Automatic Power Factor Correction Using a Harmonic-Suppressed TCR Equipped with a New Adaptive Current Controller

  • 투고 : 2013.05.05
  • 심사 : 2014.03.25
  • 발행 : 2014.07.20

초록

In this paper, a new continuously and linearly controlled capacitive static VAR compensator is proposed for the automatic power factor correction of inductive single phase loads in 220V 50Hz power system networks. The compensator is constructed of a harmonic-suppressed TCR equipped with a new adaptive current controller. The harmonic-suppressed TCR is a new configuration that includes a thyristor controlled reactor (TCR) shunted by a passive third harmonic filter. In addition, the parallel configuration is connected to an AC source via a series first harmonic filter. The harmonic-suppressed TCR is designed so that negligible harmonic current components are injected into the AC source. The compensator is equipped with a new adaptive closed loop current controller, which responds linearly to reactive current demands. The no load operating losses of this compensator are negligible when compared to its capacitive reactive current rating. The proposed system is validated on PSpice which is very close in terms of performance to real hardware.

키워드

I. INTRODUCTION

Poor power factor is a challenging issue facing power quality achievement. It causes extra losses in transmission systems and power generation stations. In addition, it may restrict the transmission capability of transmission systems. Therefore, power factor correction is an effective remedy for this issue. The benefits of power factor correction include energy savings, transmission loss reductions, and the feasibility of operating transmission lines closer to their thermal limits. Effective tools used to achieve power factor correction include static VAR compensators such as fixed capacitor thyristor controlled reactors, thyristor switched capacitors (TSC), static synchronous compensators (statcom), and power converter based static VAR compensators [1]-[8]. The traditional thyristor controller reactor (TCR) is simply a reactor connected in series to two anti-parallel thyristors where the series combination is supplied by the phase or line to line voltage of the AC power system network. It is controlled continuously by the symmetric firing angles of its thyristors. It releases significant amounts of odd current harmonics. As a result, it requires the installation of harmonic filters at its location [9]-[11]. TCRs are considered to be an important application of what is known as Flexible Alternative of Current Transmission Systems (FACTS) devices, which represent the recent application of power electronics in transmission systems [12]-[16]. FACTS devices are designed to satisfy the real time demands of power systems. A TSC is constructed of a capacitor connected in series to two anti-parallel thyristors where the series combination is supplied by the phase or line to line voltage of an AC source. A compensator constructed of several TSCs is characterized by a stepwise capacitive reactive power response [17]-[19]. In the design of TCRs, and TSC based static VAR compensators, naturally commutated thyristors are usually employed. These kinds of compensators are commonly referred to as traditional static VAR compensators.

Power converter based static VAR compensators are constructed of either voltage source inverter (VSI) or current source inverter (CSI) [20]-[22]. They are designed to exchange real power and reactive power with the AC networks through certain impedances. They can be adjusted to exchange reactive power and active power with the AC power system networks by changing the phases of the triggering signals of their solid-state switching devices. These kinds of compensators are usually supported by energy storage devices in order to stabilize their DC voltages. A statcom is an application based on the power conversion principles. It is either a voltage source inverter shunted by a DC capacitor [23] or a current source inverter shunted by a DC reactor [24]. Both categories can exchange capacitive or inductive reactive power with the AC network through, to some extent, small series impedances (usually small reactors). Statcoms can be used to control both real power and reactive power. They are built with different topologies in order to satisfy the requirements of being employed in applications requiring higher voltage and current ratings in addition to treating the current harmonics associated with their compensating currents [25]-[27]. Static VAR compensators built on the basis of power conversion are usually denoted by advanced static VAR compensators.

In this paper, a modified harmonic-free configuration constructed with a TCR and two passive circuits is presented as a reliable replacement for a fixed capacitor thyristor controlled reactor shunted by high power harmonic filters. This configuration represents a continuously and linearly controlled capacitive static VAR compensator. The capacitive current of this compensator is controlled by a new adaptive closed loop current controller, which forces the compensator to respond linearly to the reactive current demand.

 

II. SCHEMATIC DESIGN OF THE PROPOSED AUTOMATIC POWER FACTOR CORRECTION SYSTEM

The layout of the proposed system is shown in Fig. 1. The compensator power circuit is built with a traditional TCR and two filtering circuits. LX and RX are the self-inductance and resistance of the TCR reactor. The first filtering circuit is represented by the series circuit CF1LF1RF1, which is tuned at the AC source fundamental angular frequency ω. RF1 is the self-resistance of LF1. The second circuit is formed with CF2LF2RF2 and it is tuned at 3ω. RF2 is the self-resistance of LF2.

The actual waveform of the TCR current iX at a certain firing angle α is shown in Fig. 2. In this figure, vX represents the AC voltage exerted across the TCR terminals, and α is the angle measured from the positive peak point of vX to its next negative slope zero-crossing point. This angle varies in the range of 0≤α≤π/2. The absolute fundamental and nth harmonic current components of the TCR current are given by [1]:

Fig. 1.Layout of the proposed automatic power factor correction system.

Fig. 2.The TCR current waveform.

Where, Vm is the amplitude of vX, and n is a positive odd integer greater than unity.

Since the first and second filtering circuits are tuned at ω and 3ω, respectively, the following can be written:

Where, XF1 and XF2 are the characteristic impedances of the first and second filtering impedances, respectively, at the corresponding resonance frequencies of ω and 3ω. At the fundamental angular frequency ω of the AC source, these impedances can be expressed as follows:

Where, ZF1(ω) and ZF2(ω) are the impedances of the first and second filtering circuits at the AC source fundamental. In Equation (6), the self-resistance RF2 is neglected because it is very small when compared to the imaginary part of ZF2(ω).

The second filtering circuit and the TCR circuit are designed so that the parallel combination draws zero reactive current during zero reactive current demand. This implies that:

Since RX is negligible when compared to ωLX, Equation (7) can be closely approximated to:

At the nth harmonic frequency, the impedances of the first and second filtering circuits can be expressed as follows:

To make this compensator suppress all of the current harmonics with orders higher than the 9th harmonic, the nth harmonic current component flowing through the AC source side should be at least one tenth the component released by the TCR. This implies that:

Substituting Equation (9) and (10) into (11) gives the following closely approximated equation:

Equations (8) and (12) are the basic design equations of the proposed harmonic-suppressed TCR. Using these equations, the passive elements of the harmonic-suppressed TCR can be expressed in terms of its reactor inductance as follows:

 

III. SCHEMATIC DESIGN OF THE NEW ADAPTIVE CONTROLLER

The controlling scheme of the proposed compensator is shown in Fig. 3. The inputs to this controller are the instantaneous AC source voltage vAC, a voltage signal proportional to the instantaneous compensator current KIiC, and a voltage signal proportional to the instantaneous load current KIiL. Where, KI is a constant depending on the current transformer turn ratio and the parameters of its circuitry. The voltage vAC is exerted to a step-down voltage transformer in order to produce the analogue voltage KVvAC. Where, the KV constant stands for the primary to secondary turn ratio of the voltage transformer. The analogue voltage KVvAC is zero-crossed and then delayed by 5ms to produce the voltage waveforms vS1 and vS2. A third voltage waveform vS3 is produced through the XOR operation of vS1 and vS2. The waveform vS3 is exerted on a saw-tooth generator to produce the signal vST which has an amplitude of 4V and runs at a frequency of 2f. Where, f is the frequency of the AC source (f=ω/2π).

Fig. 3.The new adaptive controlling scheme.

Fig. 4.The voltage waveforms of the new adaptive controller of the proposed compensator.

The voltage waveform vST is subtracted from a DC voltage of 4V to produce the reference voltage waveform vREF which is used together with the output of the current controller to determine the TCR firing angle α. The inputs of the current controller are the analogue voltages KIiC and KIiL. In this controller, a closed loop strategy is adopted so that its output vCX settles when the reactive current components of the inductive load and the compensator current cancel each other out. The analogue signal controlling the firing angle of the TCR is obtained by comparing the output of the current controller vCX with the reference voltage waveform vREF. The latter waveform varies in the range of 0 to +4V. The waveforms of the new adaptive controlling scheme are shown in Fig. 4. By examining this figure, it can be seen that the TCR firing angle can be related to the voltage vCX as follows:

The instantaneous fundamental current of the TCR (iX1) can expressed as follows:

The instantaneous fundamental current of the third harmonic filter (iY1) can expressed as follows:

Since this compensator is designed so that negligible harmonic current components are permitted to flow into the AC source side, its instantaneous current (iC) contains only the fundamental current components of the third harmonic filter and the TCR. Consequently, iC can determined as follows:

Substituting Equations (18), (19), and (8) into (20) gives:

Substituting Equation (17) into (21) gives:

Equation (22) indicates that the compensator current is purely capacitive and can be directly controlled by the voltage vCX. If vCX is zero, then the compensator will generate its maximum reactive current. On the other hand, its current will be zero if vCX is +4V. The instantaneous current of the inductive load can be defined by:

Where, ILm and φ are the amplitude and power factor angle of the inductive load, respectively. The automatic power factor correction system is designed so that the compensator current cancels the reactive current component of the inductive load. Consequently, the following can be written:

Equation (24) is directly governed by vCX. A closed loop control strategy is adopted in this paper to make Equation (24) settle to zero within a short time.

The new adaptive current controller of the proposed compensator is shown in Fig. 5. The actual current of the harmonic-suppressed TCR iC is detected by a current transformer and converted to the analogue voltage KIiC. Where, KI is a constant depending on the current transformer turn ratio and the parameters of its circuitry. The load current is detected by a similar current transformer and converted to the analogue voltage KIiL. The analogue voltage signal KIiC is sampled and held at ωt=2kπ and ωt=(1+k)π in order to detect KIICm and -KIICm. Where, k=0, 1, 2, 3, ... and ICm is the actual amplitude of the compensator current iC. The two sampled signals are treated through a difference amplifier for obtaining the mean of KIICm. The latter signal is proportional to the compensator capacitive reactive current. The analogue voltage signal KIiL is sampled and held at ωt=2kπ for obtaining the analogue voltage signal – KIILmsin(φ), which is proportional to the inductive load reactive current component.

The voltage across capacitor CX represents the controller output voltage vCX. This voltage directly controls the triggering circuits of the thyristors employed in the compensator design. If the error signal becomes zero, then the charging and discharging processes will cease and the capacitor will sustain its final voltage as long as the error signal is not effective. Therefore, the steady state operation is reached when the error signal continues having zero values.

The TCR controlling signal vX is produced by comparing vCx with vREF. The voltage signal vX is logically multiplied by vS2 and its complement to obtain the TCR thyristor triggering signals vX1 and vX2, as shown in Fig. 4. The triggering signals vX1 and vX2 can be defined by:

A validation system for the proposed automatic power factor correction system is designed on Pspice, as shown in Fig. 6. The system is designed so that it has a reactive current rating of 110A (peak) in a 220V 50Hz power system network.

Fig. 5.The new adaptive current controller of proposed compensator.

The reference waveform generator is shown in Fig. 7. This generator produces the voltage signal vREF illustrated in Fig. 4.

A circuit diagram of the new adaptive current controller is shown in Fig. 8. This figure represents a circuit diagram that stands for the schematic design shown in Fig. 5.

Fig. 6.The PSpice validation system of proposed automatic power factor correction system.

Fig. 7.The reference waveform generator.

Fig. 8.The circuit diagram of the adaptive current controller.

According to the specified reactive current rating, the inductance of the TCR reactor LX is calculated to be (311V/110A)=9mH. 311V stands for the rms value of 220V. According to this value of LX and using the design Equations (13) to (16), the following design values are obtained: LF1=10.125mH, CF1=1000μF, LF2=1.125mH, and CF2=1000μF. The self-resistances of the reactors are chosen so that the resistance to inductance ratio is 10Ω/H in order to reduce their losses and to make them behave, to some extent, as pure reactances.

Two identical current transformers are used in this design. The primary to secondary ratio of each transformer is 1:100. The thyristors used are T627121574DNs. These thyristors have continuous voltage and current ratings of 2200V and 300A, respectively.

The npn transistors used in the new adaptive controller design are Q2N2222As. These transistors have continuous voltage and current ratings of 75V and 800mA, respectively. Their forward current gain β is 256.

 

IV. RESULTS AND DISCUSSION

The automatic power factor correction system depicted in Fig. 6 was tested in PSpice at rated load currents with different lagging power factors. The PSpice tests involve the transient and steady state performance of the compensation system. The transient performance started from the first plug in instant of the compensator to the AC power system network and ended once the compensator current was completely settled. The steady state performance started from the instant at which the compensator current was completely settled. Therefore, it is appropriate to reveal the transient and steady state performance results together to show the instants at which the steady state performance started. Then the steady state performance results are revealed to demonstrate the potency of the compensator in power factor correction and harmonic cancellation.

A. Transient and Steady State Performance

The automatic power factor correction system in this paper is proposed to correct to unity the power factor of a single-phase inductive load in a 220V 50Hz power system network. During the PSpice test, a load of a 2Ω impedance was chosen. According to the design capability of the compensation system, a lagging power factor of 0.707 of the above load can be corrected to unity. If the power factor is lower than 0.707, a partial power factor improvement can be expected. Firstly, the compensation system was tested at the rated resistive load (2Ω). Fig. 9 shows the performance results of this test. Fig. 9a shows that the adaptive current controller approached steady performance at t=200ms. This is deduced from the error signal KIΔI which attained a zero value at this time and sustained it. Fig. 9a shows that the current drawn from the AC source iAC approached zero at t=160ms. Consequently, it can be said that the steady state performance in this figure started at t=200ms. The voltage vCX attained a value of +5V, which corresponded to the zero firing angle of the TCR. Therefore, the TCR was running at its maximum inductive current rating, which cancelled the capacitive current generated by the third harmonic filter.

Fig. 9.Transient and steady state performance during rated resistive load: (a) current controller, (b) the whole compensator.

Fig. 10, Fig. 11, and Fig. 12 show the transient and steady state performance results of the automatic power factor correction system during the compensation of inductive rated loads at 0.9, 0.8, and 0.707 lagging power factors, respectively. In Fig. 10(a), the error signal of the current controller settled to the zero value at t=200ms. At this time, the voltage vX is about 2.5V. This value of vX corresponds to a firing angle of 0.98 radians (560). According to Equation (25), the zero error signal means that the compensator capacitive current and the load reactive current components are equal in magnitude and out of phase by 1800. This situation corresponds to unity power factor correction.

In Fig. 11(a), the current error signal settled to the zero value before t=200ms while vX settled to the steady state value at the same time. In this figure, vX is slightly less than 2V. This value of vX corresponds to a firing angle of slightly less than π/4.

In Fig. 12(a), the current error signal settled to the zero value before t=200ms while vX settled to the zero value at the same time. This value of vX corresponds to a firing angle of π/2, which in turn corresponds to the zero TCR current. Fig. 12(b) shows the zero reactive current absorbed by the TCR.

Fig. 10.Transient and steady state performance results during rated load at 0.9 lagging power factor: (a) current controller, (b) the whole compensator.

Fig. 11.Transient and steady state performance results during rated load at 0.8 lagging power factor: (a) current controller, (b) the whole compensator.

Fig. 12.Transient and steady state performance results during rated load at 0.707 lagging power factor: (a) current controller, (b) the whole compensator.

B. steady State Performance

The steady state performance started at about t=200ms after the first plug in of the compensator to the power system network. However, for better evaluation of the harmonic contents, the steady state performance tests were carried out beyond t=300ms. Fig. 13 shows the steady state performance of the adaptive current controller during a resistive load.

Fig. 13.Steady state performance results of the adaptive current controller during rated resistive load.

Fig. 14(a), Fig. 14(b), and Fig. 14(c) show the steady state performance results of the adaptive current controller corresponding to the loading conditions specified in Fig. 10(a), Fig. 11(a), and Fig. 12(a), respectively. Fig. 13 and Fig. 14 show that the voltage signals KIICm and KIILmsinφ are equal in magnitude and having different signs. Therefore, the error signal ΔI is zero. In addition, these figures show a constant vX during steady state performance. This guaranties a fixed firing angle.

Fig. 14.Steady state performance of the current controller during rated loads at lagging power factor of: (a) 0.9, (b) 0.8, (c) 0.707.

Fig. 15, Fig. 16, Fig. 17, and Fig. 18 show the steady state performance of the compensation process corresponding to the loading conditions specified in Fig. 9(b), Fig. 10(b), Fig. 11(b), and Fig. 12(b), respectively. Fig. 15 corresponds to the rated resistive load. Since the reactive current component is zero, the compensator current should also be zero according to Equation (25). The figure shows that the AC source iAC and the load current iL are coinciding with each other.

Fig. 16 corresponds to a rated inductive load at a 0.9 lagging power factor. The reactive current component of this current is 68A (peak value). Therefore, the compensator should generate a reactive current of 68A (peak value) in order to achieve a unity power factor correction to iAC. The unity power factor correction is obvious in this figure.

Fig. 17 and Fig. 18 correspond to rated inductive loads at 0.8 and 0.707 lagging power factors, respectively. The reactive current components of these currents are 93A and 110A (peak values), respectively. The compensator was able to compensate the above load reactive current components and the compensation processes resulted in a unity power factor correction to iAC as shown in these two figures.

In Fig. 15 to Fig. 18, no sign of current harmonics beyond the fundamental component are noticeable on the compensator current frequency spectrum F(iC), the AC source current frequency spectrum F(iAC), or the load current frequency spectrum F(iL). Consequently, this automatic power factor correction system is harmonic-free.

In Fig. 15, the instantaneous TCR current iX and the third harmonic filter current iY are pure sinusoidal, equal in magnitude, and out of phase by 1800. Therefore, they cancel each other out and result in almost zero compensating current iC. Consequently, the linearly and continuously controlled capacitive compensator used in this compensation system and represented by the harmonic-suppressed TCR is a pure reactive device having negligible no load operating losses.

Fig. 15.The compensator steady state performance during rated resistive load.

Fig. 16.The compensator steady state performance during rated inductive load at 0.9 lagging power factor.

Fig. 17.The compensator steady state performance during rated inductive load at 0.8 lagging power factor.

Fig. 18.The compensator steady state performance during rated inductive load at 0.707 lagging power factor.

The TCR current frequency spectrum F(iX) and the third harmonic filter current frequency spectrum F(iY) coincide with each other in Fig. 15 to Fig. 18. The fact that they coincide verifies that this compensation system is harmonic-free.

The above applied tests show that the new adaptive current controller approaches its steady state performance within a time of about 200ms. This time is very small when compared to those achieved by the phase shift current controller in [2], the microprocessor based power factor controller in [4], the hysteresis current controller depicted in [5], and the SVC current controller with a Fuzzy ranking system in [7]. For instance, the steady state performance time for the hysteresis current controller [5] is about one second. This is approximately five times the transient time of the new current controller adopted in this paper.

The frequency spectrums of the steady state current of the harmonic-suppressed TCR demonstrate its efficiency as a linear harmonic-free capacitive static VAR compensator. It reveals excellent harmonic cancellation when compared to traditional static VAR compensators such as the power factor compensator and harmonic suppresser in [2]. In addition, it exhibits competitive compensation and harmonic cancellation efficiencies when compared to the advanced static compensators depicted in [6], [11], [13], [22].

 

V. CONCLUSIONS

There are three types of control schemes used to govern the susceptances of static VAR compensators. The first scheme is dependent on direct computations of the VAR demands to specify the firing triggering signals of the switching devices of static VAR compensators. This type of control is referred to as open loop control. The second type depends on feedback control to govern the current of the static VAR compensator. However, this type of control requires undistorted compensating currents in order to settle accurately and rapidly to the steady state operation. The third controlling scheme mixes these two approaches of control. Traditionally, TCR control is usually realized by the first control scheme through look up tables, programmable controlling schemes, direct analogue computations, and analogue simulation of the TCR current fundamental. This is because the TCR current waveform is not sinusoidal. In this paper, an adaptive closed loop controlling strategy for a TCR is presented. This is done because all of the harmonic current components released by the TCR are not permitted to be injected into the AC source side. Consequently, the harmonic-suppressed TCR based capacitive static VAR compensator becomes a harmonic-free pure reactive device that can be controlled using closed loop strategies. The perfect unity power factor correction handled by the proposed automatic power factor correction system validates its design methodology and reveals it potency in energy saving for generation stations and the reduction of transmission losses.

참고문헌

  1. L. Gyugyi, "Power electronics in electric utilities: static Var compensators," in Proc. the IEEE, Vol. 76, No. 4, pp. 483-494, Apr. 1988. https://doi.org/10.1109/5.4433
  2. L. T. Moran, P. D. Ziogas, and G. Joos, "Analysis and design of a novel 3-$\phi$ solid-state power factor compensator and harmonic suppressor system," IEEE Trans. Ind. Appl., Vol. 25, No. 4, pp. 609-619, Jul./Aug. 1989. https://doi.org/10.1109/28.31237
  3. D. Raonic and D. Cyganski, "Power factor compensation at busses with slightly distorted voltage due to random harmonics," IEEE Trans. Power Del., Vol. 4, No. 1, pp. 502-507, Jan. 1989. https://doi.org/10.1109/61.19240
  4. H. M. Al-Bolok, M. E. Masoud, and M. M. Mahmoud, "A microprocessor-based adaptive power factor corrector for nonlinear loads," IEEE Trans. Ind. Electron., Vol. 37, No. 1, pp. 77-81, Feb. 1990. https://doi.org/10.1109/41.45846
  5. S. Hirve, K. Chatterjee, B. G. Fernandes, M. Imayavaramban, and S. Drawi, "PLL-less active power filter based on one-cycle control for compensating unbalanced loads in three-phase four-wire system," IEEE Trans. Power Del., Vol. 22, No. 4, pp. 2457-2465, Oct. 2007. https://doi.org/10.1109/TPWRD.2007.893450
  6. B. Singh, P. Jayaprakash, T. R. Somayajulu, and D. P. Kothari, "Reduced rating VSC with a zig-zag transformer for current compensation in a three-phase four-wire distribution system," IEEE Trans. Power Del., Vol. 24, No. 1, pp. 249-259, Jan. 2009. https://doi.org/10.1109/TPWRD.2008.2005398
  7. D. B. Kulkarni and G. R. Udupi, "ANN-based SVC switching at distribution level for minimal-injected harmonics," IEEE Trans. Power Del., Vol. 25, No. 3, pp. 1978-1985, Jul. 2010.
  8. Y. Xu, L. M. Tolbert, J. D. Kuek, and D. T. Rizy, "Voltage and current unbalance compensation using a static VAR compensator," IET Power Electron., Vol. 3, No. 6, pp. 977-988, Oct. 2010. https://doi.org/10.1049/iet-pel.2008.0094
  9. IEEE PES Harmonic Working Group, "Characteristics and modeling of harmonic sources-power electronic devices," IEEE Trans. Power Del., Vol. 16, No. 4, pp. 791-800, Oct. 2001. https://doi.org/10.1109/61.956771
  10. J. E. R. Alves,Jr., L. A. S. Pilotto, and E. H. Watanabe, "Thyristor-controlled reactors nonlinear and linear dynamic analytical models," IEEE Trans. Power Del., Vol. 23, No. 1, pp. 338-346, Jan. 2008. https://doi.org/10.1109/TPWRD.2007.911131
  11. A. Luo, Zhikang Shuai, Wenji Zhu, and Z. John Shen, "Combined system for harmonic suppression and reactive power compensation," IEEE Trans. Ind. Electron., Vol. 56, No. 2, pp. 418-428, Feb. 2009. https://doi.org/10.1109/TIE.2008.2008357
  12. B. T. Ooi, M. Kazerani, R. Marceau, Z. Wolanski, F. D. Galiana, D. McGillis, and G. Joos, "Mid-point siting of FACTS devices in transmission lines," IEEE Trans. Power Del., Vol. 12, No. 4, pp. 1717-1722, Oct. 1997. https://doi.org/10.1109/61.634196
  13. K. N. Strivastava and S.C Strivastava, "Elimination of dynamic bifurcation and chaos in power systems using FACTS devices," IEEE Trans. Circuits and Syst. I Fundam. Theory Appl., Vol. 45, No. 1, pp. 72-78, Jan. 1998. https://doi.org/10.1109/81.660759
  14. P. Pourbeik and M.J. Gibbard, "Simultaneous coordination of power system stabilizers and FACTS device stabilizers in a multimachine power system for enhancing dynamic performance," IEEE Trans. Power Syst., Vol. 13, No. 2, pp. 473-479, May 1998. https://doi.org/10.1109/59.667371
  15. W. L. Tan and Y. Wang, "Effects of FACTS controller line compensation on power system stability," IEEE Power Eng. Rev., pp. 55-56, Aug. 1998.
  16. M. H. Haque, "Evaluation of first swing stability of a large power system with various FACTS devices," IEEE Trans. Power Syst., Vol. 23, No. 3, pp. 1144-1151, Aug. 2008. https://doi.org/10.1109/TPWRS.2008.926095
  17. A. K. Chakravorti and A.E. Emanuel. "A current regulated switched capacitor static volt ampere reactive compensator," IEEE Trans. Ind. Appl., Vol. 30, No. 4, pp. 986-997, Jul./Aug. 1994. https://doi.org/10.1109/28.297916
  18. S. Nandi, P. Biswas, V. N. Nandakumar, and R. K. Hedge, "Two novel schemes suitable for static switching of three-phase delta-connected capacitor banks with minimum surge current," IEEE Trans. Ind. Appl., Vol. 33, No. 5, pp. 1348-1354, Sep./Oct. 1997. https://doi.org/10.1109/28.633816
  19. J. Dixon, L. Moran, J. Rodriguez, and R. Domke, "Reactive power compensation technologies: state-of-art review," in Proc. The IEEE, Vol. 93, No. 12, pp 2144-2164, Dec. 2005. https://doi.org/10.1109/JPROC.2005.859937
  20. R. Gupta, A. Ghosh, and A Joshi, "Switching characterization of cascaded multilevel-inverter-controlled systems," IEEE Trans. Ind. Electron., Vol. 55, No. 3, pp. 1047-1058, Mar. 2008. https://doi.org/10.1109/TIE.2007.896274
  21. J. Wen and K. M. Smedley, "Synthesis of multilevel converters based on single and or three-phase converter building blocks," IEEE Trans. Power Electron., Vol. 23, No. 3, pp. 1247-1256, May 2008. https://doi.org/10.1109/TPEL.2008.921175
  22. A. Hamadi, S. Rahmani, and K. Al, "A Hybrid passive filter configuration for VAR control and harmonic compensation," IEEE Trans. Ind. Electron., Vol. 57, No. 7, pp. 2419- 2434, Jul. 2010. https://doi.org/10.1109/TIE.2009.2035460
  23. Y. Sumi, Y. Hanunoto, T. Hasegawa, M. Yano, K. Ikeda, and T. Matsuura, "New Static VAR control using forced-commutated inverter," IEEE Trans. Power App. Syst., Vol. PAS-100, No. 9, pp. 4216-4224, Sep. 1981. https://doi.org/10.1109/TPAS.1981.316973
  24. Y. Ye, M. Kazerani, and V. H. Quintana, "Current-source converter based STATCOM: modeling and control," IEEE Trans. Power Del., Vol. 20, No. 2, pp. 795- 800, Apr. 2005. https://doi.org/10.1109/TPWRD.2004.837838
  25. J. A. Barrena, L. Marroyo, M. A. R. Vidal, and J. R. T. Apraiz, "Individual voltage balancing strategy for PWM cascaded H-bridge converter-based STATCOM," IEEE Trans. Ind. Electron., Vol. 55, No. 1, pp. 21-29, Jan. 2008.
  26. Q. Song and W. Liu, "Control of a cascade STATCOM with star configuration under unbalanced conditions," IEEE Trans. Power Electron., Vol. 24, No. 1, pp. 45-57, Jan. 2009. https://doi.org/10.1109/TPEL.2008.2009172
  27. H. P. Mohammadi and M.T. Bina, "A transformerless medium-voltage STATCOM topology based on extended modular multilevel converters," IEEE Trans. Power Electron., Vol. 26, No. 5, pp. 1534-1545, May 2011. https://doi.org/10.1109/TPEL.2010.2085088