초록
The cable degradation process is largely divided into three steps; Step 1 : Thermal degradation, Step 2 : Weibull degradation, Step 3 : Partial discharge. it is progress in step order. This article aims to explain the process of cable degradation using the method of insulation resistance and accordingly to compose and manufacture a system of measuring the life of electrical cable. Before measuring the insulation resistance, a system of measuring the temperature and current of cables was made, and the established system was installed for test on the site of a power plant to collect the measured data. The current sensor was used TFC30P80A-CL420, and temperature sensor was used the DK-1270 PT100 sensor as RTD sensor. When measured the temperature and the load current at the same position, was confirmed that in case of the load current value was high, also temperature value high. Therefore, the correlation between load currents and temperature was verified, and the analysis of diagnostic data was evaluated, which could be utilized in identifying the fault condition of cable systems.