DOI QR코드

DOI QR Code

Energy Coordination of Cascaded Voltage Limiting Type Surge Protective Devices

종속 접속된 전압제한형 서지방호장치의 에너지협조

  • 이복희 (인하대학교 IT공대 전기공학부) ;
  • 신희경 (주식회사 엘피에스코리아)
  • Received : 2012.10.16
  • Accepted : 2012.12.20
  • Published : 2013.02.28

Abstract

For the purpose of designing and applying optimum surge protection, one of the essential points is to take into account the energy coordination between cascaded surge protective devices(SPDs) and it is important to obtain an acceptable sharing of the energy stress between two cascaded SPDs. In this paper, in case of two voltage-limiting SPDs connected in parallel, the amount of splitting impulse current and energy that flow through each SPDs is investigated as a function of the protective distance. As a result, the energetic coordination between cascaded SPDs is strongly dependent on the voltage protection level of SPDs and the protective distance. It was confirmed that the sharing of the energy between two cascaded SPDs and the limited voltage levels are appropriate when the voltage protection levels of both upstream and downstream SPDs are the same.

Keywords

References

  1. KS C IEC 62305-4; Protection against lightning - Part 4 : Electrical and electronic systems within structures, pp. 83-84, 2007.
  2. Korea Electric Association ; Korea Electro-technical Commision Guidance - Technical Guide for selection and application of surge protective devices in low-voltage power systems, pp.10-12, 81, 2011.
  3. B. H. Lee, D. M. Lee, D. C. Cheong, S. B. Lee, and S. C. Lee, " Protection Effects According to the Conditions of Installations of SPDs for Information-Oriented Equipments", J. KIIEE, Vol.21, No.1, pp.35-41, 2007. https://doi.org/10.5207/JIEIE.2007.21.1.035
  4. ANSI/IEEE C62.41.1 Guide on the Surge Environment in low - voltage(1000V and less) AC Power Circuits pp.39-27, 2002.
  5. KS C IEC 61643-12; Low-voltage surge protective devices - Part 12 : Surge protective devices connected to low-voltage power distribution systems - Selection and Application principles, pp. 27-38, 2007.
  6. J. He, Z. Yuan, J. Xu, S. Chen, J. Zou, and R Zeng, "Evaluation of the effective protection distance of low-voltage SPD to equipment", IEEE Trans. Power Delivery., Vol. 20, No. 1, pp.123-130, 2005. https://doi.org/10.1109/TPWRD.2004.835254

Cited by

  1. Protection Characteristics of Two-Stage Cascade SPD Systems vol.27, pp.5, 2013, https://doi.org/10.5207/JIEIE.2013.27.5.095
  2. Energy Coordination between Cascaded Voltage Limiting Type SPDs in Surge Currents due to Direct Lightning Flashes vol.28, pp.5, 2014, https://doi.org/10.5207/JIEIE.2014.28.5.068
  3. Influences of the Length of Connecting Leads on the Energy Coordination in Coordinated SPD Systems vol.28, pp.6, 2014, https://doi.org/10.5207/JIEIE.2014.28.6.091
  4. Characteristics of Overvoltage Protection with Cascade Application of Surge Protective Devices in Low-Voltage AC Power Circuits vol.15, pp.3, 2015, https://doi.org/10.4316/AECE.2015.03022