DOI QR코드

DOI QR Code

A Study Vertical Surface Discharge Characteristics of the Shape Change of the Solid Insulation with the Same Creepage Distance of Dry-Air

Dry-Air 중의 동일 연면거리를 가진 고체절연물의 형상 변화에 따른 수직연면방전 특성 연구

  • Received : 2015.11.06
  • Accepted : 2015.12.07
  • Published : 2016.01.31

Abstract

In terms of power components which use environmentally-friendly dry air that can substitute SF6, there have been studies on the electrical properties of the solid insulation "spacer" for the purpose of securing dielectric strength as they become smaller. This study laminated solid insulation to keep the creeping distance the same in the dry air and investigated vertical surface discharge characteristics by shape. The three sheets of disk-type solid insulation(Bakelite) were laminated in a manner to keep the creeping distance the same. The lamination was categorized as follows: "Type A" in which the insulations with the same disk diameter were laminated; "Type B" in which the insulations whose middle disk diameter was large were laminated; and "Type C" in which the ones whose middle disk diameter was small were laminated. For a vertical surface discharge experiment, dry air was injected into the test chamber depending on the shape of the laminated solid insulation, and chamber pressure was adjusted in a range of 0.1-0.6MPa. As volume decreased, surface discharging voltage by unit volume increased. This was because of dielectric polarization according to the structural characteristics of the shape of lamination. The highest surface discharging voltage was found in "Type C."

Keywords

References

  1. L.G. Christophorou, J.K Olthoff and R.j Van Brunt, "Sulfur Hexafluoride and the Electric Power Industry",IEEE Electrical Insulation Magazine, Vol. 13, No. 5, pp.22-24, September/October, 1997. https://doi.org/10.1109/57.583423
  2. Toshiaki Rokunohe, Yoshitaka Yagihashi, Kenji Aoyagi, Takashi Oomori and Rumihiro endo, "Development of $SF_6$-free 72.5kV GIS", IEEE Trans. on Power Delivery, Vo1.22, No.3, pp.1869-1876, July 2007. https://doi.org/10.1109/TPWRD.2007.899273
  3. CIGRE WG 15.03: "LONG-TERM PERFORMANCE OF $SF_6$ INSULATED SYSTEMS", CIGRE Report 15-301, 2002.
  4. Muneaki Kurimoto, Katsumi Kato, Masahiro Hanai, Yoshikazu Hoshina, Masafumi Takei, Hitoshi Okubo, "Application of Functionally Graded Material for Reducing Electric Field on Electrode and Spacer Interface", IEEE Transactions on Dielectrics and Electrical Insulation Vol. 17, No. 1, pp256-263, 2010. https://doi.org/10.1109/TDEI.2010.5412025
  5. Jay Kyoon Lee, Arlon T. Adams, "ELECTROMAGNETICS", Hanbit Academy. Inc., 2013.
  6. G. J. Min, B. C. Kang, S. Bae, K. S. Lee, W.Z. Park, "Study of Surface Discharge Characteristics for Laminated Solid Insulator in Quasi-Uniform Field of Dry Air", J Korean Inst. IIIum. Electr. Install. Eng., pp27-28, 2013. 5.
  7. Jeong-Hoo Seok, Jong-Hyun Beak, Dong-Young Lim, Sungwoo Bae, Ki-Chai Kim, Won-Zoo Park, "A Study on Characteristics of Insulation Breakdown and Surface Discharge by the Mixing Ratio of Dry Air/$O_2$ gas mixtures", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers 29(6), pp49-57, 2015.6. https://doi.org/10.5207/JIEIE.2015.29.6.049
  8. E. Kuffel, W. S. Zaengl and J. Kuffel, "High Voltage Engineering Fundamentals", Elsevier, pp. 203, 323-345, 2000.
  9. K. C. Seo, "High Voltage Engineering (New edition)", Dong Myeong Publishers, pp.34-40, 1977.
  10. Dong-Young Lim, "A Study of Surface Insulation Characteristics in N2/O2 Mixture gas", a thesis submitted for the degree of master of Electrical Engineering, Yeungnam University, 2011.
  11. H. P. Y. S. Kim, E. H. Choi, K. S. Park, L. K. Kim, W. Z. Park, K. S. Lee, "The Breakdown Characteristics for Dry-Air with Humidity Variations", J Korean Inst. IIIum. Electr. Install. Eng., pp238-240, 2008. 5.