Study on the Assessment of the Criteria on a Door Closer for the Optimum Design of the Access Door of a Smoke Control Zone

제연구역 출입문의 최적 설계를 위한 도어클로저의 기준 산정에 관한 연구

  • Lee, Jae-Ou (Department of Fire Safety Engineering, Jeonju University) ;
  • Choi, Chung-Seog (Department of Fire Safety Engineering, Jeonju University)
  • 이재오 (전주대학교 소방안전공학과) ;
  • 최충석 (전주대학교 소방안전공학과)
  • Received : 2013.04.10
  • Accepted : 2013.06.14
  • Published : 2013.06.30

Abstract

The purpose of this study is to assess the criteria on a floor hinge and door closer for the optimum design of the access door of a smoke control room. The door opening force due to differential pressure is 60.75 N, 40.5 N, 32.91 N and 12.66 N when the differential pressure is 60 Pa, 40 Pa, 32.5 Pa and 12.5 Pa, respectively. The door opening force of the floor hinge and door closer to which the criteria of KS F 2806 are applied is 27.5 N, 40 N, 75 N, 100 N and 125 N for the Nos. 1, 2, 3, 4 and 5 class floor hinges and door closers, respectively. This study compared the differential pressure and opening force limits of floor hinges and door closers with the values specified in NFSC 501A and found that they exceeded the criteria specified in NFSC 501A. Therefore, it is necessary to reflect the differential pressure and smoke control wind speeds as well as the opening forces specified in NFSC 501A on the design of floor hinges and door closers. The installation conditions of floor hinges and door closers of access doors differ depending on the type and name of a smoke control damper. This study found that Nos. 1, 2 and 3 floor hinges and door closers could be installed for access doors with low differential pressure and that Nos. 1 and 2 floor hinges and door closers could be installed for access doors with normal differential pressure.

본 연구의 목적은 제연구역 출입문의 최적 설계를 위한 플로어힌지(floor-hinge) 및 도어클로저(door closer)의 기준을 제시하는데 있다. 차압에 대한 개방력은 60 Pa일 때 60.75 N, 40 Pa일 때 40.5 N, 32.5 Pa일 때 32.91 N, 12.5 Pa일 때 12.66 N 등이다. KS F 2806의 기준을 적용한 플로어힌지 및 도어클로저의 개방력은 No.1은 27.5 N, No. 2는 40 N, No. 3는 75 N, No. 4는 100 N, No. 5는 125 N 등이다. 차압과 플로어힌지 및 도어클로저의 개방력을 NFSC 501A의 개방력 제한값과 비교한 결과 기준을 초과하는 것으로 확인되었다. 따라서 NFSC 501A 차압과 방연 풍속을 설계에 반영하는 것뿐만 아니라 개방력도 설계에 반영할 필요가 있다. 제연댐퍼의 종류에 따라 출입문의 플로어힌지 및 도어클로저의 설치 조건은 호칭에 따라 다르다. 저차압용의 경우는 No. 1, No. 2, No. 3의 설치가 가능하며, 일반 차압용의 경우에는 No. 1, No. 2의 설치가 가능하였다.

Keywords

References

  1. H. J. Shin, J. H Choi and W. H. Hong, "Guidelines on Performance based Egress Design Criteria Considering the Risk Factors of a High-rise Building", Journal of Architectural Institute of Korea, Vol. 25, No. 7, pp. 139-148 (2009).
  2. J. O. Lee and C. S. Choi, "Study on the Analysis of Differential Pressure of the Access Door for a Smoke Control Zone and the Effectiveness of the Measurement Criteria of its Opening Force", Journal of Korean Institute of Fire Science & Engineering, Vol. 4, pp. 24-30 (2012). https://doi.org/10.7731/KIFSE.2012.26.4.024
  3. S. H. Ro, S. W. Yoon and D. H. Rie, "Study for Using VR Techniques Performance Evaluation of the Elevator Evacuation", Journal of Korean Institute of Fire Science & Engineering, Vol. 1, pp. 13-18 (2011).
  4. S. M. Park, B. K. An and M. K. Kim, "Study for Pressurized Smoke Control System", Proceedings of 2009 Spring Annual Korean Institute of Fire Science & Engineering, pp. 118-124 (2009).
  5. SFPE, "SFPE Handbook of Fire Protection Engineerng", Third Edition, Section 4, Chapter 12 "Smoke Control", Chapter 13, "Smoke Management in Covered Malls and Atria, pp. 274-310 (2002).
  6. Dougal Drysdale, "An Introduction to Fire Dynamics", Second Edition, Chapter 11, The Production and Movement of Smoke, pp. 386-401 (2002).
  7. NEMA, "National Fire Safety Code, NFSC 501A of Stair Cases of Specific Fire Escape Stairs and Smoke Control Systems of Ancillary Rooms", Administrator at National Emergency Management Agency (2012).
  8. NFPA 92A , Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences (2005).
  9. BS EN 12101-6, Smoke and heat control systems. Specification for pressure differential systems (2005).
  10. Korean Industrial Standard, "KS F 2806 Test Methods or Checking Floor-hinges and Door-closers Method", Korean Standards Association (2005).
  11. Korean Industrial Standard, "KS F 4505 Door Closer", Korean Standards Association (2005).