• 제목/요약/키워드: Sequential reclosing

검색결과 5건 처리시간 0.021초

송전계통 과도 안정도 향상을 위한 최적 순차 재폐로에 관한 연구 (A Study on Optimal Sequential Reclosing to Improve Transient Stability in Transmission System)

  • 권기현;오윤식;박지경;조규정;손승현;김철환
    • 전기학회논문지
    • /
    • 제62권10호
    • /
    • pp.1354-1360
    • /
    • 2013
  • In transmission system, reclosing scheme is very useful method to improve continuity of power supply and reliability of system. Especially, high speed reclosing which is used generally in transmission systems has a benefit improving transient stability. However, the reclosing can jeopardize the stability under the condition having high difference of voltage phase angle between both ends. Thus, this paper proposes optimal sequential reclosing scheme to improve transient stability due to reclosing operation. The optimal sequential reclosing is that each phase is closed sequentially considering transient energy. In this paper, 345kV and 154kV transmission system is modeled using EMTP (ElectroMagnetic Transient Program) to verify the performance and effectiveness of optimal sequential reclosing on transient stability. Also, Integral Square Error(ISE) method is used to assess the transient stability.

EMTP-MODELS를 이용한 Multi-Agent System 기반의 자동 재폐로 계전 알고리즘 구현 (Implementation of Auto-reclosing Relay Algorithm based on Multi-Agent System using EMTP-MODELS)

  • 이병현;여상민;이유진;김철환;성노규
    • 전기학회논문지
    • /
    • 제57권1호
    • /
    • pp.8-13
    • /
    • 2008
  • This paper presents auto-reclosing algorithms with reference to power system stability based on MAS(Multi-Agent System). And this paper shows auto-reclosing algorithms considering power system stability. It includes the variable dead time, optimal reclosing, sequential reclosing, emergency extended equal-area criterion(EEEAC) algorithm, and modified EEEAC algorithm. This paper divides Auto-reclosing algorithms into respectively agents according to their tasks. A separated agent is merely a software entity that is situated in some environment and is able to autonomously react to changes in the environment. And all the simulations in this parer were tested by EMTP MODELS.

Developing a New Risk Assessment Methodology for Distribution System Operators Regulated by Quality Regulation Considering Reclosing Time

  • Saboorideilami, S.;Abdi, Hamdi
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권4호
    • /
    • pp.1154-1162
    • /
    • 2014
  • In the restructured electricity market, Performance-Based Regulation (PBR) regime has been introduced to the distribution network. To ensure the network stability, this regime is used along with quality regulations. Quality regulation impose new financial risks on distribution system operators (DSOs). The poor quality of the network will result in reduced revenues for DSOs. The mentioned financial risks depend on the quality indices of the system. Based on annual variation of these indices, the cost of quality regulation will also vary. In this paper with regard to reclosing fault in distribution network, we develop a risk-based method to assess the financial risks caused by quality regulation for DSOs. Furthermore, in order to take the stochastic behavior of the distribution network and quality indices variations into account, time-sequential Monte Carlo simulation method is used. Using the proposed risk method, the effect of taking reclosing time into account will be examined on system quality indicators and the cost of quality regulation in Swedish rural reliability test system (SRRTS). The results show that taking reclosing fault into consideration, affects the system quality indicators, particularly annual average interruption frequency index of the system (SAIFI). Moreover taking reclosing fault into consideration also affects the quality regulations cost. Therefore, considering reclosing time provides a more realistic viewpoint about the financial risks arising from quality regulation for DSOs.

송전선로의 과도 안정도를 고려한 적응 자동재폐로 기법 (An Adaptive Autoreclosure Scheme with Reference to Transient Stability for Transmission Lines)

  • 허정용;김철환
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권12호
    • /
    • pp.698-704
    • /
    • 2003
  • Autoreclosure provides a mean of improving power transmitting ability and system stability. The conventional reclosure adopts the fixed dead time interval strategy, that is, the reclosure is activated after a time delay to restore the system to normal as quickly as possible without regard to the system conditions, however, these simple techniques cannot give the optimal operating performance. For this reason, various adaptive reclosure algorithms have been proposed recently, This paper presents an adaptive autoreclosure algorithm including the variable dead time, optimal reclosure, sequential reclosure and emergency extended equal-area criterion (EEAC) algorithm in order to improve the system stability. The reclosure algorithm performs out the operations that are attuned to the power system conditions. The proposed adaptive reclosure algorithm is verified and tested by using EMTP MODELS, and the simulation results show that the system oscillations are reduced and the transient stability is enhanced by employing the proposed adaptive reclosure algorithm.

리클로징 시간을 고려한 배전계통 순간전압강하의 3상 유도전동기에 미치는 영향 검토 (Investigation of the impact of Voltage Sags on 3-Phase Induction Motors Considering Reclosing Interval in Distribution System)

  • 강봉석;김재철;문종필;윤상윤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.45-47
    • /
    • 2004
  • This paper describes the various characteristics of voltage sags which can affect the functions of three-phase induction motors that are mostly used in the power distribution systems. These assorted characteristics include motor speed losses, voltage recovery, motor reacceleration, and transient characteristics. An experimental study on the induction motor behaviors was also carried out to confirm these impacts. In addition, sequential voltage sags with short durations were considered and investigated. The results show that the occurrence of the second voltage sag after the first one may affects the induction motor adversely.

  • PDF