DOI QR코드

DOI QR Code

저압용 소형 관형퓨즈의 용단 특성에 관한 실험적 연구

An Experimental Study on Melting Characteristics of Low-voltage Miniature Cartridge Fuse

  • 투고 : 2013.07.10
  • 심사 : 2013.09.04
  • 발행 : 2013.09.30

초록

This paper dealt with melting characteristics of low-voltage miniature cartridge fuse used for 220 V electronic equipment. The experimental sample is low-voltage miniature cartridge fuse with rating of 250 V(3A) and size of $5{\times}20$ mm. In order to evaluate melting and scattering characteristics of the fuse, we applied to 8/20 ${\mu}s$ surge current, overload current and external thermal stress such as flame of fire. From the experimental results, the fuse element was melted and scattered by applied surge current(above 0.79 kA) and overload current(above 4.5 A). It was also attached to the inner surface of the fuse tube. The fuse element was attached as a thin film on inner surface of fuse tube when large surge current was applied. It was confirmed, however, the fuse element was not changed by external thermal stress such as flame and hot-air.

키워드

참고문헌

  1. W. F. Cooper, Electrical Safety Engineering, 3th Edition 1993.
  2. A. A. Hattangadi, Electrical Fires and Failures, Mcgraw Hill 2000.
  3. Marcus O. Durham, Robert , Rosemary Durham, Jason Coffin, Electrical Failure Analysis for Fire and Incident Investigations, Createspace, 2011.
  4. C. H. Lee, S. K.. Kim and K. J. Ok, "A Study on the Causal Analysis of Electrical Fire by using Fuse", Journal of Korean Institute of Fire Science & Engineering, Vol. 22, No. 1, pp. 24-28, 2008.
  5. C. S. Choi, "Analysis of the Melting Characteristics of a Blade Type Fuse Used for Vehicles due to Overload", Journal of Korean Institute of Fire Science & Engineering, Vol. 24, No. 2, pp. 38-43, 2010.
  6. Y. H. Kim, "A Study on the Melting Characteristics of Fuse Element by Repeating Overcurrent", Journal of the Korean Institute of Illuminating and Electrical Installation Engineering, Vol. 24, No. 2, pp. 120-126, 2010. https://doi.org/10.5207/JIEIE.2010.24.2.120
  7. Korean Industrial Standards, KS C0503, Glossary of terms of fuses, 2002.
  8. COOPER Bussmann Data sheet 2019, 5${\times}$20 mm fuses, 2010.
  9. International Electrotechnical Commission, IEC 61000-4-5, Surge Immunity Test, pp. 60-77, 2002.