초록

A fire sprinkler system is very important to extinguish fire in the building. The sprinkler system initiates sprinkler discharge if the detection system identifies a developing fire and opens the pre-action valve. However, pre-action fire sprinkler systems mainly installed in the underground parking lot at the apartment complex do not properly operate at fire if the connection type of fire sprinkler systems does not properly installed and operated. This study identified the relationship between fire dispersion & damage and the connection type of water supply in the sprinkler system from many fire cases at the apartment complex in South Korea. In addition, this study also identified the water supply differences and characteristics between South Korea and foreign countries. The main purpose of this study is also to improve the water connection types in the sprinkler system that can reduce the potential failures of pre-action valve operation through electrical signal system. The study also suggests the improvement plan for water connection types in pre-action fire sprinkler system that can minimize potential failure of pre-action fire sprinkler system. The suggestions for revising the fire safe standard in South Korea includes letting the water supply pipe of sprinkler system water inlet connect to the second side of pre-action valve and the water flow device that can minimize potential failure of sprinkler system.

키워드

참고문헌

  1. NFSC 103.(2015) "Sprinkler Systems for National Fire Safety Codes"National Emergency Management
  2. Yoon-Hag An(2013), Apartment Undergroun d Parking Lot The Vehicle Fire Can Damage Teens. YTN,
  3. Tae-Wan Kim(2010), "Fire Protection System of Understanding I", Sobang Moonhwasa, 351-355
  4. Sang-Uk Nam(2010), "Design and Construction of Fire Protection System" Seongandang, 1-395-1-397
  5. Hyeon-Cheol Sin(2011), "The Study on Countermeasure High-Rise Building Fire" Master's thesis, Mokwon Univ
  6. Eung-jin Kim(2013),"An Experimental Study on the Effective Using of Fire Department Connection in High-rise Building"17-19, Master's thesis, Kyonggi Univ
  7. Ministry of Public Safety and Security(2015) "A Perspective on the Establishment Gear in 2014, Fire Occurrence" 11
  8. NFPA13 (2010) Edition "FIGURE A.8.16.1.1 Examples of Acceptable Valve Arrangements" 13-286