한국입자에어로졸학회지 (Particle and aerosol research)
- 제11권2호
- /
- Pages.37-46
- /
- 2015
- /
- 1738-8716(pISSN)
- /
- 2287-8130(eISSN)
DOI QR Code
지하철 공조실 미세먼지에 대한 자성포집연구
Study of Magnetic Filtration for Subway MVAC Dust
-
Park, Hae Woo
(Department of Applied Environmental Science, Kyunghee University) ;
- Chung, Sang Gui (Department of Environmental Engineering, Kunkook University) ;
-
Jo, Young Min
(Department of Applied Environmental Science, Kyunghee University)
- 투고 : 2015.06.21
- 심사 : 2015.06.29
- 발행 : 2015.06.30
초록
Dust particles, which inflow to the subway mechanical ventilation and air conditioning(MVAC) chamber, contain a fair amount of iron compounds, approximately 25.2w/w%. This work attempted to capture those iron containing dust using magnetic filters. Average magnetization value of the test MVAC dust was 0.012 emu on 5,000 Oe, which could correspond sufficiently with the magnetic interaction. External permanent magnets provided with magnetization of iron mesh screen showing high gradient magnetic field(HGM). It resulted in the capture efficiency with 84.0 ~ 99.7% and 81.2 ~ 99.8% for