I. INTRODUCTION
Three-phase grid-connected inverters are an important part of distributed generation systems. An inverter may continue supplying power to a local load when it is disconnected from the grid. In this case, islanding happens and electrical equipment is damaged. As a result, personal safety can be threatened. Therefore, islanding detection is necessary to improve the stability and safety of inverter systems [1]-[6].
Passive islanding detection methods detect the amplitude, frequency, phase angle and harmonic content of the grid voltage. It is easy to realize and does not cause additional current distortion. However, the non-detection zone cannot be avoided [7]-[11]. Active islanding detection methods can reduce the non-detection zones. However, disturbances such as frequency or phase drifts of the grid current are added. The quality of the grid current can be reduced because of these disturbances [12]-[15].
Changes in the parameters of an inverter system can reflect its working condition. If the inverter is disconnected from the grid, some of the parameters may change and can be easily detected. These parameters can be seen as the "features" of the inverter system. The working condition of the system can be recognized depending on these features. Islanding can be detected when these features are changed. As a result, modern feature recognition technology can be introduced to realize islanding detection. Feature recognition contains speaker recognition, image recognition and so on [16]-[20]. Speaker recognition is a typical feature recognition technology. It provides a way to take advantage of speaker features regardless of verbal information [21]. However, it cannot be directly applied to islanding detection. In the Vector Quantization (VQ)-based feature recognition, the decision is made by measuring the similarities between a testing pattern and every codeword achieved during training [22]-[27]. In a three-phase inverter system, the codeword can be seen as the parameters of the system, such as the three-phase current and voltage, the DC voltage, the grid frequency, and so on. The codebook is the vector formed by different codewords. A codebook is a collection of codewords which can reflect a certain feature. It can be seen as a feature vector and can be obtained by a theoretical analysis of the inverter’s operation condition instead of the training of signals. The codebooks can form an operation vector model of the inverter system. With this model, changes in the features in an inverter system can be detected in real-time.
For the above reasons, a novel islanding detection method based on modern feature recognition technology is proposed in this paper. The features of an inverter system are analyzed. When islanding occurs, one or some of the features change. Abnormal phenomenon can be detected and the non-detection zone can be eliminated. To exacerbate the changes of the features and accelerate the speed of detection, an active islanding detection method is applied. This can help avoid miscalculations. When the grid-connected inverter operates normally, the quality of the grid current is not reduced. When the inverter is disconnected from the grid, the changes in the features can be exacerbated. The operating condition of the inverter will be analyzed in Section II. The vector model will be established and an islanding detection method based on modern feature recognition technology will be introduced in Section III. An active islanding detection method will be described in Section IV. Simulation and experimental results obtained from an 18kVA three-phase grid-connected inverter will be presented to verify the theoretical analysis in Section V.
II. OPERATION ANALYSIS
A. Parameters in the Inverter System
Fig. 1 (a) shows a control diagram of a three-phase grid-connected inverter system. There are several parameters in this system. ia, ib and ic are the AC side current. ua, ub and uc are the AC side voltage. ea, eb and ec are the grid voltage. When the inverter works in the grid-connected condition, ua, ub and uc are the same as ea, eb and ec. θ is the phase angle of the grid voltage, which can be obtained by a PLL. id and iq are the active and reactive current. id* and iq* are the references of active and reactive current.
Fig. 1.Introduction of the three-phase inverter system. (a) Control diagram of the system. (b) Relationship among the parameters of the system.
The relationships among the parameters is shown in Fig. 1 (b). When the inverter works in the grid-connected condition, the phase angle of the AC side current is the same as that of the AC side voltage. With the PLL method, a non-ideal grid cannot influence the accuracy of θ [28]-[31]. Therefore, θ can be seen as the ideal value. If ua, ub and uc are sampled, the theoretical values of the AC side current ia*, ib* and ic* and the projection of the three-phase voltage on the dq frame ud and uq can be calculated. id* and iq* are also the theoretical values of active and reactive current. The actual value of the active and reactive current id and iq can be calculated by ia, ib and ic. The frequency of the grid f1 can be obtained by a change in the rate of θ.
There are three situations in terms of local loads [32]-[33]. Fig. 2 shows changes in the key parameters before and after the inverter is disconnected from the grid at time t0. The waveforms from top to bottom are for ua, ia and θ. Due to the filter L, the AC side current ia, ib and ic does not have sudden changes. The instantaneous changes at t0 are not obvious because of the parallel RLC resonant load.
Fig. 2.Changes of the key parameters before and after the inverter is disconnected from the grid. (a) The local load is capacitive or inductive. (b) The local load is resistive without power matching. (c) The local load is resistive with power matching.
In Fig. 2(a), the local load is capacitive or inductive. Before t0, the phases of ua and ia are the same. θ changes from–π to π linearly. After t0, the phases of ua and ia are different. θ reaches π at t4 instead of t3.
In Fig. 2(b), the local load is resistive and the powers of the load and the inverter are not matched. If the power of the load is lower than that of the inverter, the power of the inverter is partly supply to the grid. If the power of the load is higher than that of the inverter, the power of the load is partly absorbed from the grid. After t0, the phases of ua and ia are still the same. Thus, θ can reach π at t3. When the inverter is still connected to the grid, the change of θ is the same. However, the amplitude of ua, ub and uc changes, which reflects the change of ud.
In Fig. 2(c), the local load is resistive and the powers of the load and the inverter are matched. If only the fundamental components are considered, none of the parameters change after t0. In this condition, a non-detection zone may occur. To avoid this non-detection zone, at least one varying parameter needs to be determined. Therefore, further analysis is necessary.
B. Changes in the Parameters
To avoid a non-detection zone, only the third situation is under consideration. When the inverter is connected to the grid, ud is regulated according to standards. It is limited in a certain range. The voltage harmonics are also regulated according to standards and their content is slight. After the inverter is disconnected from the grid, ua, ub and uc are not clamped by the grid voltage. The harmonics of ua, ub and uc increase because of the switching and nonlinear load.
The voltage harmonics introduced by the switching are caused by two reasons [34]. One is dead-time. The other is SVPWM (Space Vector Pulse Width Modulation). The output voltage harmonic of the bridge arm caused by the dead-time can be expressed as:
where td is the dead-time and Tc is the switching cycle. The output voltage harmonic of the bridge leg caused by the SVPWM can be expressed as:
where n corresponds to the multiple of the reference wave frequency, and m corresponds to the multiple of the carrier wave frequency. h is m*(fc/f1)+n. The coefficient Cmn can be expressed as:
The equivalent reference of the SVPWM control umod can be expressed as:
where VDC is the DC voltage, M is the modulation ratio, and k is the sector number. At a low frequency, m is 0, and n is a multiple of 3.
Fig. 3 shows the voltage harmonics of the bridge leg caused by the SVPWM. The switching frequency fs is 5kHz. The grid current can be seen as the superposition of the fundamental current and the harmonics. The local load can be simplified as a parallel circuit of the resistor R1, the inductor L1 and the capacitor C1. The resonance frequency can be expressed as:
Fig. 3.Voltage harmonics of the bridge leg caused by SVPWM.
When fr is the grid frequency f1, the local load is resistive. If the inverter is disconnected from the grid, the current harmonics caused by the voltage harmonics uoh described in (1) and (2) can be expressed as:
where L is the AC side filter. Thus, the AC side voltage can be expressed as:
The voltage harmonic projections in the dq-frame can be expressed as:
Fig. 4 shows the changes in the AC side voltage caused by the SVPWM. The inverter is disconnected from the grid at the time t0. The switching frequency current harmonic is added to the ideal fundamental current of the AC side.
Fig. 4.Changes of the AC side voltage caused by SVPWM.
The top waveforms ua, ub and uc do not noticeably change after t0. ud and uq are the projections of ua, ub and uc in the dq-frame. The phase angle, which takes part in the coordinate transformation, is the output of the PLL. The input of the PLL is ua, ub and uc so that uq is always 0. The frequency of the three-phase current harmonic is the switching frequency fs. The bottom waveform Kud(h+1) is the output of a high passed filter (HPF). The input of the HPF is ud. K is the gain of the HPF. In order to amplify the voltage harmonic, K is set as 10 in this paper. h is the voltage harmonic order, which is fs/f1. The cut-off frequency of the HPF should be less than fs. It is set as 2.5kHz in this paper. The voltage harmonic noticeably changes after t0. Thus, the non-detection zone can be solved through testing udh by a HPF.
The voltage harmonics introduced by the nonlinear load also contain the low and high frequency components [35]. After the inverter is disconnected from the grid, the voltage harmonics with both low and high frequencies increase. The delay of the HPF is much shorter than that of a LPF (Low Passed Filter). Therefore, a HPF is applied instead of other filters.
III. MODEL ISLANDING DETECTION METHOD
A. Establishment of a Vector Model
Changes in the parameters are analyzed in Section II. Thus, the features of the inverter system can be extracted. The feature vector can be expressed as:
y1 and y2 are two groups of three-dimensional vectors. They can be expressed as:
y1 is a feature of the current in an inverter system, and y2 is a feature of the voltage. udh is a sinusoidal variation and cannot be applied in the feature recognition as a codeword. It can be replaced by a function f(udh), which is the amplitude of udh. The algorithm of f(udh) is shown in Fig. 5.
Fig. 5.The algorithm of f(udh).
In Fig. 5, fz is the testing frequency of udh. The calculation of f(udh) costs half of a switching cycle, which is a very short time.
B. Islanding Detection Method
The theoretical value of the feature vector can be expressed as:
where C1 and C2 are the codebooks. ia*, ib*, ic*, f1*, ud* and f(udh*) are the codewords. f(udh*) is 0 in the ideal condition.
According to standard GB12325-90, the ideal value of f1* is 50Hz, and ud* is 280V. A slight deviation is allowed in the standard. Therefore, C1 and C2 are different from y1 and y2 even when the inverter works normally. Therefore, islanding should be judged by the mean square quantization distortion, which can be expressed as:
The threshold δ should be set reasonably set. When the inverter works normally, δ should be larger than d. When the inverter is disconnected from the grid, d exceeds δ and islanding can be detected. δ can be expressed as:
where Cijmax and Cijmin are the upper and lower limits of the codewords regulated by standards. Fig. 6 shows the processes of the speaker recognition and the proposed islanding detection method. It can be seen that the codebooks of the islanding detection method can be directly obtained by the feature analysis, while the codebooks of the speaker recognition are obtained by Vector Quantization.
Fig. 6.Comparison of the processes of the speaker recognition and the islanding detection method. (a) The speaker recognition. (b) The islanding detection method.
IV. ACTIVE DETECTION METHOD
If an inverter is connected to a non-ideal grid, voltage harmonics always occur and udh in Fig. 5 is not zero before t0. Islanding may be misjudged through testing f(udh) if the threshold δ is too small. However, the changes in the features may be slight. If δ is too high, islanding may not be detected in time. To accelerate the speed of detection and to avoid miscalculation, an active islanding detection method should be applied to exacerbate the changes in the features. According to the above analysis, after the inverter is disconnected from the grid, ud cannot be clamped by the grid. If a disturbance is added to exacerbate the changes in ud, islanding can be easily detected. Fig. 7 shows an active islanding detection method.
Fig. 7.Active islanding detection method.
f(udh) described in Fig. 5 is added to the active current reference id*. A HPF is applied to separate the high frequency voltage harmonics. udh is the output of the HPF, which was designed in section II. It is the sum of the high frequency voltage harmonics. Their frequencies are higher than the cut-off frequency of the HPF.
In a non-ideal grid, the grid harmonics are mainly the 3rd, 5th, 7th, 11th and 13th time voltage harmonics [36]. The containing of the switching frequency voltage harmonics is very slight. Therefore, f(udh) is close to 0 when the inverter connects to the grid. If islanding happens, the AC side voltage is not be clamped by the grid and f(udh) increases. According to the current loop shown in Fig. 8, uoh increases with an increment of f(udh). According to (7) and (8), f(udh) increases further. After a few times’ accumulation, the islanding can be quickly detected.
Fig. 8.Control diagram of the current loop.
V. SIMULATION AND EXPERIMENTAL RESULTS
An 18kVA three-phase grid-connected inverter with the SVPWM control method has been simulated by the simulation software MATLAB/Simulink. The grid is 220V/380V/50Hz, and the DC voltage is 700V.
Fig. 9 shows the changes in the parameters both with and without the active islanding detection method. The three-phase inverter is simulated by a three-phase current source. The amplitude of the fundamental current is 40A. The amplitude of the switching frequency positive sequence current harmonic is 1A. The switching frequency fs is 5kHz. The RLC resonant load is 7Ω, 10.1424mH and 1000μF. The resonant frequency of the local load is 50Hz. The parameters of the HPF are the same as those from the theoretical analysis.
Fig. 9.Changes of the parameters. (a) AC side voltage and current without active islanding detection method. (b) The feature parameters without active islanding detection method. (c) AC side voltage and current with active islanding detection method. (d) The feature parameters with active islanding detection method.
The inverter is disconnected from the grid at time t0. Fig. 9 (a) shows the AC side voltage and current without the active islanding detection method. It seems that there is no change and that islanding can happen. However, the parameters discussed in Section III change obviously after t0.
In Fig. 9 (b), the waveforms from top to bottom respectively are ud, udh and f(udh). Positive sequence current harmonics are added so that h is fs/f1+1 in this figure. According to f(udh), islanding can be detected.
Fig. 9 (c) shows the AC side voltage and current with the active islanding detection method. The AC side voltage and current change obviously after the inverter is disconnected from the grid. Because of the positive feedback, the amplitude of the current harmonic is able to increase after t0, which is shown in Fig. 9 (d). Thus, the islanding can be quickly detected.
Tab. 1 shows the values of the parameters of (12). The principle of the weighting factors αij is that the influence of the parameters can realize an average distribution. According to Tab. 1, the threshold δ can be set as 1.
Fig. 10 shows the passive and active islanding detection results in a non-ideal grid. An 18kVA three-phase inverter model is applied. The waveforms from top to bottom are the AC side voltage ua, ub and uc, the AC side current ia, ib and ic, the driving enable signal, d and δ. The inverter is disconnected from the grid at the time t=0.04s.
Fig. 10.The islanding detection result in the non-ideal grid. (a) Passive islanding detection method (δ=1). (b) Active islanding detection method (δ=1). (c) Passive islanding detection method (δ=2). (d) Active islanding detection method (δ=2).
TABLE ITHE VALUES OF THE PARAMETERS
Fig. 10(a) and (b) show the passive and active islanding detection results when the threshold δ is 1. The islanding is more quickly detected with the active islanding detection method. However, sometimes d is close to δ when the inverter works normally. δ should be high enough to avoid misprotection. However, it cannot be too high to detect the islanding. Fig. 10(c) and (d) show the detection results when δ is 2. The islanding may not be detected with the passive islanding detection method while the active islanding detection method can solve the problem.
An 18kVA three-phase grid-connected inverter with the SVPWM control strategy based on a TMS320F240PQA has been built to verify the analysis. The parameters are the same as those used in the simulation.
Fig. 11(a) and (b) show the experimental results with the passive and active islanding detection method when δ is 1. The waveforms from top to the bottom are the AC side voltage ua, ub and uc, and the AC side current ia, ib and ic. The islanding can be quickly detected with both methods.
Fig. 11.Experimental results in the non-ideal grid. (a) Passive islanding detection method (δ=1). (b) Active islanding detection method (δ=1). (c) Passive islanding detection method (δ=2). (d) Active islanding detection method (δ=2). (e) AFD islanding detection method.
Fig. 11(c) and (d) show the experimental results when δ is 2. The islanding can be quickly detected with the active method. However, the passive method cannot detect the islanding in time. Fig. 11 (e) shows the experimental results with the active frequency drift (AFD) method. The detection speed of the proposed active detection method is quicker than that of the AFD method.
Fig. 12 shows the current harmonics of the grid current when the inverter works normally. There are third-time current harmonics because the three-phase transformer is not completely symmetrical. Fig. 12 (a) and (b) are the current harmonics with the passive and active islanding detection methods. Their THDs are 3.7 and 4.0, respectively. It can be seen that the active islanding detection method does not introduce a lot of harmonic. The lower h is, the higher the increment of the current harmonic becomes. Fig. 12 (c) shows the current harmonics with the AFD. The THD is 4.9 and it is higher than that of the proposed method.
Fig. 12.The current harmonics. (a) Passive islanding detection method. (b) Active islanding detection method. (c) Active islanding detection method.
VI. CONCLUSION
This paper proposes a novel islanding detection method based on the modern feature recognition technology. The proposed method can identify the features of the inverter system and it can calculate the quantizing distortion. The principle of the feature recognition technology is described in detail. Passive and active islanding detection methods based on feature recognition technology are analyzed. Simulation and experimental results from an 18 kVA grid-connected inverter are presented to verify the theoretical analysis. The proposed method has the following advantages:
1) This method can avoid the non-detection zone through changes of the parameters.
2) The active method can accelerate the speed of detection and avoid miscalculation.
3) Compared to the active frequency or phase drift methods, the AC side current with the proposed method has less distortion when the inverter works normally.
References
- D. Reigosa, F. Briz, C. Blanco, P. Garcia, and J. M. Guerrero, “Active islanding detection for multiple parallel-connected inverter-based distributed generators using high-frequency signal injection,” IEEE Trans. Power Electron., Vol. 29, No. 3, pp. 1192-1199, Mar. 2014. https://doi.org/10.1109/TPEL.2013.2263845
- D. Zhang, H. C. Niu, and M. Jiang, "Modeling of islanding detection by sensing jump change of harmonic voltage at PCC by the combination of a narrow band-pass filter and wavelet analysis," in IEEE ECCE Asia Downunder, pp. 1289-1294, Jun. 2013.
- W. Cai, B. Liu, S. Duan, and C. Zou, “An islanding detection method based on dual-frequency harmonic current injection under grid impedance unbalanced condition,” IEEE Trans. Ind. Informat., Vol. 9, No. 2, pp. 1178-1187, May 2013. https://doi.org/10.1109/TII.2012.2209669
- E. J. Estébanez, V. M. Moreno, A. Pigazo, M. Liserre, and A. Dell’Aquila, “Performance evaluation of active islanding-detection algorithms in distributed-generation photovoltaic systems: two inverters case,” IEEE Trans. Ind. Electron., Vol. 58, No. 4, pp. 1185-1193, Apr. 2011. https://doi.org/10.1109/TIE.2010.2044132
- S. H. Lee and J.-W. Park, “Improvement on stability and islanding detection performances by advanced inverter control of DG,” IEEE Trans. Power Syst., Vol. 28, No. 4, pp. 3954-3963, Nov. 2013. https://doi.org/10.1109/TPWRS.2013.2262716
- R. M. Kamel, A. Chaouachi, and K. Nagasaka, “Three control strategies to improve the microgrid transient dynamic response during isolated mode: a comparative study,” IEEE Trans. Ind. Electron., Vol. 60, No. 4, pp. 1314-1322, Apr. 2013. https://doi.org/10.1109/TIE.2012.2209609
- G. G. Pozzebon, A. F. Q. Goncalves, G. G. Pena, N.E.M. Mocambique, and R. Q. Machado, “Operation of a three-Phase power converter connected to a distribution system,” IEEE Trans. Ind. Electron., Vol. 60, No. 5, pp. 1810-1818, May 2013. https://doi.org/10.1109/TIE.2012.2191751
- H. Laaksonen, “Advanced islanding detection functionality for future electricity distribution networks,” IEEE Trans. Power Del., Vol. 28, No. 4, pp. 2056-2064, Oct. 2013. https://doi.org/10.1109/TPWRD.2013.2271317
- H. Vahedi, G. B. Gharehpetian, and M. Karrari, “Application of duffing oscillators for passive islanding detection of inverter-based distributed generation units,” IEEE Trans. Power Del., Vol. 27, No. 4, pp. 1973-1983, Oct. 2012. https://doi.org/10.1109/TPWRD.2012.2212251
- J.-H. Kim, J.-G. Kim, Y.-H. Ji, Y.-C. Jung, and C.-Y. Won, “An islanding detection method for a grid-connected system based on the goertzel algorithm,” IEEE Trans. Power Electron., Vol. 26, No. 4, pp. 1049-1055, Apr. 2011. https://doi.org/10.1109/TPEL.2011.2107751
- A. Cataliotti, V. Cosentino, N. Ngoctrung, and P. Russotto, "Hybrid passive and communications-based methods for islanding detection in medium and low voltage smart grids," in 4th International Power Engineering, Energy and Electrical Drives(POWERENG), pp. 1563-1567, May 2013.
- A. Yafaoui, B. Wu, and S. Kouro, “Improved active frequency drift anti-islanding detection method for grid connected photovoltaic systems,” IEEE Trans. Power Electron., Vol. 27, No. 5, pp. 2367-2375, May 2012. https://doi.org/10.1109/TPEL.2011.2171997
- H. H. Zeineldin and M. M. A. Salama, “Impact of load frequency dependence on the NDZ and performance of the SFS islanding detection method,” IEEE Trans. Ind. Electron., Vol. 58, No. 1, pp. 139-146, Jan. 2011. https://doi.org/10.1109/TIE.2009.2033482
- Q. Zhang, X. Sun, Y. Zhong, B. Ren, and M. Matsui, "Research on an novel active anti-islanding method based on positive feedback of even harmonic current disturbance," in IEEE Power Engineering and Automation Conference (PEAM), pp. 22-25, Sep. 2011.
- H. Novanda, P. Regulski, V. Stanojevic, and V. Terzija, “Assessment of frequency and harmonic distortions during wind farm rejection test,” IEEE Trans. Sustain. Energy, Vol. 4, No. 3, pp. 698-705, Jul. 2013. https://doi.org/10.1109/TSTE.2013.2242499
- M. Ferras and H. Bourlard, "MLP-based factor analysis for tandem speech recognition," in IEEE International Conference on Acoustics, Speech and Signal Processing (ICASSP), pp. 6719-6723, May 2013.
- J. Ming, R. Srinivasan, D. Crookes, and A. Jafari, “CLOSE—a data-driven approach to speech separation,” IEEE Trans. Audio, Speech, Language Process., Vol. 21, No. 7, pp. 1355-1368, Jul. 2013. https://doi.org/10.1109/TASL.2013.2250959
- S. Garimella and H. Hermansky, “Factor analysis of auto-associative neural networks with application in speaker verification,” IEEE Trans. Neural Netw. Learn. Syst., Vol. 24, No. 4, pp. 522-528, Apr. 2013. https://doi.org/10.1109/TNNLS.2012.2236652
- Y.-T. Chuang, Y.-L. Hong, K.-C. Huang, and S.-W. Shih, “Autofocus of iris patterns using a triangle aperture,” IEEE Trans. Cybern., Vol. 43, No. 4, pp. 1304-1309, Aug. 2013. https://doi.org/10.1109/TSMCB.2012.2227722
- M. Hu, Y. Wang, Z. Zhang, D. Zhang, and J. J. Little, “Incremental learning for video-based gait recognition with LBP flow,” IEEE Trans. Cybern., Vol. 43, No. 1, pp. 77-89, Feb. 2013. https://doi.org/10.1109/TSMCB.2012.2199310
- T. Kinnunen, E. Karpov, and P. Franti, “Real-time speaker identification and verification,” IEEE Trans. Audio, Speech, Language Process., Vol. 14, No. 1, pp. 277-288, Jan. 2006. https://doi.org/10.1109/TSA.2005.853206
- B. V. Srinivasan, Y. Luo, D. G. Romero, D. N. Zotkin, and R. Duraiswami, “A symmetric kernel partial least squares framework for speaker recognition,” IEEE Trans. Audio, Speech, Language Process., Vol. 21, No. 7, pp. 1415-1423, Jul. 2013. https://doi.org/10.1109/TASL.2013.2253096
- L. E. Shafey, C. Mccool, R. Wallace, and S. Marcel, “A scalable formulation of probabilistic linear discriminant analysis: applied to face recognition,” IEEE Trans. Pattern Anal. Mach. Intell., Vol. 35, No. 7, pp. 1788-1794, Jul. 2013. https://doi.org/10.1109/TPAMI.2013.38
- S. Yaman and J. Pelecanos, “Using polynomial kernel support vector machines for speaker verification,” IEEE Signal Process. Lett., Vol. 20, No. 9, pp. 901-904, Sep. 2013. https://doi.org/10.1109/LSP.2013.2273127
- W. Rao and M.-W. Mak, “Boosting the performance of i-vector based speaker verification via utterance partitioning,” IEEE Trans. Audio, Speech, Language Process., Vol. 21, No. 5, pp. 1012-1022, May 2013. https://doi.org/10.1109/TASL.2013.2243436
- R. Wallace and M. McLaren, “Total variability modelling for face verification,” IET Biometrics, Vol. 1, No. 4, pp. 188-199, Dec. 2012. https://doi.org/10.1049/iet-bmt.2012.0024
- M. S. Paja, T. H. Falk, and D. O'Shaughnessy, "Whispered speaker verification and gender detection using weighted instantaneous frequencies," in IEEE International Conference on Acoustics, Speech and Signal Processing (ICASSP), pp. 7209-7213, May 2013.
- S. A. O. Silva, R. Novochadlo, and R. A. Modesto, "Single-phase PLL structure using modified p-q theory for utility connected systems," in IEEE Power Electronics Specialists Conference(PESC), pp. 4706-4711, Jun. 2008.
- C. H. G. Santos, S. M. Silva, and B. J. C. Filho, "A fourier-based PLL for Single-Phase grid connected systems," in IEEE Energy Conversion Congress and Exposition(ECCE), pp. 2626-2632, Sep. 2010.
- K.-J. Lee, J.-P. Lee, D. Shin, D.-W. Yoo, and H.-J. Kim, “A novel grid synchronization PLL method based on adaptive low-pass notch filter for grid-connected PCS,” IEEE Trans. Ind. Electron., Vol. 61, No. 1, pp. 292-301, Jan. 2014. https://doi.org/10.1109/TIE.2013.2245622
- M. K. Ghartemani, S. A. Khajehoddin, P. K. Jain, and A. Bakhshai, “Problems of startup and phase jumps in PLL systems,” IEEE Trans. Power Electron., Vol. 27, No. 4, pp. 1830-1838, Apr. 2012. https://doi.org/10.1109/TPEL.2011.2169089
- J. He and Y. W. Li, “Hybrid voltage and current control approach for DG-grid interfacing converters with LCL filters,” IEEE Trans. Ind. Electron., Vol. 60, No. 5, pp. 1797-1809, May 2013. https://doi.org/10.1109/TIE.2012.2190374
- S. Mishra, D. Ramasubramanian, and P. C. Sekhar, “A seamless control methodology for a grid connected and isolated PV-diesel microgrid,” IEEE Trans. Power Syst., Vol. 28, No. 4, pp. 4393-4404, Nov. 2013. https://doi.org/10.1109/TPWRS.2013.2261098
- J. Li, J. Li, and S. Ding, "Research on a novel method for improving inverter output waveforms," in 5th IEEE Conference on Industrial Electronics and Applications (ICIEA), pp. 1194-1197, Jun. 2010.
- B. Singh, K. A. Haddad, and A. Chandra, “Harmonic elimination, reactive power compensation and load balancing in three-phase, four-wire electric distribution systems supplying non-linear loads,” Electric Power Systems Research, Vol. 44, No. 2, pp. 93-100. Feb. 1998. https://doi.org/10.1016/S0378-7796(97)01187-5
- J. Lianwei, D. Qinhua, and Z. Jiang, "Harmonic survey and solutions of Xining power grid in western China," in International Conference on Power System Technology, pp. 1161-1165, Dec. 2000.
Cited by
- Improved Three-Phase AFD Islanding Detection Based on Digital Control and Non-Detection Zone Elimination vol.11, pp.9, 2018, https://doi.org/10.3390/en11092421