure insulation defects and to use in safety inspection of domestic cast-resin transformers.

Keywords

References

  1. Kil-Mok Shong, Myung-Il Choi, Young-Seog Kim, Sun-Bae Bang, Chong-Min Kim, "A Study on the Comparison of the Vibration Data in Cast Resin Transformer According to the Load Type", KIIEE, V.26, No. 4, pp. 75-81, 2012.
  2. KESCO, "A Study on the Expected Service Life of 22.9kv. Class Electrical Equipments", pp. 136-138, 2009.
  3. KESCO, "The laser detection through the mounting reflector and the development of mold transformer vibration analysis system", pp. 14-17, 2012.
  4. Soongsil University, "A Study o the Protection of the Risk & the Developmet of Monitoring System on the Mold Transformer", pp. 3-12, 1997.
  5. Masaaki Kando, "Fault Detection Method with Antennas", IEEE Proceedings of the 5" International Conference on Properties and Applications of Dielectric Materials, Vol. 2, pp. 1140-1143, 1997.
  6. Myeong-Il Choi, Jae-Chul Kim, "A Study on the Comparison of Denoising Performance of Stationary Wavelet Transform for Discharge Signal Data in Cast-resin Transformer, KIIEE, Vol. 28, No. 3, pp. 84-90, 2014.