Abstract
A directional feeding method at the railway transformer is applied for supplying the power to the electric railway substations, and the pre-installed facilities with common feeder are utilized in preparation for the failure of feeding system and in finding a fault location in case that the catenary failure occurs. However, it is some difficulty in finding the fault location since there is an interface problem with the facilities when the supplying power system operates. In this paper, Auto Fault Locator Transfer Drive System (ALTDS) is designed to search for the fault location efficiently, and the measuring data are obtained and compared with the KORAIL standards. Further, the ground connection test is accomplished 24 times as the verification method, and it is shown that the methodology provides better performance than the existing traditional one.
전기철도에 전력을 공급하기 위하여 철도변전소에서는 급전특성상 방면별 급전을 시행하고 있으며, 급전계통에 고장이 발생하는 경우를 대비한 공통반 차단기와 같은 예비설비와 전차선로 고장 발생 시 고장위치를 찾기 위해 고장점 표정장치를 설치하여 사용 중에 있다. 그러나, 고장 발생 시 공통반 차단기를 사용하여 급전계통을 운용하는 경우에는 고장점 표정반과의 인터페이스가 되지 않아 고장위치를 찾는데 어려움이 있다. 본 논문은 이러한 문제점을 해결하기 위한 고장점 표정반 자동절체 시스템을 설계하고 동작 상태를 검증한다. 또한 자동절체 시스템을 공통반 차단기에 설치한 후 검증방법으로 설정된 24회의 지락시험을 통하여 성능시험을 수행하였으며 고장점 표정장치를 이용하여 기존의 고장위치를 효율적으로 검지하는 방법을 제시하는 데 있다.