초록

Inflow or outflow from the water treatment plant and the sewage water has potential energy. If this potential energy can be converted into electrical energy by water turbine generator, it can help to save energy because of the high capacity utilization. So recently, micro hydro power plant is reviewed in the water treatment facility. If generation capacity is low, induction generator is primarily used. If output capacity is low, generated power is supplied to the inside load. Induction generator can cause voltage drop by the inrush current at a start-up and requires reactive power for magnetization. In this study, we analyzed the flow of power and voltage variation against inrush current that occurs when the induction generator starts under the terms that loads of linear and non-linear of the water purification plant are used. Analysis results are that the voltage drop is within an allowable range and the power factor is slightly reduced by the need of reactive power.

키워드

참고문헌

  1. Jong-Gyeum Kim et al., "Activation Strategy of Hydropower Development as New & Renewable energy", KIEE Summer Conference, pp. 1231-1232, 2010.7.
  2. 2013 New & Renewable Energy, MOKE & KEMCO.
  3. M. Godoy Simoes & Felix A. Farret, "Renewable Energy Systems-Design and Analysis with Induction Generators", CRC Press, 2004.
  4. Jong-Gyeum Kim, Young-Jeen Park, Il-Jung Kim, Young-Kuk Kim, "Characteristics Analysis of Induction Generator with a Change in Rotor Speed", KIEE, Vol.60, No.12, pp.2225-2229, 2011, Dec. https://doi.org/10.5370/KIEE.2011.60.12.2225
  5. D. S. Henderson, "Synchronous or induction Generators?-The choice for small scale generation", IEE Conf, Pub, pp.146-149, 1996.
  6. K. S. Pankaj, J. P. Nelson, "Application Guidelines for Induction Generators," in Proc. International Conference on Electrical Machines and Drives, Milwaukee, Wisconsin, May 18-21, 1997, Paper WC1/5.1 - WC1/5.3.
  7. Jong-Gyeum Kim, "Output Characterization Analysis of Induction Genarator using Test Data", KIEE, Vol.62, pp.1027-1032, No.7, 2013.
  8. Young-Kuk Kim, Jong-Gyeum Kim, "A Study on the Operation Characteristic of Induction Generator in the small Hydropower Plant", KIEE, Vol.62, pp.632-638, No.5, 2013. https://doi.org/10.5370/KIEE.2013.62.5.632
  9. Jong-Gyeum Kim, Young-Kuk Kim, "A comparison of the operating characteristics of the synchronous generator and induction generator applied to the small hydroelectric power plant", KIEE, Vol.63P, pp.55-60, No.2, 2014. https://doi.org/10.5370/KIEEP.2014.63.2.055
  10. KEPCO, "Power distribution system interconnection technical standards for distributed power". 2010. 7.
  11. Jong-Gyeum Kim et al. "Variance of Harmonics Element due to Linear & Non-linear Load Quantity", KIEE, Vol.51B, pp.441-448, No.8, 2002.
  12. IEEE Std 519-1992, "IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems".
  13. Shehab Abdulwadood Ali, "A Norton Model of a Distribution Network for Harmonic Evaluation", Energy Science and Technology, Vol.2, No.1, pp.11-17, 2011.
  14. H. W. Dommel, "Electromagnetic Transients Program, Reference Manual(EMTP Theory Book)", BPA, 1986.