DOI QR코드

DOI QR Code

Research on Assessment Method of Deterioration Condition for Power Transformer Using Sweep Frequency Response Analyzer

주파수응답분석기를 이용한 전력용 변압기 열화상태 평가방법 연구

  • Received : 2013.03.29
  • Accepted : 2013.06.12
  • Published : 2013.08.31

Abstract

This paper describes the assessment method of deterioration condition for a power transformer using SFRA. Frequency Response Analysis(FRA) is a method to evaluate the mechanical and geometrical integrity of the core and windings within a power transformer by measuring the electrical transfer functions over a wide frequency range. SFRA is sweep frequency response analyzer for power transformer winding diagnosis. The FRA is a comparative method, that evaluates the transformer condition by comparing the obtained set of FRA results to reference results on the same, or a similar, unit. FRA techniques were widely used and much more sensitive than the traditional and internationally accepted method of impedance measurements, but that work was required on standardization and interpretation. In order to analyze the deterioration condition for power transformer, overvoltage test and mechanical distortion test were carried out. The deterioration condition for power transformer was evaluated by SFRA. It is intended to present the elemental technology of assessment method for power transformer using SFRA.

Keywords

References

  1. Hyoung-Jun Gil, Dong-Ook Kim, Dong-Woo Kim, Ki-Yeon Lee, "Comparison of Assessment Method for Power Transformer Using SFRA", Summer Conference of The Korean Institute of Electrical Engineers, pp.1597-1598, 2012.
  2. Hyoung-Jun Gil, Dong-Woo Kim, "Research on Condition Diagnosis Method for Power Transformer Using SFRA", Autumn Conference of The Korean Society of Safety, pp.11, 2012.
  3. CIGRE, "Guide for Transformer Maintenance", Working Group A2.34, pp.51-56, 2011.
  4. Patrick Picher et al., "Mechanical Condition Assessment of Transformer Windings Using Frequency Rersponse Analysis(FRA)", ELECTRA, pp.30-34, 2006.
  5. Phil-Hoon Cho, "Case Study on SFRA Measurement of Power Transformer", Power Equipments Condition Monitoring and Diagnosis, pp.1-39, 2012.
  6. Yun-Haeng Cho, "A Study of the Power Transformer Dia gnostic Using Frequency Response Analysis", Master's Thesis of Hanyang University, pp.1-47, 2010.
  7. Megger, "Sweep Frequency Response Analyzer", pp.10-40, 2010.