DOI QR코드

DOI QR Code

The Neural-Fuzzy Control of a Transformer Cooling System

  • Lee, Jong-Yong (Ingenium college of liberal arts, KwangWoon University) ;
  • Lee, Chul (Department of Mechatronics, Inhatechnical Collage)
  • Received : 2016.05.25
  • Accepted : 2016.06.10
  • Published : 2016.06.30

Abstract

In transformer cooling systems, oil temperature is controlled through the use of a blower and oil pump. For this paper, set-point algorithms, a reset algorithm and control algorithms of the cooling system were developed by neural networks and fuzzy logics. The oil inlet temperature was set by a $2{\times}2{\times}1$ neural network, and the oil temperature difference was set by a $2{\times}3{\times}1$ neural network. Inputs used for these neural networks were the transformer operating ratio and the air inlet temperature. The inlet set temperature was reset by a fuzzy logic based on the transformer operating ratio and the oil outlet temperature. A blower was used to control the inlet oil temperature while the oil pump was used to control the oil temperature difference by fuzzy logics. In order to analysis the performance of these algorithms, the initial start-up test and the step change test were performed by using the dynamic model of a transformer cooling system. Test results showed that algorithms developed for this study were effective in controlling the oil temperature of a transformer cooling system.

Keywords

References

  1. Seo, S., Han, S., Kim, N., and Kin, J., 2006, On the development of Korean tilting train express, Proceedings of KSME, pp. 287-291.
  2. Eum, K., and Um, J., 2004, Evaluation of running stability of tilting trains in conventional curved track, Proceedings of the KSR, Vol 7, No. 4, pp. 153-159.
  3. Woojin industrial systems Co., 2007, Technical development of propulsion system, Construction and Transportation Report, pp. 307-357.
  4. Han, D., and Kim, S., 2008, Effective dynamic models for the development of control algorithms of a condensing gas boiler system, SAREK, Vol. 20, No. 8, pp.365-371.
  5. Han, D., and Noh, H., 2010, Mathematical models of a transformer cooling system for the control algorithm development, SAREK, Vol. 22, No. 2, pp. 70-77.
  6. Han, D., and Won, J., 2010, The intelligent control algorithm of a transformer cooling system, SAREK, Vol. 22, No. 8, pp.515-522.
  7. Han, D., and Oh, W., 2010, The oil temperature reset algorithm for a transformer cooling system, Proceedings of SAREK, pp. 499-504.
  8. Han, D., and Won, J., 2009, The control of a transformer cooling system by a fuzzy logic, Proceedings of SAREK, pp. 425-430.
  9. Han, D., and Park, S., 2010, The high pressure control of a CO2 air-conditioner by using a fuzzy algorithm, Proceedings of SAREK, pp. 499-504.