Abstract
As modern houses are constructed with high-density and high-insulation, there is benefit to reduce energy consumption, but there are many side effects raised from polluted air. To solve the problem, a ventilation system is used to improve a indoor air quality. In this research, we experimentally estimate ventilation performance of HRV(heat recovery ventilator) with heat-pipe according to working fluid filling quantity and ventilation. Heat-pipe used in this study was designated separately to be applied to a ventilation system. The working fluid was R22, which was filled from 40 to 55 (%vol.) by 5(%vol.). Ventilation based on the front velocity was measured from 0.3 m/s to 1.5 m/s by 0.3 m/s intervals. Refrigerant filling quantity with the highest efficiency was found to depend on the ventilation. From this study the optimal refrigerant filling quantity in accordance with the ventilation of the detachable heat pipes was found experimentally.
현대 주택이 고기밀 고단열로 건축되기 때문에 에너지 절감의 이점이 있는 반면 오염된 공기로 인한 많은 부작용이 발생하고 있다. 이런 부작용을 해결하기 위해 환기장치를 사용하여 실내 공기 환경을 개선하고 있다. 본 연구에서는 폐열회수 환기장치의 일종인 히트파이프를 사용하여 작동유체 충진량 및 환기량에 따른 히트파이프의 환기성능을 시험적으로 평가하였다. 본 연구에서 사용된 히트 파이프는 환기장치에 적용이 가능하도록 분리형으로 제작되었다. 작동유체는 R22이고 유체의 충진량은 40~55(%vol.)로 5(%vol.) 단위로 충진 하였다. 환기량은 전면풍속을 기준으로 0.3~1.5m/s로 0.3 m/s 간격으로 바꿔 가며 측정하였다. 시험결과 최대 효율을 가지는 냉매 충진량이 환기량에 따라 다름을 알 수 있었고, 실험 결과 분석을 통하여 분리형 히트파이프의 환기량에 따른 최적 냉매 충진량을 찾을 수 있었다.