데이터 센터의 외기냉수냉방 시스템에 대한 에너지 절감효과 분석

Analysis on the Energy Saving Effect of Free Cooling System in Data Center

  • 윤정인 (부경대학교 냉동공조공학과) ;
  • 손창효 (부경대학교 냉동공조공학과) ;
  • 허정호 (부경대학교 냉동공조공학과 대학원) ;
  • 김영민 ((주) 정인하이테크)
  • Yoon, Jung-In (Refrigeration and Air-conditioning Engineering, Pukyong University) ;
  • Son, Chang-Hyo (Refrigeration and Air-conditioning Engineering, Pukyong University) ;
  • Heo, Jeong-Ho (Graduate School of Refrigeration and Air-conditioning Engineering, Pukyong University) ;
  • Kim, Young-Min (JUNG IN HI-TECH CO., LTD.)
  • 투고 : 2014.03.28
  • 심사 : 2014.05.07
  • 발행 : 2014.06.30

초록

Recently, Free cooling system usage has increased at many buildings in intermediate and winter season. Free cooling system is used to reduce the energy consumption of refrigeration in that season. Free cooling system is refrigeration system using cooled water. In general, this system is applied with the building having refrigeration load at all time such as a data center. In this study, energy consumption of a data center taking free cooling system in Ulsan was evaluated by the software HYSYS. the main result is as in the following : free cooling system is effective from January to April and from November to December. In case of Ulsna in 2013, using free coolng system is able to spend refrigeration energy of about 15% less than existing system. According to this result, it is appropriated that free cooling system is used in building having refrigeration load at all time such as data center.

키워드

참고문헌

  1. S. H. Kim, J. Y. Yeon, Y. K. Choi and E. K. Lee, 2011, "A Study on Free Coolig System for the Energy Saving in the Data Center", Summer Annual Conference of Society of Air-conditioning and refrigerating engineers of Korea, pp. 810-814.
  2. S. H. Kim, J. Y. Yeon, Y. K. Choi and E. K. Lee, 2006, "A Study on the Energy Saving Effects of Free Coolig System", Journal of Archetural Institute of Korea, Vol. 22, No. 2, pp. 228-234.
  3. B. S. Kim, Y. G. Kim, Y. G. Kwon, J. E. Choi and M. K. Song, 2010, "Saving of Free Cooling System", Summer Annual Conference of Society of Air-conditioning and refrigerating engineers of Korea, pp. 394-397.
  4. J. I. Yoon, C. H. Son, Y. M. Kim, 2013, "Power Reduction Cooling System Using Outdoor Air", Journal of the Korean Society for Power System Engineering, Vol. 17, No. 4, pp. 12-16
  5. Aspentech Software HYSYS. 8.0v

피인용 문헌

  1. A Study on the Humidity Paper for Indicating Moisture Absorbed in R-22 vol.18, pp.5, 2014, https://doi.org/10.9726/kspse.2014.18.5.055
  2. A Study on Application of the Free Cooling System with Dry Cooler Using Economic Evaluation vol.19, pp.4, 2015, https://doi.org/10.9726/kspse.2015.19.4.050
  3. Development of a Prediction Model and an Adaptive Control Algorithm for the Data Center Thermal Environment vol.20, pp.6, 2014, https://doi.org/10.12813/kieae.2020.20.6.107