An Experimental Study on the Ensuring the Fire Resistance Performance of Non-Refractory Coating CFT

무내화피복 CFT 공법의 내화성능 확보를 위한 실험적 연구

  • Lee, Ji-Hwan (Department of Architectural Engineering, Cheong-Ju University) ;
  • Han, Min-Cheol (Department of Architectural Engineering, Cheong-Ju University)
  • Received : 2015.02.03
  • Accepted : 2015.04.13
  • Published : 2015.06.20

Abstract

In this study, tests were carried out to find out a method to ensure the fire resistance performance of high-performance non-refractory coating CFT columns. For the high performance concrete fabrication with 100MPa, blast furnace slag(BS) and steel and nylon fibers were used. It was found that the partial replacement with BS improved the fire resistance performance of the concrete. Based on the results of lab tests, the large fire test was conducted. For this test, the CFTs with the size of ${\phi}500{\times}4,200mm$ and the reinforcement of SS 400 steel were prepared and they were subjected to a loading condition. It was found that as the level of load increased, the level of fire resistance decreased. For example, In with the loading condition of 2000kN the CFT could resist the fire for over 240 minutes, whereas, with the loading condition of 3,000kN and 4000kN applying to equivalent CFTs, the resisting time against fire were 184 minutes, and 120 minutes, respectively.

본 연구는 3시간 내화성능을 만족할 수 있는 고성능 무내화피복 CFT 기둥 개발을 위한 연구로서, 고로슬래그 미분말 치환율에 따른 성능평가를 실시한 결과 고로슬래그 미분말 치환율이 증가함에 따라 내화성능이 개선되는 것을 확인 할 수 있었으며, 내화성능을 고려한 CFT 기둥용 100MPa 충전콘크리트의 고로슬래그 미분말 적정 사용량은 40%로 나타났다. 이에 따라 고로슬래그 미분말 40% 혼입 100MPa 충전콘크리트를 적용한 CFT 실물 시험체를 대상으로 재하하중별 내화시험을 실시한 결과 재하하중이 증가함에 따라 내화성능 발현시간이 감소하는 것으로 나타났으며, 재하하중 2,000kN에서는 240분 이상의 내화성능을 나타내었고, 3,000kN에서는 184분, 4,000kN에서는 120분의 내화성능을 나타내었다.

Keywords

References

  1. Kim WJ, Lee YD, Park HG, Lee JS,Jung SJ. Research on the mock-up fo CFT using 100MPa high strength concrete and 800MPa strength steel. Proceedings of the Korea Institute of Building Construction; 2011 May 20; Dong-eui University, Busan, Korea. Korea Institute of Building Construction; 2011. p.35-7.
  2. Kim KY, Kim YS, Lee TG, Kang SJ, Kim MH. An experimental study on the evaluation of fire-resist performance of high-strength concrete filled steel tube column. Journal of Architectural Institute of Korea. 2008 Aug;24(8):147-54.
  3. Han HC, Kim YG, Kang SJ, Choi, SM. The 1st site application of non-fire-protection CFT columns. Jounal of Korean society of steel construction. 2007 Jun; 19(2):77-83.
  4. Cho KS, Kim HY, Kim HJ, Kwon IK. The study on the fire resistance performance of the CFT column according to the concrete compressive strength and load ratio. The 1st site application of non-fire-protection CFT columns. Journal of the Korean Institute of Fire Science & Engineering 2010 Apr;24(2):44-51.
  5. Hong SB, Kim WJ, Pare HG. Development and Application of CFT without Fire Protection using High Performance Steel and Concrete. Journal of the Korea Institute of Building Construction. 2013. Jun; 13(3):p.272-6. https://doi.org/10.5345/JKIBC.2013.13.3.272
  6. H.Y. Wang. The effects of elevated temperature on cement paste containing GGBFS. Cement and Concrete Composites. 2008 Nov;30(10):992-9. https://doi.org/10.1016/j.cemconcomp.2007.12.003
  7. C.S. Poon, A. Salmam, A. Mike, Y.L. Wang . Performance of metakaolin concrete at elevated temperatures. Cement and Concrete Composites. 2003 Jan;25(1):1291-300.
  8. ACI Committee 233. "Ground Granulated Blast Furnce Slag as a Cementitious Constituent in Concrete". 1995
  9. Korean Standards Association. KS F 2257-1 Methods of fire resistance test for elements of building construction-general requirements. Seoul(Korea) : 2010.
  10. Korean Standards Association.. KS F 2257-7 Methods of fire resistance test for elements of building construction-specific requirements for columns. Seoul(Korea) : 2011.
  11. Jung KH. Application of Concrete Filled Steel Tube Using High Strength Concrete[Dissertation]. [Seoul]: University of Dankook; 2004. 241 p.