초록

This paper deals with the characteristics of partial discharge (PD) for the purpose of a condition based maintenance (CBM) of gas insulated switchgears (GIS) in power equipment. Four types of electrode systems such as a protrusion on enclosure (POE), a particle on spacer (POS), a free particle (FP) and a Floating were designed and fabricated. PD pulses were measured using UHF sensor with a frequency range of 300 MHz~1.4 GHz and a DAQ with a sampling rate of 250 MS/s. Discharge inception voltage (DIV), discharge extinction voltage (DEV), and phase resolved partial discharge (PRPD) were analyzed depending on electrode systems. The average DIV in the POS was 28.8 kV. It was about 1.7 times higher than that in the FP, which was the lowest value of 17.2 kV. The FP shuffled and jumped at the applied voltage of 23.5 kV. Over 95% of PD pulses in the POE were generated in the negative polarity ($181^{\circ}{\sim}360^{\circ}$) of applied voltage. The results showed the phase (${\Phi}$)-magnitude (dBm) of PD pulses by UHF sensor, a cluster was formed separately depending on electrode systems.

키워드

참고문헌

  1. S. J. Kim, G. Wang, M. Y. Yun, and G. S. Kil, 2015 Autumn Conference of the Korean Society for Railway, (The Korean Society for Railway, Yeosu, 2015) p. 1474-1479.
  2. S. J. Kim, H. E. Jo, G. W. Jeong, G. S. Kil, and S. W. Kim, Journal of the Korean Inst. Electr. Electron. Mater. Eng., 28, 1 (2015).
  3. F. H. Kreuger, Partial Discharge Detection in High-Voltage Equipment the 1st ed. (Butterworth-Heinemann, United Kingdom, 1989) p. 140-143.
  4. M. S. Naidu and V. Kamaraju, High Voltage Engineering (McGraw-Hill, India, 2009) p. 364-366.
  5. M. S. Kim, G. W. Jeong, G. S. Kil, and D. W. Park, 2013 Autumn Conference of the Korean Society for Railway (The Korean Society for Railway, Daegu, 2013) p. 459-464.
  6. G. Wang, S. J. Kim, H. E. Jo, G. W. Jeong, and G. S. Kil, 2015 19th International Symposium on High Voltage Engineering (ISH 2015, Czech Republic, 2015) p. 165(1)-165(5).
  7. S. J. Kim, H. E. Jo, G. Wang, M. Y. Yun, and G. S. Kil, Journal of the Korean Inst. Electr. Electron. Mater. Eng., 28, 12 (2015).
  8. K. H. Kim, D. Z. Lee, and H. R. Kwak, Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, 17, 1 (2003).
  9. F. N. Budiman, Y. Khan, N. H. Malik, and A. A. Al-Arainy, IEEE Transactions of Dielectrics and Electrical Insulation, 20, 6 (2013). [DOI: http://dx.doi.org/10.1109/TDEI.2013.6678863]
  10. G. W. Jeong, M. E. Thesis, p. 24-26, National Korea Maritime and Ocean University, Busan (2015).
  11. G. Wang, M. E. Thesis, p. 21, 22, National Korea Maritime and Ocean University, Busan (2015).

피인용 문헌

  1. Analysis of PD Signal for Condition Monitoring of MV Switchboards by the Measurement of Transient Earth Voltage vol.19, pp.3, 2018, https://doi.org/10.1007/s42341-018-0037-5