1. Introduction
The key measures of a creative economy are the creation of many new jobs and increasing industry convergence, for instance, information and communication technology (ICT) fused with preexisting industry.
Currently, environmental concerns as well as energy supply and demand concerns are increasing. Even though government has constructed large scale new power plants and power grids every year to resolve the energy demand for peak power, there has been a reality confronting big trouble due to people’s objection. Furthermore, though the electric power demand in the industrial sector has been increasing annually, the power supply is not followed in time as the demand needs
This increase in power demand and the expansion of the power generating systems have led to an increase in fault current. Numerous studies for reducing the fault current, including those that applied a superconducting fault current limiter (SFCL) have been conducted [1-5]. Among the developed SFCLs, in the magnetic flux-lock type SFCL, the magnetic flux that is generated from the two coils offset each other during normal conditions. However, when a fault occurs, the resistance from the quenching of the high- Tc superconducting (HTSC) element generates the induced voltage through which the fault current is limited. Thus, it has a characteristic of being able to adjust the limit impedance and operational current through which the fault current is limited by adjusting the inductance ratio and the direction of the two coils of the magnetic flux-lock type SFCL [6-8]. On the other hand, the fault current that is greatly increased while the fault occurs may cause saturation of the core because of the increased magnetic flux inside the core, which would reduce the fault current limiting effects of the SFCL. To prevent this, SFCL structures using cores with two magnetic paths or using one core with a third separate coil have been proposed and reported [9-11]. However, to date, there is no reported research on the internal magnetic flux characteristics of the E-I core in a peak current limiting structure having a third coil and an additional HTSC element
Therefore, this study proposes an SFCL capable of preventing the occurrence of magnetic flux inside the core under normal conditions while preventing saturation in the core owing to the sudden occurrence of magnetic flux and having peak current limiting possibilities. The fault current limiting characteristics of the subtractive polarity winding and additive polarity winding cases and the voltage characteristics of the two HTSC elements have been analyzed through simulation experiments. Furthermore, exciting currents, and current limiting characteristics of each coil were analyzed for different winding directions of the first and second coils. Finally, the Joule heat of the HTSC element and the distribution of the magnetic flux were compared and analyzed for different winding directions. From the magnetic flux distribution analysis of the E-I core during the fault, it was observed that the SFCL with subtractive polarity winding is able to further reduce the saturation potential of the core when compared with the SFCL with additive polarity winding.
2. Theoretical Calculation
The peak current is limited primarily to reduce the fault current burden of the HTSC element by splitting the current limiting action when the fault current peak value is very high initially. As shown in Fig. 1, the SFCL having two magnetic paths consists of three coils on the E-I core and two HTSC elements. Its basic principle is that under normal conditions, the magnetic flux generated from two coils (N1, N2) that are connected in parallel offset each other. However, when a fault occurs, the resistance from the quench of the HTSC element that is connected in series with the second coil prevents the magnetic flux from being offset, which induces the voltage in each coil and limits the fault current. At the same time, the voltage is induced and the current flows in the third coil because of the magnetic flux, which is not offset, inside the core. Here, the induced magnetic flux in the core is large if the fault current is large in the initial stages, which significantly increases the induced current that flows in the third coil. When the critical current of the second HTSC element that is connected to the third coil exceeds, a resistance is created because of the quench, and the second peak current limiting action is carried out at the initial stages of the fault occurrence.
Fig. 1.Magnetic system of flux-lock-type SFCL with two magnetic paths using E-I core.
Fig. 2 shows the electrical equivalent circuit of the SFCL that has two HTSC elements with two magnetic paths using the duality method [12]. Here, Rl1, Rl2, and Rl3 each respectively denote the resistances of each winding whereas Ll1, Ll2, and Ll3 denote the leakage inductance of each winding. In addition, N1, N2, and N3 represent the number of turns of each coil. L1, L2, and L3 that are comprised of exiting branches are expressed as magnetization inductances of the E-I core. Here, the areas of the core are expressed as for L1, for L2, and for L3, Score is the area of core. Further, μ0 is the free space permeability, and μr is the relative permeability. From the equivalent circuit in Fig. 2, the exciting current and voltage across the exciting branch can be expressed as Eqs. (1) and (2).
Fig. 2Equivalent circuit of SFCL with two magnetic paths.
In Eq. (1), is equal to . v1 is the induced voltage in the first coil, and φ is the linkage flux of the E-I core. If each winding is tightly wound and the resistance of each winding is assumed to be small, the leakage inductance (Ll1, Ll2, and Ll3) and the resistance of each winding (Rl1, Rl2, and Rl3) can be neglected. Therefore, the linkage flux of the E-I core can be obtained by integrating the stray voltage in the first winding from t0 to t.
3. Experimental Results and Discussion
Table 1 shows the design parameters of the SFCL having two magnetic paths. YBa2Cu3O7-δ (YBCO) thin film having a critical temperature of 87 K was used as the HTSC element, which was connected to the second and third coils. To protect the thin film device from the heat generated during the quench, a 200-nm-thick Au layer was deposited. The value of the critical electric current was measured to be 27 A. Fig. 3 shows the schematic diagram of the experimental circuit used to simulate the occurrence of a fault, which comprises a 60 Hz AC power supply (Ein = 160 V), a line impedance (Li = 1.82 mH, Ri = 0.097 Ω), a load resistance (RLoad = 41.2 Ω), and the SFCL with two magnetic paths using the E-I core. A short circuit was induced for five cycles by turning on the switch SW2 during the fault cycle after inputting switch SW1; thereafter, the induced voltage and the current that flows in the three coils including the line and the HTSC elements 1 and 2 were measured and analyzed.
Table 1.Specifications of SFCL using E-I Core.
Fig. 3.Experimental circuit of SFCL having two magnetic paths
Fig. 4 shows the fault current limiting characteristics of the SFCL with two magnetic paths for different winding directions of the first and second coils before and after the occurrence of the fault as well as the voltage curves of the two HTSC elements. Fig. 4(a) shows the limited line current mode without and with the application of the SFCL based on the winding direction. It can be observed that at the start of the fault, the fault current is limited more effectively in the case of additive polarity winding when compared with that of subtractive polarity winding. As observed in Fig. 4(b), the fault and peak current limiting actions take place because a resistance is generated through the quench of HTSC elements 1 and 2 in the case of subtractive polarity winding.
Fig. 4.(a) Limited line currents and (b) voltage curves for each HTSC element of SFCL for different winding directions of the two coils.
Fig. 5 shows a comparison of the current limiting characteristics and exciting current mode of the SFCL with two magnetic paths that use the E-I core when the fault occurs at 0° for the subtractive and additive polarity winding cases. The exciting current can be determined by using Eq. (1). As seen in Fig. 5(a), in the subtractive polarity winding case, the current mode of the first coil is limiting the fault current as the exciting current is increasing without significant distortion. However, in the case of additive polarity winding, as shown in Fig. 5(b), the fault current limiting is less because the current that flows in the first, second, and third coils is greatly distorted. Even if the fault current is limited through the quench occurrence of the first HTSC element, the exciting current increases greatly because the saturation of the E-I core causes the second peak current of the first coil. Therefore, the saturation of the iron core must be taken into consideration for different winding directions between the two coils when designing the SFCL having two magnetic paths using the E-I core.
Fig. 5.Current limiting characteristics and exciting current of flux-lock-type SFCL having two magnetic paths for (a) subtractive and (b) additive polarity winding cases when fault occurs at 0° .
Fig. 6 shows the magnetic flux distribution of the SFCL having two magnetic paths and the Joule heat characteristics of each HTSC element with respect to the winding direction of the first and second coils when the fault occurs. Here, the magnetic flux of the three legs of the E-I core was calculated from the induced voltage of Eq. (3). In the subtractive polarity winding case, the Joule heat was significantly higher for HTSC element 1 when compared with HTSC element 2 and showed a gradual increase. It can be observed that the magnetic flux generated from the central and left legs of the E-I core flows to the right leg in case of the subtractive polarity winding during the fault. However, in the case of additive polarity winding, the magnetic flux generated from the central and left legs flows to the right leg very minimally. Additionally, most of the magnetic flux travels through the paths of the left and right legs. Therefore, the Joule heat is generated in only the first HTSC element. Therefore, the maximum value of the magnetic flux inter-linkage increases slightly more in the case of additive polarity winding when compared with that of the subtractive polarity winding, signifying that there is greater possibility of saturation in the iron core in the additive polarity winding case.
Fig. 6.(a) Magnetic flux of SFCL and Joule heat curve of each HTSC element for the subtractive polarity winding; (b) Magnetic flux of SFCL and Joule heat curve of each HTSC element for the additive polarity winding.
4. Conclusion
A peak current limiting structure in which the first and second coils are connected in parallel using one E-I core and an additional second HTSC element is used in the third coil is proposed in this study. The internal magnetic flux characteristics of the E-I core before and after the occurrence of the fault as well as the fault current limiting effects were analyzed through short-circuit simulation. Although the fault current limiting effects were slightly superior in the case of additive polarity winding, when compared with the subtractive polarity winding case, the fault current limiting action was observed to be present in only one HTSC element thus increasing the burden of the HTSC element and preventing the peak current limiting function. Furthermore, from the magnetic flux distribution, the maximum value of the magnetic flux inter-linkage and the value of the magnetization current were observed to be small in the subtractive polarity winding case, thus confirming that the saturation potential in the iron core can be reduced.
참고문헌
- T. Hara, T. Okuma, T. Yamamoto, D. Ito K. Tasaki, and K. Tsurunaga, "Development of a new 6.6 kV/1500 A class superconducting fault current limiter for electric power systems," IEEE Trans. Power Delivery, vol. 8, no. 1, pp. 182-192, June 1993. https://doi.org/10.1109/61.180335
- H. Kadoe and M. Ichikawa, "Performance of a high-Tc superconducting fault current limiter-design of a 6.6 kV magnetic shielding type superconducting fault current limiter," IEEE Trans. Appl. Supercon., vol. 7, no. 2, pp. 993-996, June 1997. https://doi.org/10.1109/77.614672
- Ok-Bae Hyun, Kwon-Bae Park, Jungwook Sim, Hye- Rim Kim, Seong-Woo Yim, and Il-Sung Oh "Introduction of a hybrid SFCL in KEPCO grid and local points at issue," IEEE Trans. Appl. Supercon., vol. 19, no. 3, pp. 1946-1949, June 2009. https://doi.org/10.1109/TASC.2009.2018256
- H. Yamaguchi, T. Kataoka, K. Yaguchi, S. Fujita, K. Yoshikawa, K. Kaiho, "Characteristics analysis of transformer type superconducting fault current limiter," IEEE Trans. Appl. Supercon., vol. 14, no. 2, pp. 815-818, June 2004. https://doi.org/10.1109/TASC.2004.830284
- S. H. Lim, Y. S. Cho, H. S. Choi, and B. S. Han, "Improvement of current limiting capability of HTSC elements in hybrid type SFCL," IEEE Trans. Appl. Supercon., vol. 17, no. 2, pp. 1807-1810, June 2007. https://doi.org/10.1109/TASC.2007.899246
- Sung-Hun Lim, Hyo-Sang Choi, Dong-Chul Chung, Seokcheol Ko, and Byoung-Sung Han, "Impedance variation of a flux-lock type SFCL dependent on winding direction between coil 1 and coil 2," IEEE Trans. Appl. Supercon., vol. 15, no. 2, pp. 2039-2042, June 2005. https://doi.org/10.1109/TASC.2005.849446
- Sung-Hun Lim, Seckcheol Ko, and Tae-Hee Han, "Analysis on current limiting characteristics of a transformer type SFCL with two triggering current levels," Physica C, vol. 484, pp. 253-257, January 2013. https://doi.org/10.1016/j.physc.2012.03.011
- Sung-Hun. Lim, H. S. Choi, and B. S. Han, "Fault current limiting characteristics due to winding direction between coil and coil 2 in a flux-lock type SFCL," Physica C, vol. 416, no. 3-4, pp. 34-42, November 2004. https://doi.org/10.1016/j.physc.2004.08.019
- S. H. Lim, H. S. Choi, and B. S. Han, "The improved hysteresis characteristics of flux-lock type SFCL using third winding," Physica C, vol. 406, no. 1-2, pp. 37-45, July 2004. https://doi.org/10.1016/j.physc.2004.02.177
- Seckcheol Ko, Sung-Hun Lim, and Tae-Hee Han, "Analysis on fault current limiting and recovery characteristics of a flux-lock type SFCL with an isolated transformer," Physica C, vol. 484, pp. 263- 266, January 2013. https://doi.org/10.1016/j.physc.2012.03.041
- S. H. Lim, S. C. Ko, and T. H. Han, "Hysteresis characteristics of flux-lock type SFCL with series connection of two coils," Physics Procedia, vol. 45, pp. 301-304, 2013. https://doi.org/10.1016/j.phpro.2013.05.027
- Minseok Joo, and Tae-Kuk Ko, "Improvement on Current Limiting Performance of Current Limiting Devices with Damping Coils," IEEE Trans. Appl. Supercon., vol. 9, no. 3, pp. 4613-4618, Sep., 1999. https://doi.org/10.1109/77.791917
피인용 문헌
- Comparison of Peak Current Limiting in Two Magnetically Coupled SFCLs Using Dual Iron Cores vol.26, pp.3, 2016, https://doi.org/10.1109/TASC.2015.2509183
- Analysis on Magnetizing Characteristics Due to Peak Fault Current Limiting Operation of a Modified Flux-Lock-Type SFCL With Two Magnetic Paths vol.26, pp.4, 2016, https://doi.org/10.1109/TASC.2016.2539976
- Current Limiting and Recovery Characteristics of Two Magnetically Coupled Type SFCL with Two Coils Connected in Parallel Using Dual Iron Cores vol.17, pp.5, 2016, https://doi.org/10.5762/KAIS.2016.17.5.717
- Comparative Study on Current Limiting Characteristics of Transformer-Type SFCL With Common Connection Point Between Two Secondary Windings vol.28, pp.3, 2018, https://doi.org/10.1109/TASC.2017.2786264