DOI QR코드

DOI QR Code

태양광 발전설비의 침수 시 설비영향 및 전기적 안전성 평가

An Assessment on Effect of Facility and Electrical Safety During the Flooding of the Photovoltaic Power System

  • 박찬엄 (한국전기안전공사 전기안전연구원) ;
  • 정진수 (한국전기안전공사 전기안전연구원) ;
  • 한운기 (한국전기안전공사 전기안전연구원) ;
  • 임현성 (한국전기안전공사 전기안전연구원) ;
  • 송영상 (한국전기안전공사 전기안전연구원)
  • 투고 : 2014.08.07
  • 심사 : 2014.09.30
  • 발행 : 2014.12.31

초록

The photovoltaic power system is performing power generation by being installed in outdoors. Therefore it has the characteristics affected by environmental factors. In particular, if the solar power generation facility connected to the grid, the power can be generated continuously in a state of being secured operating voltage of the inverter and solar irradiation. In that case, if an abnormal situation such as flooding or heavy rains has occur, the possibility of electric shock or damage of facilities due to current leakage or a floating matters is present. In this paper, we performed electrical safety assessment about the connection part, junction box and cable of the solar module when the solar power system was flooded. we also assessed whether or not the leakage current is occurred in case of the cable was damaged. As a result, in case of the leakage current is large, we can be known that it is the risk of electric shock as well as cause of inverter damage.

키워드

참고문헌

  1. C.E. Park, W.K. Han J.S. Jung, "An Assessment on Harmonics Effect in Customer and the Distributed Power System during Grid Connection of Residential Fuel Cell System" KIEE Trans. Vol. 60, No. 6, Jun, 2011.
  2. C.E. Park, W.K. Han J.S. Jung, H.S. Lim, Y.s. Song, C.S. Kim, D,G. Lim, "An Assessment on Voltage and Power Quality in Load Facility during the Islanding of Residential Fuel Cell System. KIEE Trans. Vol. 62, No. 12, Dec, 2013.
  3. Y.K. Choi, J.S. Lee, "The Technique of Installing Floating Photovoltaic Systems", Journal of the Korea Academia-Industrial Cooperation Society, Vol. 14, No. 9, 2013.
  4. Y.K. Choi, "An Experimental Study on Ground Resistivity and Grounding Resistance of Water Environment", Journal of the Korea Academia-Industrial Cooperation Society, Vol. 15, No. 4, 2014.
  5. S.H. Kim, T.G. Lee, H.J. Joo, S.J. Yoon, "Structural Design and Installation of Tracking-type Floating PV Generation System", Composites Research, Vol. 27, No. 2, 2014.
  6. G.J. Kim, S.J. Lee, H.B. Kang, J.H. Song, "An Evaluation Technique of Building Integrated Photovoltaic System Performance Test" , The Proceedings of the KIEE(World of Electricity), Vol 63, No. 3, 2014.
  7. J.H. Yoon, "The State of the Art in BIPV Technology" J. KIEEME, Vol. 27, No. 1, Jan 2014.
  8. KS C IEC 61215 Crystalline silicon terrestrial photovoltaic modules - Design qualification and type approval, 2011.11.09, Korean Industrial Standards.
  9. KS C IEC 61730 Photovoltaic Module Safety Qualification, 2013.11.12, Korean Industrial Standards.
  10. KS C IEC 62257-7-1 Recommendations for small renewable energy and hybrid systems for rural electrification - Part 7-1: Generator - Photovoltaic arrays, 2012.12, Korean Industrial Standards.
  11. KS C IEC 60529 Degrees of Protection Provided by Enclosures(IP Code), 2011.11, Korean Industrial Standards.