Abstract
The insulation performance of the insulation currently used in building structures is reflected only during design based on initial performance and the reduction in heat insulation performance due to the degradation of long-term durability is not reflected. This study reviewed the degradation of heat insulation performance due to the durability degradation of insulating materials through the accelerated durability test. The study findings showed that the foamed polystyrene insulation bead method did not show performance degradation due to aging in the standard environmental condition and laboratory accelerated test condition but the performance is degraded in the freeze-thaw test condition. On the other hand, in the case of the extrusion method, the degradation of the heat insulation performance was less in the freeze-thaw test condition, but the rapid performance degradation was caused by the release of the internal gas at the beginning of aging. In addition, the hard polyurethane foam insulation showed better initial insulation performance than other insulation materials, but the performance was found to be degraded somewhat under laboratory accelerated test conditions and freeze-thaw test conditions.
현재 건축구조물에 사용되는 단열재의 단열성능은 초기성능을 기준으로 설계 시에만 반영하고 있으며, 장기 내구성 저하에 따른 단열성능 감소는 반영되고 있지 않다. 본 연구에서는 가속내구성 시험을 통해 단열재의 내구성 저하에 따른 단열성능 저하를 검토하였다. 연구결과, 발포폴리스티렌 단열재 비드법의 경우 표준환경 조건 및 실험실 가속 시험 조건에서는 경시변화에 따른 성능저하가 나타나지 않았으나, 동결 융해 시험 조건에는 성능이 저하하는 것으로 나타났다. 반면, 압출법의 경우 동결 융해 시험 조건에서는 단열성능 저하가 작았지만, 경시변화 초기에 내부 가스의 방출로 급격한 성능저하를 나타내었다. 또한, 경질 폴리우레탄 폼 단열재의 경우 다른 단열재에 비해 초기 단열성능이 매우 뛰어났으나, 실험실 가속 시험조건 및 동결 융해 시험 조건에서는 성능이 다소 저하하는 것으로 나타났다.