Abstract
In transmission system, reclosing scheme is very useful method to improve continuity of power supply and reliability of system. Especially, high speed reclosing which is used generally in transmission systems has a benefit improving transient stability. However, the reclosing can jeopardize the stability under the condition having high difference of voltage phase angle between both ends. Thus, this paper proposes optimal sequential reclosing scheme to improve transient stability due to reclosing operation. The optimal sequential reclosing is that each phase is closed sequentially considering transient energy. In this paper, 345kV and 154kV transmission system is modeled using EMTP (ElectroMagnetic Transient Program) to verify the performance and effectiveness of optimal sequential reclosing on transient stability. Also, Integral Square Error(ISE) method is used to assess the transient stability.