Protection Coordination Associated with Connection Location of Residual Current Devices and Surge Protective Devices

RCD와 SPD의 접속 위치에 따른 보호협조

  • Received : 2013.01.08
  • Accepted : 2013.02.06
  • Published : 2013.03.31

Abstract

In this paper, in order to analyze lightning impulse response characteristics in combined installations of SPDs and RCDs, surge protection coordination between SPDs and RCDs are experimentally investigated by using the combination wave generator. Six different types of single-phase residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs) being present on the domestic market are tested according to KS C IEC 61009-1 standard. As a result, when a class I SPD is located on the source side of an RCBO, all kinds of specimens are able to provide the proper coordination between the SPD and RCBOs without nuisance tripping, unintended operation or damage due to test impulse currents. However, in the case that the class II SPD is located on the load side of RCBOs, a lot of L-N mode injected currents is split into the RCBO, and a few RCBOs are damaged. Coordination between SPDs and RCDs is not valid and a role of SPDs is of no use. When combining SPDs with RCDs, it is necessary to select SPDs and RCDs in consideration of the protection voltage level of metal oxide varistor embedded in RCDs.

Keywords

References

  1. KS C IEC 62305-4; Protection against lightning - Part 4 : Electrical and electronic systems within structures, pp. 83-84, 2007.
  2. Korea Electric Association ; Korea Electro-technical Commission Guidance - Technical Guide for selection and application of surge protective devices in low-voltage power systems, pp.10-12, 81, 2011.
  3. KS C IEC 61643-1; Surge protective devices connected to low-voltage power distribution systems - Part 1: Requirements and tests, pp. 22-24, 2010.
  4. IEEE C62.41, IEEE Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits, pp.47-57, 1991.
  5. KS C IEC 60364-5-53; 2007, Electrical installations of buildings - Part 5-53: Selection and erection of electrical equipment - Isolation, switching and control, pp.4-11, 2007.
  6. KS C IEC 61009-1; 2009, Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses(RCBOs) - Part 1 : Genral rules, pp.19-24, 73-75, 2009.
  7. KS C IEC 60947-2:2009, Low-voltage switchgear and controlgear - Part 2 : Circuit-breakers, pp. 79-92, 2009.
  8. KS C IEC 61643-12; Low-voltage surge protective devices - Part 12 : Surge protective devices connected to low-voltage power distribution systems - Selection and Application principles, pp. 27-38, 76-81,104-111, 2007.
  9. B. H. Lee and S. C. Lee, Protection of Information and Communication Facilities against Lightning, The Publishing Department of Inha University, pp.26-29, 2004.