DOI QR코드

DOI QR Code

소규모 LNG 저장시설의 안전거리 기준 연구

A Study on Safety Distance for Small Scale LNG Storage facility

  • 투고 : 2014.07.14
  • 심사 : 2014.12.08
  • 발행 : 2014.12.31

초록

In this study safety distance was investigated for small-scale LNG storage facilities in order to provide basic data for safety. The results are as follows; (1) For explosion pressure criteria, current criteria are reasonable, but water spray system should be recommended to LNG storage tank to ensure safety. (2) For criteria based on the results of the quantitative risk assessment, criteria applied to people are $5kW/m^2$ for radiation, LFL for dispersion, and 7kPa for explosion pressure. And criteria applied to facility are $37.5kW/m^2$ for radiation and 20 kPa for explosion pressure.

키워드

참고문헌

  1. CPR 18E, Guideline for quantitative risk assessment, 'Purple book', RVIM
  2. BS EN 473, Installation and equipment for liquefied natural gas-Design of onshore installations, (2007)
  3. BS EN 13645, Installations and equipment for liquefied natural gas-Design of onshore installations with a storage capacity between 5 t and 200 t, (2002)
  4. OGP, Risk Assessment Data Directory, Report No. 434-1, March (2010)
  5. IGC Doc 75/07/E, Determination of safety distances, Revision of Doc 75/01/rev, European Industrial Gases Association

피인용 문헌

  1. Case Study: Safety Assessment of Plant Layout between Ethylene Storage Tanks and Process Equipment According to Capacity and Weather Conditions vol.17, pp.8, 2014, https://doi.org/10.3390/ijerph17082849