Development of UV Corona Camera for the Detecting of Discharge on Power Facility using UV Transmittance Improvement Filter

UV 투과율 향상 필터 기술을 이용한 전력설비 방전 검출용 자외선 코로나 카메라 개발

  • 김영석 (한국전기안전공사 전기안전연구원) ;
  • 최명일 (한국전기안전공사 전기안전연구원) ;
  • 김종민 (한국전기안전공사 전기안전연구원) ;
  • 방선배 (한국전기안전공사 전기안전연구원) ;
  • 송길목 (한국전기안전공사 전기안전연구원)
  • Received : 2012.09.17
  • Accepted : 2012.10.24
  • Published : 2012.11.01

Abstract

UV inspection technology is being used for predictive maintenance of power facility together with IR-thermography and ultrasonic devices. In this paper, the UV corona camera design, fabrication, and perform a simple test to be take advantage of the diagnostic equipment. The UV corona camera developed a $6.4^{\circ}{\times}4.8^{\circ}$ of the field of view as a conventional camera to diagnose a wide range of slightly enlarged, and power equipment to measure the distance between the camera and the distance meter has been attached. The transmission between 250 to 280nm was 11% ($12.5%{\times}88%{\times}98%$) by combing the transmission on absorption film, window and other filter(UG 5, nickel sulphate and so on). In a distance of 5m with the UV corona camera it is possible to detect partial discharge with a PD level of 2.5pC and a RIV level of $3.6dB{\mu}V$.

Keywords

References

  1. 한국전기안전공사 전기재해통계분석, pp. 57-63, 2011
  2. Kil-Mok Shong, Sun-Gu Kim, Woon-Ki Han, Young-Seok Kim, Jin-Su Jung and Hyoung-Jun Choi, "Recognition and Detection of Corona Discharge on Porcelain Insulators at 22.9kV Distribution Line Using UV-Camera", XVth International Symposiumon High Voltage Engineering, 2007
  3. 정종만, 곽현관, 김한홍, "자기 현수애자의 누설전류 불량판정기준", 대한전기학회 전기설비부문회 추계학술대회 논문집, pp. 413-418, 2010
  4. Wenjun Zhou, Han Li, Xiao Yi, Jun Tu and Jianhui Yu, "A Criterion for UV Detection of AC Corona Inception in a Rod-plane Air Gap", IEEE Transactions on Dielectrics and Electrical Insulation, VOL.18, NO.1, pp.232-237, 2011 https://doi.org/10.1109/TDEI.2011.5704514
  5. Vasquez-Arnez, R.L.; Jardini, M.G.M.; Masuda, M.; Carita, L.A.; Jardini, J.A, "Preventive inspection of line insulators through corona emission: A case study ", Transmission and Distribution Conference and Exposition, 2010 IEEE PES, pp. 1-6, 2010.
  6. 김영석, 송길목, 방선배, 김종민, 최명일, "광학렌즈가 부착된 자외선 센서 어레이를 이용한 폴리머 애자의 코로나 방전신호 분석과 판별방법 연구", 대한전기학회 하계학술대회 논문집, pp.2165-2166, 2010
  7. 김영석, 최명일, 김종민, 방선배, 송길목, "노출 충전부의 코로나 방전에 따른 자외선 특성 분석", 한국조명전기설비학회 춘계학술대회, pp.39-40, 2010.
  8. M. Lindner, S. Elstein, P. Lindner and J. M. Topaz, A. J. Phillips, "Daylight Corona Discharge Imager", High Voltage Engineering Symposium, pp.22-27, 1999.
  9. "Methods of Measurement of Radio Influence Voltage(RIV) of High-Voltage Apparatus", NEMA Standard Pulication No. 107, 1987.
  10. IEC 60270, "High-voltage test techniques-Partial discharge measurements", 2000.