DOI QR코드

DOI QR Code

Analysis on Characteristics of Core and Winding Vibration in Cast Resin Transformer

몰드변압기 철심과 권선 진동 특성분석

  • 김종민 (한국전기안전공사 전기안전연구원 진단기술연구팀) ;
  • 최명일 (한국전기안전공사 전기안전연구원 진단기술연구팀) ;
  • 김영석 (한국전기안전공사 전기안전연구원 진단기술연구팀) ;
  • 방선배 (한국전기안전공사 전기안전연구원 진단기술연구팀) ;
  • 송길목 (한국전기안전공사 전기안전연구원 진단기술연구팀)
  • Received : 2012.07.11
  • Accepted : 2012.09.11
  • Published : 2012.10.30

Abstract

In this paper, The cast resin transformer's vibration is measured using noncontact raser vibrometer(LV110D). The vibration characteristics of transformer windings and core are analyzed for relation between vibration magnitude and cause. Using the analysis results, the technique is presented to diagnose cast resin transformer. which is able to diagnose transformer' deformation in winding and core geometry. The magnetostriction and electromagnetic force act on the core and windings, causing them to vibrate. The vibration from windings and core penetrates into transformer cast resin and reaches the outside walls. The fundamental frequency of the core and windings vibration signal is twice that of the power frequency(120Hz). The results show that the magnitude of core vibration is linear to driving voltage amplitude and magnitude of windings vibration is increased to loading current under the some level and then stabilized.

Keywords

References

  1. Ji Shengchang, "Research on Extraction Technique of Transformer Core Fundamental Frequency Vibration Based on OLCM" IEEE Transactions on power delivery, vol. 21, no. 4, oct, 2006.
  2. Lavelle, Juan C, "Failure Detection Transformers Using Vibration Analysis" Dept. of Electrical Engineering and Computer Science, M.I.T., Cambridge, MA, 1986.09.
  3. S.Y Yoo, J.S Lee, U.K Lee, M.G Noh, "Magnetostriction Modeling for the Analysis of Electromagnetically Induced Vibration of Transformers ", Journal of the Korean Society of Precision Engineering Vol. 25, No. 1, 2008.01.
  4. S.H Lee, C.G Kang, J.C Kim, "A study on the modelling of power transformer winding vibration", '94 KIEE summer conf., pp.216-218, 1994.07.
  5. S.J Kim, W.Y Pa가, S H Lee, Y.D Kim, "A study on the vibration phenomenon of running power transformer(154kV single phase)", 2008 KIEE autumn conf., pp. 144-146, 2008.09.
  6. Y.K Chung, J.W Jung, J.C Kim, H.R Kwak, "FFT and AR Coefficient Analysis of Vibration Signal in Mold Transformer ", Journal of the Korean institute of illuminating and electrical , Vol. 12, No. 4, pp. 136-145, 1998.
  7. Y.H Yoon, C.H You, J.C kim, C.S Chung, J.J Lee, "Fault Discrimination of Power Transformers using Vibration Signal Analysis ", Trans. KIEE, Vol. 48A, No. 1, 1999.01.
  8. V. A. Rusov, "Monitoring clamping forces in windings and cores of large power transformers using their vibration characteristics",(in Russian) trasl Electric power plant elektricheskie stanzii, vol. 6. pp. 52-57, 1988.
  9. Z. Berler, A. Goluber, and V. Rusov et al., "Vibro-acoustic method of transformer clamping presure monitoring", in Proc. conf. IEEE Int. Symp. electrical Insulation, Anaheim, CA, Apr. 2-5, 2000, pp. 263-256.