Abstract
The purpose of this study was to measure the airtightness and Air-Flow Performance for 7th house of small apartment houses adopted window frame-type natural ventilation. All window and living room door is provide with window frame-type natural ventilation, and there is provide with manual controller. As the object of measurement, the 6th type small apartment houses with area of $33m^2$ to $51m^2$ was selected. airtightness performance was measured at the front door using Blower door system. We measured ventilation rate per hour on 50Pa pressure different between inside and outside by the 1st to 6th cases. As a result, when the natural ventilation frame was closed, average amounts are shown as the ventilation rate per hour were 2.27ACH (CASE1). and the result is similar to general apartment house (1.65~4.28ACH). When the natural ventilation frame was open, average amounts are shown as the ventilation rate per hour were 5.87ACH (CASE6). In addition, that's a 3.6ACH increased more than CASE1.
본 연구에서는 창문형 자연환기장치가 설치된 7개 세대의 소형공동주택($33m^2{\sim}51m^2$)을 대상으로 Blower Door를 이용한 현장 기밀성능 및 공기유동 성능을 측정하였다. 창문형 자연환기장치는 외기에 면하는 모든 창호 및 거실분합문에 설치되어 있으며, 수동 개폐형 장치가 설치되어있다. 본 연구에서는 자연환기장치와 창호의 개폐여부에 따라서 6개의 CASE를 설정하여 실측하였다. 측정결과, 자연환기장치와 모든 개구부를 밀폐한 상태의 기밀성능 값(CASE1)은 1.77~3.12ACH로 평균 2.27ACH로 나타났으며, 문헌조사 결과 자연환기장치가 설치되지 않은 일반 공동주택(1.65~4.28ACH)과 유사하게 나타났다. 내외측의 자연환기장치를 모두 열었을 때의 공기유동성능 값(CASE6)은 평균 5.87ACH로 나타나 밀폐조건과 비교하여 평균 3.6ACH가 증가하는 것으로 나타났다. 외측 환기장치와 창호를 밀폐한 조건에서 내측 환기장치만 개방시와 내측창을 개방시의 공기유동성능값의 차이는 평균 0.29ACH로 내측창호 개방시의 기밀성능 값이 높게 나타났다. 반대로 내측 환기장치와 창호를 밀폐한 조건에서 외측 환기장치만 개방시와 외측창 개방시의 차이는 평균 0.30ACH로 외측창호 개방시가 높게 나타났다. 내측창호만의 공기유동성능과 외측창호만의 공기유동성능 측정값의 차이는 0.77ACH로 내측창호가 더 우수하게 나타났다. 향후에는 자연환기장치와 창호 및 새시의 종류에 따른 기밀성능의 추가 측정을 통해 정량적 상관관계 조사가 필요할 것으로 판단된다.