Design of DC Side Voltage and Compensation Analysis of THD for Shunt Power Quality Controller under System Load of Rectifier with R-L Load

  • Zhao, Guopeng (state Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, School of Electrical and Electronic Engineering, North China Electric Power University) ;
  • Han, Minxiao (State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, School of Electrical and Electronic Engineering, North China Electric Power University)
  • Received : 2013.03.19
  • Accepted : 2014.09.04
  • Published : 2015.01.01

Abstract

For a shunt power quality controller (SPQC) the DC side voltage value which is closely related to the compensation performance is a significant parameter. Buy so far, very little discussion has been conducted on this in a quantitative manner by previous publications. In this paper, a method to design the DC side voltage of SPQC is presented according to the compensation performance in the single-phase system and the three-phase system respectively. First, for the reactive current and the harmonic current compensation, a required minimal value of the DC side voltage with a zero total harmonic distortion (THD) of the source current and a unit power factor is obtained for a typical load, through the equivalent circuit analysis and the Fourier Transform analytical expressions. Second, when the DC side voltage of SPQC is lower than the above-obtained minimal value, the quantitative relationship between the DC side voltage and the THD after compensation is also elaborated using the curve diagram. Hardware experimental results verify the design method.

Keywords

1. Introduction

As advanced equipment for improving the power quality, Shunt Power Quality Controller (SPQC) combines the functions of Shunt Active Power Filter (SAPF) [1, 2] and Static Synchronous Compensator (STATCOM) [3, 4]. The SPQC can be used to compensate both the reactive current and the harmonic current. Three-phase voltage source converter is widely employed in SPQC [5]. The SPQC has a DC side voltage control loop to keep the DC side voltage as a constant which has a big influence on the compensation performance. When the SPQC is used to compensate the reactive current and the harmonic current, the higher the DC side voltage is, the better the compensation result is. However, with higher DC side voltage, voltage stress of the power device will be larger, and it will increase the cost. In addition, higher DC side voltage will cause bigger converter losses. So, in order to reduce the losses in practical applications, it is desirable to make the constant rated value of the DC side voltage as low as possible. According to the analysis above, the choice of the DC side voltage constant rated value of SPQC is very important, and needs a detailed quantitative analysis and specification.

The researches on the DC side capacitor and DC voltage are very important. In many applications, the DC side voltage is controlled as a constant [6-8]. In [9], for a given DC side voltage, the maximum fundamental out voltage was shown in a wind generating system, and, it was very useful that the paper presented the relationship between the DC side voltage and the maximum fundamental output voltage. Furthermore, in [10], the selection of the DC side voltage for the Static Var Generator was presented, and the relationship between the compensation performance and the DC side voltage was also analyzed. These two papers mainly focused on the DC side voltage with the fundamental output voltage. However, the situation that the output voltage and the output current were the harmonic components was not discussed in these two papers. For the PAPF, in [11], an approximate value of the DC side voltage was presented, and the DC side voltage was selected as 1~1.3 p.u.. In [11], the DC side voltage selection methods presented approximate values. However the DC side voltage should be selected more accurately. In [12], the values of the DC side voltage were selected by considering the capability of reactive power compensation and harmonics current reduction. And, the capacitor value was designed to reduce the fluctuations of the DC side voltage caused by load unbalance and load change. The selection method of the DC side voltage was more accurate, but it may be a little complex. Especially, it is difficult to obtain the capability of harmonics current reduction. In [13], the DC side voltage reference was constant and was determined by simulation and experimental studies. Simulation method was valid, but it was inconvenient. In order to design an accurate DC side voltage, in [14], the effect of the DC side voltage on the compensation performance of a PAPF was studied by focusing on 5th negative and 7th positive harmonic sequences. The minimal required DC side voltage for the linear modulation range was presented. But, only focusing on 5th and 7th harmonics was not comprehensive, and the method, which was mentioned in [14] to determine a DC side voltage value for all harmonic currents, was too complex. An accurate method to select the DC side voltage was presented in [15] for the system load with phase control six-pulse converter. The minimal DC side voltage was obtained by using the voltage instantaneous space vectors in the d-q orthogonal coordinates. The optimal instantaneous space vectors voltage was the minimum voltage that always existed inside the hexagon when the SVPWM was used. The selection method of the minimal DC side voltage mentioned in [15] was very useful. However, the further study should be presented when the DC side voltage was smaller than the minimal value, because the full compensation for harmonic current was not necessary at most of situations. When the DC side voltage is smaller than the minimal value and the modulation is nonlinear, the influence of the DC side voltage on the compensation performance has not been discussed in published papers. The relationship between the compensation performance and the DC side voltage should be analyzed in a quantitative manner.

This paper focuses on the design method of the DC voltage and the relationship between the compensation performance and the DC voltage. Specifically, the contributions of this paper are:

1) A required minimal value of the DC voltage for full compensation is presented. 2) For the situation where the DC voltage is smaller than the above-obtained minimal value, the quantitative relationship is detailed between the DC voltage value and the THD after compensation. 3) The DC side voltages of the single-phase system, the three-phase system with SPWM control and the three-phase system with SVPWM control are analyzed respectively.

 

2. DC Side Voltage Analysis and Specification

2.1 System configuration

There are two types of systems which are the single-phase system shown in Fig. 1 and the three-phase system shown in Fig. 2, where uk(k=a, b, c) is the instantaneous value of the source phase voltage, iLk is the instantaneous value of the load phase current, isk is the instantaneous value of the source phase current, ick is the instantaneous value of the output phase current, and Udc is the average value of the DC side voltage. Assume that the system is balanced, the single-phase equivalent circuit is shown in Fig. 3, where us is the instantaneous value of the source voltage, uL is the instantaneous value of the voltage of inductor, ic is the instantaneous value of the output current, uI is the instantaneous value of the output voltage of converter. The losses of the converter are regarded as the active power in the resistor of the inductor [16].

Fig. 1.Single-phase main circuit of the SPQC

Fig. 2.Three-phase main circuit of the SPQC

Fig. 3.Circuits of the principle of superposition

2.2 Design of DC side voltage

The method of analysis adopts the superposition principle of the single-phase equivalent circuit in Fig. 3, and the relationship equations are shown in Eqs. (1) and (2).

The maximal value of the output voltage (uI_max) and the DC side voltage are shown in Eqs. (3) and (4), where k=1 for the single-phase system, k = 1/2 for the Sinusoidal Pulse Width Modulation (SPWM) and for the Space Vector Pulse Width Modulation (SVPWM) of the three-phase system [17-19]. The modulation index m=1.

There are two basic issues for the PWM control of SPQC: The minimal DC side voltage for full compensation; and the influence on the THD of the source current when the DC side voltage is lower than the minimal value for the part compensation.

The system load is the rectifier with resistive and inductive load. The system load current and the output reference current are shown in Figs. 4 and Fig. 5. In Fig. 4, the single-phase load current is the ideal quadrate waveform. In Fig. 5, in the three-phase system, it is not an ideal waveform and it can be considered as a trapezoidal waveform which the overlap angles are less than 10º (usually occurring in electrical plants) [20].

Fig. 4.System load current and reference current (single phase)

Fig. 5.System load current and reference current (three phases)

2.3 Minimal DC side voltage at full compensation (For Single-phase System)

By using the Fourier analysis, the load current can be expressed as Eq. (5), where ω is the radian frequency of the fundamental component. The output reference current is shown in Eq. (6).

The inductor voltage can be expressed as Eq. (7).

Assume that

The output current can be shown as Eq. (9).

According Eqs. (7) and (9), the waveform of f1(ωt) is shown in the Appendix by using the mathematical software. The peak value of f1(ωt) in Eq. (8) is 25.9 at ωt=0. Because the peak value of ωLIchf1(ωt) is much larger than the peak value of the source voltage, the peak value of the output voltage can be expressed as Eq. (10), where the source phase voltage is is the phase between the source phase voltage and the source phase current, and Icq is the RMS value of the output reactive current (assume that Icq is RMS value of the required output reactive current).

When the output harmonic current is zero, the DC side voltage is 1.414(Us+ωLIcq). From Eq. (10), the DC side voltage is related to the phase φ and the output harmonic current. Assume that the base of per-unit is (Us+ωLIcq) and kL=ωLIch/(Us+ωLIcq), the DC side voltage in Eq. (10) can be expressed as Eq. (11). The minimal DC side voltage with the typical values of phase φ is illustrated in Fig. 6. If the peak value of 25.9ωLIchf1(ωt) is smaller than the value of (Us+ωLIcq), the DC side voltage is determined by the peak value of (Us+ωLIcq). When the DC side voltage is lower than 1.414(Us+ωLIcq), the DC side voltage is chosen as 1.414(Us+ωLIcq). So, there is an inflection point of the curves. The current of harmonic orders from 5th to 25th is just considered.

Fig. 6.Relationship between the minimal DC side voltage and kL (single phase)

2.4 Minimal DC side voltage at full compensation (For Three-phase system with SPWM control)

When the SPWM is used in three-phase system, the load current from 0~π can be considered as Eq. (12) from Fig. 5, where γ1 is overlap angle.

The Fourier series of load current from 0 to 2π is shown in Eq. (13). And, the output reference current can be obtained as Eq. (14). The RMS value of the output reference current is expressed as Eq. (15), when the current of harmonic orders from 5th to 25th is just considered.

Assume that the inductor voltage is uL. Ich is the RMS of output current of phase a. uL can be expressed as Eq. (16).

Where

The peak value of f2(ωt) is f(γ1). By using the mathematical software, the values of f(γ1) can be obtained according to γ1. The relationship between f(γ1) and γ1 is illustrated in Fig. 7. From Fig. 7, the value of f(γ1) can be gotten according to the value of γ1.

Fig. 7.Relationship between f(γ1) and γ1

Because the peak value of ωLIchf(γ1) is much larger than the peak value of the source voltage, the value of the output voltage reaches the peak value at ωt=π/6. The minimal DC side voltage is shown in Eq. (18). The DC side voltage in Eq. (18) can be expressed as Eq. (19). And, the relationship between the minimal value and kL are carried out in Fig. 8 with different γ1 and φ.

Fig. 8.Relationship between the minimal DC side voltage and kL (three-phase system with SPWM control)

2.5 Minimal DC side voltage at full compensation (For three-phase system with SVPWM control)

When the SVPWM is used in three-phase system, the output voltages of inverter are shown in Eq. (20). The output voltages are transformed into α-β frame, and the voltage vector are expressed as Eq. (21) and Eq. (22) [21, 22]. The switching vectors are shown in Eq. (23). If the voltage vector exists inside the hexagon in Fig. 9, the THD of the source current after compensation is zero [14].

Fig. 9.Relationship between space vector and hexagon (for full compensation)

The minimal DC side voltage is shown in Fig. 10 with different γ1 and φ by using the mathematical software.

Fig. 10.Relationship between the minimal DC side voltage and kL (three-phase system with SVPWM control)

 

3. Analysis of Compensation Characteristics with DC Side Voltage Lower than the Minimal Value

In order to reduce the DC side voltage, the compensation performance can be reduced, as long as the requirement of THD after compensation is satisfied. When the DC side voltage is lower than the minimal value, the modulation control is the non-linear control. It is very difficult to analyze the relationship between the compensation performance and the DC side voltage. A group of simulation results are present to obtain the relationship between the compensation performance and the DC side voltage in this paper.

3.1 For single-phase system

In Fig. 11, with different φ and kL, the THD of the source current is presented. The THD becomes unregulated when the DC side voltage is lower than 1.414 times of the peak value of the source voltage. Because the DC side voltage of inverter is 1.414 p.u. when the output current is zero. If Icq is changed, the base of per-unit is also changed to (Us+ωLIcq), and Udc_pu in the figure is based on the per-unit value.

Fig. 11.Relationship between DC side voltage and compensation performance (single phase)

3.2 For three-phase system with SPWM control

When the DC side voltage is lower than the minimal value, the modulation control is the non-linear control. A group of simulation results are present to obtain the relationship between the compensation performance and the DC side voltage in this paper. From Fig. 12, with different φ, kL and γ1, the THD of the source current after compensation is presented. With those curves, the relationship between the compensation performance and the DC side voltage are obtained.

Fig. 12.Relationship between DC side voltage and compensation performance for three-phase system with SPWM control

3.3 For Three-phase system with SVPWM control

When the DC side voltage is lower than the minimal value, the THD of the source current after compensation is presented in Fig. 13 with different φ, kL and γ1 by using the simulation software.

Fig. 13.Relationship between DC side voltage and compensation performance for three-phase system with SVPWM control

 

4. Simulation and Experimental Results

The simulation investigation and the experiment were carried out to verify the minimal DC side voltage equations and the output current equations after changing DC side voltages.

For a design example, in three-phase system for full compensation, the DC side voltage was related to the phase angle between the source phase voltage and the peak value of inductor voltage. When the system load was diode rectifier with resistive and inductive load, the phase angle was 0º. In Fig. 14, the inductor was 0.4mH. The RMS of the source phase voltage was 220V. The output current (RMS) was 93.6A.The modulation index was 1, and the triangular wave modulation SPWM was used.

Fig. 14.Compensation result with the minimal DC side voltage (for SPWM)

In Fig. 14, the overlap angle was γ1=0 and the DC side voltage for full compensation was 1104V according to the theoretical analysis. The compensation result was acceptable with a minimal DC side voltage 1104V and the THD of the source current after compensation was 0.5% (harmonic current from 5th to 25th order was just considered), which approximately equaled to the theoretical value (0%). The simulation results verified the analysis and the conclusion about the minimal DC side voltage. Because of the current tracking error and the dead time of PWM, in practical applications, the DC side voltage should be higher than the theoretical value, when the SPQC is designed. The theoretical value is the best situation with zero tracking error and one modulation index. The Eq. (11), Eq. (19) and diagrams can be used as a reference of the best situation. However, in the practical applications, the voltage which is lower than 1104V is used, as the compensation result with a THD lower than 5% is satisfied.

In order to verify the analysis results, the hardware experiment has been carried out which is shown in Fig. 15. For a design example, the three-phase inverter was used. The DSP TMS320F2812 was used to realize the direct current control strategy and the PWM control method. The peak value of the phase source voltage is Us=70.7V, the inductor is 5.5mH, the capacitor of DC side is 3333uF, and Icq is zero.

Fig. 15.Experimental hardware view

For the SPWM control, in Fig. 16, the overlap angle was 5.9 º and γ1≈17. The output current was 0.086 p.u., and the theoretical DC side voltage was 6.963 p.u.. The dead time of PWM was 4μs and the switching frequency was 15kHz, so the error was approximately 6%, then the minimal DC side voltage was modified as 7.558 p.u.. In Fig. 17, the source current after compensation was presented with the minimal DC side voltage. The THD of the source current was very small and it was 3.5%( from 5th to 25th) after compensation. From the experimental results, the selection method of the minimal DC side voltage was verified. Because of the current tracking error and the dead time of PWM, in practical applications, the DC side voltage should be higher than the theoretical value, when the SPQC was designed. The theoretical value was the best situation with a zero tracking error and one modulation index. The Eq. (19) and diagrams can be used as a reference of the best situation.

Fig. 16.Load current

Fig. 17.Source current after compensation

The simulation and experimental results verified the design method of the DC side voltage. For a design point of view, the equations and curves of DC side voltage can be used as reference to determine DC side voltage. The dead time of PWM and the current tracking error should be considered, and chooses a suitable DC side voltage according to the desired THD.

 

5. Conclusion

In this paper, a method to design the DC side voltage of SPQC and the DC side voltage rated value are presented according to the compensation performance. A required minimal value of the DC side voltage for full compensation is obtained for a typical harmonic current. In order to reduce the DC side voltage, the compensation performance can be reduced, as long as the requirement of THD after compensation is satisfied. The quantitative relationship between the DC voltage and the THD after compensation is detailed when the DC voltage is smaller than the aboveobtained minimal value by using the curve diagrams. The curve diagrams can be used as a reference of the best situation, and the DC side voltage should be higher than the best situation with the tracking error and dead time. Hardware experimental results verify the validity of the design method.

References

  1. Ji-Ho Park and Young-Sik Baek, “Coordination Control of Voltage Between STATCOM and Reactive Power Compensation Devices in Steady-State,” J. Electr. Eng. Technol., vol. 7, no. 5, pp. 689-697, Sep. 2012. https://doi.org/10.5370/JEET.2012.7.5.689
  2. Wen-Hao Zhang, Seung-Jae Lee and Myeon-Song Choi, “Setting Considerations of Distance Relay for Transmission Line with STATCOM,” J. Electr. Eng. Technol., vol. 5, no. 4, pp. 522-527, Dec. 2010. https://doi.org/10.5370/JEET.2010.5.4.522
  3. Yash Pal, A. Swarup and Bhim Singh, “A Novel Control Strategy of Three-phase, Four-wire UPQC for Power Quality Improvement,” J. Electr. Eng. Technol., vol. 7, no. 1, pp. 1-8, Jan. 2012. https://doi.org/10.5370/JEET.2012.7.1.1
  4. Jun-Bo Sim, Ki-Cheol Kim, Rak-Won Son and Joong-Ki Oh, “Ride-through of PMSG Wind Power System Under the Distorted and Unbalanced Grid Voltage Dips,” J. Electr. Eng. Technol., vol. 7, no. 6, pp. 898-904, Nov. 2012. https://doi.org/10.5370/JEET.2012.7.6.898
  5. Sung-Eun Lee, Dong-Jun Won and Il-Yop Chung, “Operation Scheme for a Wind Farm to Mitigate Output Power Variation,” J. Electr. Eng. Technol., vol. 7, no. 6, pp. 869-875, Nov. 2012 https://doi.org/10.5370/JEET.2012.7.6.869
  6. M. Reyes, P. Rodriguez, S. Vazquez, A. Luna, R. Teodorescu, and J. M. Carrasco, “Enhanced Decoupled Double Synchronous Reference Frame Current Controller for Unbalanced Grid-Voltage Conditions,” IEEE Trans. Power Electron., vol. 27, no. 9, pp. 3934-3943, May 2012. https://doi.org/10.1109/TPEL.2012.2190147
  7. Van-Tung Phan and Hong-Hee Lee, “Enhanced Proportional-Resonant Current Controller for Unbalanced Stand-alone DFIG-based Wind Turbines,” J. Electr. Eng. Technol., vol. 5, no. 3, pp. 443-450, Sep. 2010. https://doi.org/10.5370/JEET.2010.5.3.443
  8. Young-Do Choy, Byung-Moon Han, Jun-Young Lee and Gilsoo Jang, “Real-Time Hardware Simulator for Grid-Tied PMSG Wind Power System,” J. Electr. Eng. Technol., vol. 6, no. 3, pp. 375-383, May 2011. https://doi.org/10.5370/JEET.2011.6.3.375
  9. S. W. Mohod, M. Aware, “Analysis and design of a grid connected wind generating system with VSC,” in Proceedings of 2008 IEEE Region 10 Conference, Hyderabad, India, Nov. 2008.
  10. G. P. Zhao, M. X. Han, “DC voltage design and corresponding compensation performance analysis for static var generator,” Int. J. Electr. Power & Energy Syst., vol. 43, no. 1, pp. 501-513, Dec. 2013.
  11. Y. B. Wang, J. W. Li, J. Yu, “Comprehensive analysis and design for one-cycle controlled DC side APF,” in Proceedings of IEEE Industrial Technology International Conference, Mumbai, India, Dec. 2006.
  12. S.J. Chiang, J. M. Chang, “Design and implementation of the parallelable active power filter,” in Proceedings of IEEE 30th Annual Power Electron. Specialists Conference, Charleston, SC, USA, Aug. 1999.
  13. S. Fukuda, D.S. Li, “A static synchronous compensator using hybrid multi-inverters,” in Proceedings of IEEE 35th Annual Power Electron. Specialists Conference, Aachen, Germany, June, 2004.
  14. A. Tarkiainen, R. Pollanen, M. Niemela, J. Pyrhonen, “DC-link voltage effects on properties of a shunt active filter,” in Proceedings of IEEE 35th Annual Power Electron. Specialists Conference, Aachen, Germany, June, 2004.
  15. H. Akagi, Y. Tsukamoto, A. Nabae, “Analysis and design of an active power filter using quad-series voltage source PWM converters,” IEEE Trans. on Ind. Appl., vol. 26, no. 1, pp. 93-98, Jan./Feb. 1990. https://doi.org/10.1109/28.52679
  16. G. P. Zhao, J. J. Liu, “Analysis and specifications of switching frequency in parallel active power filters regarding compensation characteristics,” J. Power Electron. vol. 10, no. 6, pp. 749-761, Nov. 2010. https://doi.org/10.6113/JPE.2010.10.6.749
  17. A. M. Hava, E. Demirkutlu, “Output voltage control of a four-leg inverter based three-phase UPS,” in Proceedings of 2007 European Conference on Power Electronics and Applications, Aalborg, Denmark, Sept. 2007.
  18. Young-Do Choy, Byung-Moon Han, Jun-Young Lee and Gilsoo Jang, “Real-Time Hardware Simulator for Grid-Tied PMSG Wind Power System,” J. Electr. Eng. Technol., vol. 6, no. 3, pp. 375-383, May 2011. https://doi.org/10.5370/JEET.2011.6.3.375
  19. Sol-Bin Lee, Kyo-Beum Lee, Dong-Choon Lee and Jang-Mok Kim, “An Improved Control Method for a DFIG in a Wind Turbine under an Unbalanced Grid Voltage Condition,” J. Electr. Eng. Technol., vol. 5, no. 4, pp. 614-622, Dec. 2010 https://doi.org/10.5370/JEET.2010.5.4.614
  20. A. Cavallini, M. Loggini, G.C. Montanari, “Comparison of approximate methods for estimate harmonic currents injected by AC/DC converters,” IEEE Trans. on Ind. Electron., vol. 41, no. 2, pp. 256-262, Apr. 1994. https://doi.org/10.1109/41.293887
  21. L. Asiminoaei, F. Blaabjerg, S. Hansen, “Evaluation of harmonic detection methods for active power filter applications,” in Proceedings of IEEE 2005 Twentieth Annual Applied Power Electronics Conference and Exposition, Austin, Texaa, USA, March, 2005.
  22. S.J. Lee, H. Kim, S.K. Sul, F. Blaabjerg, “A novel control algorithm for static series compensators by use of PQR instantaneous power theory,” IEEE Trans. on Power Electron., vol. 19, no. 3, pp. 814-827, May, 2004. https://doi.org/10.1109/TPEL.2004.826499

Cited by

  1. Numerical investigation of trichel pulse of negative corona discharge in N2–O2 mixture vol.50, pp.50, 2017, https://doi.org/10.1088/1361-6463/aa9604
  2. Hierarchical NiO–In2O3 microflower (3D)/ nanorod (1D) hetero-architecture as a supercapattery electrode with excellent cyclic stability vol.4, pp.13, 2016, https://doi.org/10.1039/C5TA10407F
  3. Realization of Unified Power Quality Conditioner for Mitigating All Voltage Collapse Issues vol.07, pp.06, 2016, https://doi.org/10.4236/cs.2016.76067
  4. Collecting public RGB-D datasets for human daily activity recognition vol.14, pp.4, 2017, https://doi.org/10.1177/1729881417709079
  5. Time-resolved analysis and optical diagnostics of Trichel corona in atmospheric air vol.49, pp.24, 2016, https://doi.org/10.1088/0022-3727/49/24/245206
  6. Polymer-based interconnection cables to integrate with flexible penetrating microelectrode arrays vol.19, pp.4, 2017, https://doi.org/10.1007/s10544-017-0217-9
  7. Precision control of a sensorless PM BLDC motor using PLL control algorithm 2017, https://doi.org/10.1007/s00202-017-0571-x
  8. Dynamic Economic Scheduling Strategy for a Stand-alone Microgrid System Containing Wind, PV Solar, Diesel Generator, Fuel Cell and Energy Storage:- A Case Study vol.168, pp.1755-1315, 2018, https://doi.org/10.1088/1755-1315/168/1/012006
  9. Multiple of Hybrid Lambda Iteration and Simulated Annealing Algorithm to Solve Economic Dispatch Problem with Ramp Rate Limit and Prohibited Operating Zones vol.14, pp.1, 2019, https://doi.org/10.1007/s42835-018-00001-z