Abstract

The temperatures with the ground depth, the positions of circulation water in ground heat exchanger were measured and thermal diffusion characteristics with the distances of the direction normal to the borehole was analysed. The deeper the depth of ground, the less the influences of outdoor temperature, but below 10m of ground, there was no influences of ground temperature. When the depth of trench pipe was below the depth of 2m, there was no influence. In the ground of 10m when the distances between the pipe and the other places were above 0.5m, the variations of temperature were less than $1.6^{\circ}C$ and above 2.5m they were less than $0.1^{\circ}C$. When the distances of bore hole were above 5m, there were no. influences of the nearest ground heat exchanger.

Keywords

References

  1. Woo.W," A Performance Prediction of a Vertical-type Geothermal Heat Exchanger by CFD Analysis", Journal of the Korean Solar Energy Society Vol.27, No3, pp. 117-125, 2007
  2. Koo, K. M., Jeong, Y. M., Hoang, Y. J., Lee, J. K., Jang, S. Y., Kim, I. K., Jin, S. W., Lee, D. H., Heating Performance of a Ground Source Heat Pump System through Actual Operation, Proceedings of the SAREK, Summer Annual Conference. pp. 0788-0793, 2008.
  3. Choi, J. H., Lim, H. J., Kong, H. J., Sohn, B. H., Effect of Some Parameters on Ground Effective Thermal Conductivity, Proceedings of the SAREK, Winter Annual Conference. pp 033-038, 2008.
  4. Jeong,Y. M., Koo, K. M., Hwang, Y. J., Jang, S. Y., Lee,Y. H., Lee, D. H., Lee, J. K., Measurement of Ground Thermal Conductivity and Characteristics of Thermal Diffusion by the Ground Heat Exchanger, Korean Journal of Air- Conditioning and Refrigeration Engineering, Vol.20, No.11, pp.739-745, 2008.
  5. Choi, J. M., Lim, H. J., Kang, S. H., Choi, J. H., Moon, J. Y., Kwon,Y. S., Kwon, H. J., Kim, R. H., Verificationexperiment of aground sourcemulti-heatpump at heatingseason, Proceedings of the SAREK Summer Annual Conference. pp.052-057, 2009.
  6. Choi, J..M.,, Lim, Kang, H.. S., Daily Heating Performance of a Ground Source Multi-heat Pumpat Heating Mode, Korean Journal of AirConditioning and Refrigeration Engineering, Vol.21, No.9, pp.527-535, 2009
  7. Choi, J. M., Kang, S. H., Choi, J. H., Lim, H. J., Moon, J. Y., Kwon, Y. S., Kwon, H.J., Kim, R. H., Verification Experiment of a Ground Source Multi-heat Pumpat Cooling Mode, Korean Journal of air-Conditioning and Refrigeration Engineering, Vol.21, No.5, pp.297-304, 2009.
  8. Lim, H. J., Kong, H. J., Kang, S. J., Choi, J. H.,The effects of the installation conditions of ground loop heatexchanger to the thermal conductivity and borehole resistance, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol.23, No.2, pp.95-102, 2011. https://doi.org/10.6110/KJACR.2011.23.2.095
  9. Han, J S., Han, G. S., Han, H. S., Han, C., Geothermal Pump Heating and Cooling System HanLim Won Pub. Seoul pp 4-13, 2005.

Cited by